• Title/Summary/Keyword: 빙체적충전율

Search Result 2, Processing Time 0.016 seconds

The Heat Exchangers Performance Experiment for a Field Application Ice Slurry Cooling System (현장 적용 아이스슬러리 시스템의 열교환기 성능 실험)

  • Lee, Sang-Hoon;Yoo, Ho-Seon;Lee, Yoon-Pyo
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1002-1007
    • /
    • 2009
  • The research are performed to check the characteristics of the ice slurry transport system for the district cooling. The system are installed at the 1st floored building which is as large as the $1204\;m^2$ ($86\;m{\times}14\;m$). Three kinds of heat exchanger are selected, such as, plate, spiral and shell & tube type, to apply to the ice slurry systems. Experiment was done in the two cases. The first case, circulation water flow fixed at the design conditions for the state to change the flow of the supply of ice slurry. The second case, Ice slurry flow fixed at the design conditions for the state to change the flow of circulation water. Both side of Energy balance was calculated. The performance of plate heat exchanger is higher than others and it's enthalpy effectiveness is higher too.

  • PDF

Ice slurry transporting and branching characteristics for the district cooling (지역냉방을 위한 아이스슬러리 시스템의 수송 및 분기 특성)

  • Lee, Sang-Hoon;Yoo, Ho-Seon;Lee, Yoon-Pyo;Lee, Chang-Jun;Kwon, Hyeok-Min
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.662-667
    • /
    • 2009
  • The research are performed to check the characteristics of the ice slurry transport system for the district cooling. The system are installed at the 1st floored building which is as large as the $1204\;m^2$ ($86\;m{\times}14\;m$), and the pumping power and branching characteristics are measured by transporting of the ice slurry. The ice slurry transporting pipe is as long as 200 m. For the same cooling load, the higher IPF is, the lower the transporting flow rate and the pumping power are. But when the IPF is higher than 15%, no less decrease of the pumping power does happen. For the branching characteristics, through the branch pipe where the flow resistance is higher, the higher IPF is measured. A little higher IPF is measured at the thermal expansion branch.

  • PDF