Numerical Study on the Improvement Heat and Smoke Control System in Old Subway Station on Train Fire (수치해석을 통한 노후 지하철 역사 내 열차 화재 시 제연모드 개선에 관한 연구)

  • Kim, Hyo-Gyu;Baek, Doo-San;Yoo, Yong-Ho
    • Fire Science and Engineering
    • /
    • v.31 no.3
    • /
    • pp.88-96
    • /
    • 2017
  • The subway can transport a lot of people at a certain route at once, and the railway and the platform are underground, so it is advantageous to use the ground space efficiently. But If a fire occurs in a subway that is used by an unspecified number of people, such as the Daegu Subway Fire Disaster, many casualties can occur. As a result of the previous research, it was confirmed that the performance of the ventilation system of the old subway platform was remarkably degraded. Therefore, in this study, based on the experimental results of the previous research, we confirmed the flow of the hot and CO flows according to the ventilation mode in the case of fire by three - dimensional numerical analysis. As a result, it was found that the old ventilation system could not maintain the hot air temperature below the reference value for 4 minutes based on the evacuation time of the platform, and when the ventilation performance was enhanced by adding Oversized Exhaust Ports at the upper part of the platform, And the temperature of the heat flow can be maintained.

Analysis of Passenger Refuge Model Using EXODUS Refuge Simulator: Case of the Daegu Underground Station Fire (EXODUS 피난시물레이터를 이용한 대구지하역사화재 승객피난모델분석)

  • Lee, Chang-Hyun;Jang, Yong-Jun;Park, Won-Hee;Kim, Dong-Hyeon
    • Proceedings of the KSR Conference
    • /
    • 2007.05a
    • /
    • pp.1807-1813
    • /
    • 2007
  • The study aims at analyzing an underground station refuge model using EXODUS, one of the refuge simulation programs. The model for simulation is the Daegu Subway (Joongang-ro station). The details of the accident are referred to as the simulation condition the refuge time of traveling from the $3^{rd}$ basement platform to the $1^{st}$ basement is mainly calculated, with passengers numbering 1,000 including 329 at car 1079, 320 at car 1080, and 360 who are not on board. Reference data is used to set up the position of passengers. CFAST fire simulator is also used, and a fast curve among the $t^2$ growth curves, selected as fire growth scenario. The zone is divided into a total of 24 including 18 at the $3^{rd}$ basement platform and 6 at the $2^{nd}$ basement the $1^{st}$ basement is excluded in the fire simulation, however.

  • PDF

The Passenger Evacuation Simulation Using Fluent and EXODUS (Fluent 와 EXODUS를 이용한 승객피난 시뮬레이션)

  • Jang, Yong-Jun;Park, Won-Hee;Lee, Chang-Hyun;Jung, Woo-Sung
    • Proceedings of the KSR Conference
    • /
    • 2007.11a
    • /
    • pp.1346-1353
    • /
    • 2007
  • The simulation analysis of fire-driven flow and passenger evacuation in Daegu subway station, Chung-Ang, have been performed. The first location of outbreak of fire is inside passenger car in the third basement in Chung-Ang station. The smoke flow in the second and third basement has been analyzed using FLUENT 6.2. The CO(carbon monoxide) and temperature distribution in the train units and station platform have been obtained and transferred to input data for evacuation simulation. The highest temperature in the train units was 1500K. For the simulation of passenger evacuation, EXODUS has been used for whole basements (level 1${\sim}$ level 3) in the station. Total number of people was assumed to be one thousand and 640 were placed inside train and 360 were placed outside train. In evacuation simulation, an average of 135 passengers were killed and an average time to evacuate takes 10min 19sec. The main evacuation routes used by passengers were investigated and the cause of death was identified by evacuation simulation.

  • PDF

Experimental and Numerical Studies on Heat/Smoke Behavior due to a Fire on Underground Subway Platform (II) - Numerical Approach - (지하철 역사 승강장 화재발생시 열/연기 거동 분석을 위한 실험 및 수치 연구(II) - 수치적 접근 -)

  • Chang, Hee-Chul;Kim, Tae-Kuk;Park, Won-Hee;Kim, Dong-Hyeon
    • Fire Science and Engineering
    • /
    • v.20 no.3 s.63
    • /
    • pp.15-20
    • /
    • 2006
  • In this study the flow characteristics of smoke and heat on a bank type platform of the underground subway station are studied numerically by considering two different emergency operation modes. Effects of the natural flow through the tunnel and the stair ways are considered in the numerical simulations by using the measured velocities presented in Part I as the boundary condition. Distributions of heat, smoke, visible range and toxic gas on the platform are analysed for different smoke extraction flowrates corresponding to the two different emergency operation modes. The numerical results show that the extraction flowrate affects the smoke control performance significantly by improving the smoke removal performance as the extraction flowrate is increased.

A Study on Smoke Extract Vents in a Subway with Screen door by Evacuation Performance Evaluation through RSET vs. ASET based on Computer Simulations (스크린도어가 설치된 지하철 승강장의 대피안전성 평가를 통한 제연환기구의 방재성능 개선방안 연구)

  • Park, Hyung-Joo;Lee, Young-Jae;Shin, Dong-Cheol;Baek, Dong-Ho
    • Journal of the Korean Society for Railway
    • /
    • v.10 no.5
    • /
    • pp.511-519
    • /
    • 2007
  • This study provides comprehensive design improvements covering technical issues concerning life safety matter In case of fire train stoppage in the middle of a tunnel. Recently Government announced that most of subway platforms will have screen doors in 3 years. Therefore, many fire safety engineers considered that they may contribute on life safety on train stoppage in tunnel. Especially The screen door can protect platform from smoke along tunnel ceiling when fire train stopped in tunnel. The study showed that platform ventilation ducts and the a tunnel ventilation chimney in the middle of tunnel in exiting subway tunnel could not guarantee life safety ability in terms of RSET vs. ASET comparison. Furthermore during evacuation process many peoples may be threatened from the smoke spread from the origin of fire. Although only additional vertical route can be installed in tunnels In order to decrease RSET, it will costs high or no spaces remains in outside on the road. The study suggested that increase of ASET can be best solution without additional escape route, therefore alternative design methods suggested on the base of simulation results. Finally the study shows alternative methods can give good result in terms of evacuation performance evaluation. The evacuation performance evaluation helps the decision-maker to determine the preferred alternatives or upgrades to existing tunnel infrastructure and other measure to meet safety objectives. Finally, the study details the effectiveness of measures the can be taken to reduce the risk of incidents in subway tunnels.

Pressure Differentials in the Elevator Lobby Depending on the Reference Pressures of the Pressurizing Dampers (급기가압 댐퍼의 설정 기준압에 따른 부속실 차압 특성 연구)

  • Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.21 no.4
    • /
    • pp.12-17
    • /
    • 2007
  • This paper investigated pressure differentials in the elevator lobby depending on reference pressures of the pressurizing damper using FDS fire modeling. The results showed the temperatures and pressures in the contained fire room with small leak gaps can increase significantly. Setting reference pressure of the pressurizing dampers to 0 Pa can cause reduction of real pressure differentials and air velocity to resist smoke flow. This would cause smoke movement from fire room to elevator lobby which should be safe area for evacuation.

Experimental Study for the Capacity of Ordinary and Emergency Ventilation System in Deeply Underground Subway Station (대심도 지하역사 승강장 및 대합실 평상시/비상시 급·배기 풍량에 대한 실험적 연구)

  • Jang, Yong-Jun;Lee, Ho-Seok;Park, Duck-Shin
    • Journal of the Korean Society for Railway
    • /
    • v.15 no.6
    • /
    • pp.579-587
    • /
    • 2012
  • Shin-gumho station in Seoul underground subway have been selected to be experimentally investigated and analyzed for the real air supply & exhaust capacity compared to the original capacity of ordinary and emergency condition. The depth of Shin-gumho station is 43.6m which consists of the island-type platform ($8^{th}$ floor in underground) and a two-story lobby (first & second floor in underground). An emergency staircase connects between the platform and the lobby. Hot-wire anemometer, capture hood, wind vane & velocity meter and data acquisition systems are employed to perform the automatic measurement in this experiment. For ordinary case, air supply and exhaust capacity in the lobby were reduced by 34% and 46% compared to the original capacity, respectively. Air supply and exhaust capacity in the platform were reduced by 66% and 38%, respectively. For emergency case, air supply in the lobby was reduced by 42% and air exhaust in the platform was reduced by 28% compared to the original capacity. Therefore, air pollution in the station is expected to be worse in the ordinary environment and smoke control capability in the platform will be weakened in case of fire emergency.

성능위주의 배연설비를 위한 지하철 승강장 화재시뮬레이션에 관한 연구

  • 김용주;이동호;김종원;조정훈
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2001.11a
    • /
    • pp.225-231
    • /
    • 2001
  • 최근 인구 증대 및 도시 집중화에 따른 지상공간 부족의 대안 및 택지 이용도 효율 방안으로 지하공간 개발의 필요성이 증대되고 있다 특히 날로 증대되고 있는 지하공간에서의 문제점으로 설계 및 용도에 적합한 환기 시스템의 도입 및 운영의 미흡으로 공기질 악화 현상과 국민 보건상의 문제로 노출되고 있는 실정이다. 환기시스템은 일상적 공간환기는 물론 화재시의 배연기능을 포함한다. 따라서, 정상적인 작동(일반 환기)과는 별도로 비정상 환경(화재시의 배연)에서의 중요성이 인식되고 있다. 따라서, 시스템 설계 오류는 화재발생시 중대한 인명피해로 연결됨으로서 그 중요성은 아무리 강조하여도 지나침이 없다 이미 미국, 일본, 노르웨이 등의 선진 외국에서는 지하공간의 최적환경 개선은 국민 삶의 질 향상이라는 관점 하에 꾸준히 진행되어오고 있다. $^{(1~3)}$ 우리나라에서도 서울1기 지하철을 시작으로 교통난의 해소를 위하여 2005년까지 총연장 60km에 이를 것으로 전망됨에 따라 지하공간의 공기질 개선 및 화재시의 배연설비의 최적화가 요구된다.(중략)

  • PDF

The Experimental Study on the Leakage of Automatic Pressure Differential·Overpressure Control Dampers by Increasing the Number of Damper Operation (자동차압·과압조절형댐퍼의 개폐동작횟수 증가에 따른 누설량 실험 연구)

  • Shin, Pyung-Shik;Kim, Hak-Joong
    • Fire Science and Engineering
    • /
    • v.30 no.2
    • /
    • pp.56-61
    • /
    • 2016
  • Recently, Since buildings are bigger and higher, the damage of human life can be increased by fire flame and smoke in fire. Smoke control system is necessary to decrease this damage. Therefore, Air supply pressurization smoke control system is applied to vestibule of escape stairway. NFSC requires pressure differential of above 40 Pa, but pressure differential is excessively overpressure in the field. It is known that the cause of this over pressure differential is much leakage of damper. Over pressure differential can bad effect to escaper by pressurizing the door. Analyze the real leakage of damper by increasing the number of dampers operation for identifying this problems. The result of testing, the leakage has difference between new dampers and increased the number of operation dampers. As the static preassure increase, the leakage difference increase. Comparison with preceding study, this result has similar linear tendency.