• Title/Summary/Keyword: 슬림 루버 핀

Search Result 1, Processing Time 0.015 seconds

Experimental Study on the Airside Performance of Aluminum Heat Exchangers Having Slim Louver Fins (슬림형 루버 핀이 장착된 알루미늄 열교환기의 공기측 전열 성능에 대한 실험적 연구)

  • Kim, Nae-Hyun;Cho, Honggi
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.41 no.9
    • /
    • pp.587-595
    • /
    • 2017
  • Recent trends in slim air conditioners require heat exchangers of reduced flow depth. In this study, slim louver fin geometry was obtained using predictive correlations. The deduced geometry yielded 10 mm flow depth, 0.9 mm louver pitch, and $35^{\circ}$ louver angle. Samples were made and tests were conducted. The new slim sample yielded 36% higher j factor and 2.3% higher f factor compared with those of the standard sample. This implies that 26% reduction of heat exchanger volume was possible by reducing the flow depth. In addition, the $j/f^{1/3}$ of the slim sample was 55% larger than that of the standard sample. Furthermore, the results are compared with predictions made using existing correlations.