• Title/Summary/Keyword: 액기분리기

Search Result 2, Processing Time 0.015 seconds

A Study on the Characteristics of Refrigeration System Installed with Precooler, and Liquid-Vapor Separator after Expansion Device (과냉각기와 팽창장치 후 액기분리기를 적용한 냉동시스템 성능특성 연구)

  • Yun, Sang-Kook
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.35 no.1
    • /
    • pp.40-45
    • /
    • 2011
  • The purpose of research is to understand the characteristics of refrigeration system having a liquid-vapor phase separator after expansion device and precooling heat exchanger. After expansion process of typical refrigerant of freezer, R134a, the cold vapor of the expanded refrigerant mixture is separated in the liquid-vapor separator and introduced in the precooling heat exchanger to enable the liquid refrigerant to be subcooled. The analysis results showed that the increasing rate of refrigeration capacity and COP can be 8.6% and 1.4%, each. The cause of these performance improvements is due to the difference of the slope of saturated vapor and saturated liquid lines in Mollier diagram of refrigerant.

Theoretical study on the performance improvement of refrigeration system installed with ejector entraining expansion gases after expansion process (이젝터를 적용한 팽창기체 흡입 냉동시스템의 성능향상 해석 연구)

  • Yun, Sangkook
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.38 no.7
    • /
    • pp.828-833
    • /
    • 2014
  • In this paper, the performance characteristics for newly developed ejector refrigeration system, which is that the part of saturated vapor from liquid-vapor separator after ejector expansion process is entrained in ejector, and the saturated liquid flows in the evaporator and compressed with the rest of vapor in separator, is studied. The reasons of the performance improvement of refrigeration system are that the refrigeration capacity is increased due to quality reduction after iso-entropic expansion process by ejector and the compression work is reduced because of the relatively high pressure of vapor refrigerant before compression process. The comparison results of the ejector system entraining expansion gases with the present residential freezer show that the COP increases to 27.8% maximum in case of the pressure drop to 65% of high pressure of freezer, and to 40.1% for 75% pressure drop of refrigerant R401A. The COP improvement rate with 20%~60% pressure lift in diffuser of ejector is only 2.6%~3%.