• Title/Summary/Keyword: 수직형 유하액막 흡수기

Search Result 2, Processing Time 0.016 seconds

Effect of Wavy Flow of Vertical Falling Film on the Absorption Performance (흡수성능에 미치는 수직 액막 파동의 영향에 관한 연구)

  • 김정국;조금남
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.2
    • /
    • pp.194-201
    • /
    • 2004
  • In the present study, the improvement of absorption characteristics on combined heat and mass transfer process in a falling film of a vertical absorber by change of geometric parameters were studied experimentally and analytically. The energy and diffusion equations are solved simultaneously to give the temperature and concentration variations at the liquid solution-refrigerant vapor interface and at the wall. Absorption behaviors of heat and mass transfer were analyzed through falling film of the LiBr aqueous solution contacted by refrigerant vapor in the absorber. Effects of film Reynolds number, geometric parameters by insert device (spring) and flow pattern on heat and mass transfer performances have been also investigated. Especially, effects of the flow pattern by geometric parameters have been considered to observe the total heat and mass transfer rates through falling film along the absorber. As a numerical and experimental result, maximum absorption rate was shown at the wave-flow by insert device (spring). The error ranges between experiment and analysis were from 5.8 to 12% at Re$_{f}$ > 100.0.

Influence of Spring on The Absorption Performance of a Vertical Absorber Tube (수직 흡수전열관의 흡수성능에 미치는 스프링의 영향)

  • 김정국;조금남
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.10
    • /
    • pp.825-832
    • /
    • 2002
  • The present study investigated the enhancement of the absorption performance by the spring wrapped around the outer surface of the vertical falling film absorber tube. Heat and mass transfer enhancements were experimentally investigated, and flow visualization was performed to observe the wettability and flow pattern of the solution. The key experimental parameters were spring diameter (0.5, 1.0 mm) and spring pitch (1, 3, 10 mm), film Reynolds number (50~150), and concentration of LiBr-$H_2O$ solution (55, 60, 65 wt%). As the spring diameter was increased, the absorption mass flux, Sherwood number, Nusselt number, heat flux, and heat transfer coefficient were increased The Nusselt and Sherwood numbers showed the maximum at the spring pitch of 3mm, and the ratio of pitch to diameter of approximately 3 and 6 for the spring diamter of 0.5 mm, respectively.