• Title/Summary/Keyword: 액백

Search Result 1, Processing Time 0.017 seconds

A Study on Dynamic Characteristics of a Refrigeration System by Controlling the Evaporator Superheat (증발기 과열도제어에 따른 냉동장치의 동특성에 관한 연구)

  • 김재돌;오후규;윤정인
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.19 no.8
    • /
    • pp.2012-2021
    • /
    • 1995
  • An experimental study was performed for the analysis of dynamic characteristics of refrigeration system by controlling the evaporator superheat. Experimental data have been taken utilizing two different devices, thermostatic expansion valve(T.E.V.) and electronic expansion valve(E.E.V.), for the control of the evaporator superheat. The ranges of parameters, such as superheat, mass flow rate of refrigerant and inlet temperature of evaporator were 5-30.deg. C 90-170 kg/h and 10-25.deg. C, respectively. The data taken from the T.E.v.and E.E.v.were discussed with the control of the superheat, pressure drop, refrigerating capacity, compression work, evaporating temperature, condensing temperature and COP affecting performance characteristics of refrigeration system. In case of the refrigerant flow control with T.E..V., the superheat and pressure drop of the evaporator varied periodically, but the control with E.E.V., the parameters were very stable. In E.E.v.control, refrigerating capacity, compression work and evaporating temperature were decreased with increasing superheat, and the highest COP was obtained in the range of superheat from 5.deg. C to 15.deg. C.