신안풍력발전소 풍력터빈의 성능저하 분석 (Analysis on Wind Turbine Degradation of the Shinan Wind Power Plant)

  • 김현구
    • 한국태양에너지학회 논문집
    • /
    • 제33권4호
    • /
    • pp.46-50
    • /
    • 2013
  • This paper investigated wind turbine degradation quantitatively by analyzing the short-term operation records of the Shinan Wind Power Plant. Instead of a capacity factor which is needed to be normalized its variability due to monthly wind speed change, this study suggests an analysis method by taking the difference between the theoretical power output calculated from the nacelle wind speed and actual power output as the quantitative index of performance degradation. For three-year SCADA data analysis of the Shinan Wind Power Plant, it was confirmed that power output degradation rate of 0.54% per year. This value is within the average reduction rate 0.4%/year~0.9%/year of normalized capacity factor of the onshore wind power plants in U.K. and Denmark; however, lower than the rate 2%/year of Canadian wind power plants.

라이다(LiDAR) 측정을 이용한 나셀전달함수의 유도 (Derivation of Nacelle Transfer Function Using LiDAR Measurement)

  • 김현구;강용혁;윤창열
    • 대한기계학회논문집A
    • /
    • 제39권9호
    • /
    • pp.929-936
    • /
    • 2015
  • 풍력터빈 블레이드의 후단, 나셀 상부에 설치되는 나셀 풍속계는 블레이드 회전에 따른 후류효과 및 나셀형상 등으로 인하여 풍력터빈에 입사되는 자연풍속과는 다른 왜곡된 풍속을 측정한다. 풍력터빈 출력성능의 신뢰성 확보를 위해서는 나셀풍속을 자연풍속으로 보정하는 나셀전달함수를 유도하여 성능곡선을 보정하여야 한다. 본 연구에서는 전라남도 비금도 북부 해안에 건설된 신안풍력발전소에서 지상기반 원격탐사 장비인 라이다(LiDAR)를 설치하여 나셀 풍속계와 동일 높이에서의 자연풍속을 측정하였다. 나셀풍속을 자연풍속으로 보정하는 기존의 단순회귀분석에 의한 선형 나셀전달함수를 개선하기 위하여 다중회귀분석에 의한 비선형 나셀전달함수를 유도하였다. 나셀전달함수로 계산한 보정풍속을 풍력터빈 출력곡선에 대입하여 산출한 이론 발전량과 실제 발전량의 잔차를 비교하여 개선효과를 검증하였다. 다중회귀분석 나셀전달함수는 단순회귀분석에 비해 풍속의 표준오차는 9.4% 감소하였으며, 발전량 잔차 분포의 평균은 6.5% 감소하여 개선효과가 있음을 확인하였다.