• Title/Summary/Keyword: 부분부하 운전

검색결과 87건 처리시간 0.026초

여름철 공조시스템의 최적 운전 제어 방식 (Optimal air-conditioning system operating control strategies in summer)

  • 허정호
    • 설비공학논문집
    • /
    • 제9권3호
    • /
    • pp.410-425
    • /
    • 1997
  • Buildings are mostly under part load conditions causing an inefficient system operation in terms of energy consumption. It is critical to operate building air-conditioning system with a scientific or optimal manner which minimizes energy consumption and maintains thermal comfort by matching building sensible and latent loads. Little research has been performed in developing general methodologies for the optimal operation of air-conditioning system. Based on this research motivation, system simulation program was developed by adopting various equipment operating strategies which are energy efficient especially for humidity control in summer. A numerical optimization technique was utilized to search optimal solution for multi-independent variables and then linked to the developed system simulation model within a mam program. The main goal of the study is to provide a systematic framework and guideline for the optimal operation of air-conditioning system focusing on air-side. For given cooling loads and ambient outdoor conditions the optimal operating strategies of a commercial building are determined by minimizing a constrained objective function by a nonlinear programming technique. Desired space setpoint conditions were found through evaluating the trade-offs between comfort and system power consumption. The results show that supply airflow rate and compressor fraction play main roles in the optimization process. It was found that variable setpoint optimization technique could produce lower indoor humidity level demanding less power consumption which will be benefits for building applications of humidity problem.

  • PDF

현장에서 운전중인 터보냉동기의 성능 측정과 전력 소비량 예측 (Field Performance Test and Prediction of Power Consumption of a Centrifugal Chiller)

  • 장영수;신영기;김영일;백영진
    • 대한기계학회논문집B
    • /
    • 제25권12호
    • /
    • pp.1730-1738
    • /
    • 2001
  • This paper presents an overview of testing and analyzing field performance of a centrifugal chiller which has a rated capacity of 200 RT(703 kW). Field data of a chiller installed in the cleanroom research building of KIST has been collected far performance analysis. The operating data included start-up, shut-down, and quasi-static state where cooling capacity and compressor power consumption varied cyclically. It was found that the steady-state thermodynamic model could be applied to relate the cooling capacity and COP under quasi-static conditions. The results led to finding the required cooling load pattern and a possible energy saving method. This study provides a method of evaluating performance of a large capacity centrifugal chiller in which field test is necessary.

축열형 지열원 냉난방 시스템의 단기 성능 특성 연구 (Capacity Modulation of a Ground Source Multi-Heat Pump in the Part Load Condtions)

  • 김남태;조찬용;최종민
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 추계학술대회 초록집
    • /
    • pp.119-119
    • /
    • 2010
  • 무한 지속 가능한 지열 에너지를 활용한 공조시스템인 지열원 냉난방 시스템은 기존의 공조 시스템보다 열원이 안정적이기 때문에 높은 효율과 우수한 성능을 가지므로, 기후변화협약 대응의 주요수단으로서 기술개발과 보급이 증대되고 있다. 본 연구에서는 대수층 축열 지열원 열펌프 시스템에 대한 실증 연구를 통하여 대수층 축열 지열원 열펌프 시스템의 하절기 냉방 성능을 분석하였다. 대수층 축열 냉난방 시스템은 주입정과 양수정의 2개의 우물공이 설치되어 있으며, 겨울 난방 운전 중에 한 개의 우물공으로부터 지하수를 열펌프로 유입한 후 낮은 온도의 지하수를 타 우물공에 축열하고, 하절기에 겨울에 저온으로 축열된 우물공으로부터 지하수를 열펌프로 유입하여 온도가 증가된 지하수를 타 우물공에 주입한다. 즉, 계절별로 열펌프에서 생성된 냉수와 온수의 대수층 축열을 위하여 계절별로 주입정과 양수정이 바뀌게 된다. 본 연구의 대수층 축열 지열원 열펌프 시스템의 2009년 8월의 주요일자별 시스템 운전 중의 평균 냉방 열펌프 유닛 COP와 냉방 시스템 COP는 각각 4.7과 3.4이상의 우수한 성능을 나타냈다. 또한, 모든 일자에 대하여 외기온도가 $31.6^{\circ}C$$22^{\circ}C$까지 변화가 크게 나타났지만 열펌프 유닛 COP와 시스템 COP의 변화는 미소하였다. 이는 양수정으로부터의 지중 순환수가 운전기간 중에 $17.5^{\circ}C$로 일정하게 유지되었기 때문이다. 양수정과 주입정 사이에 5개의 관측공을 설치하였으며, 양수정 측에 인접한 관측공의 온도는 거의 변화가 없었으며, 단기간이지만 널리 사용되고 있는 수직밀폐형 시스템과 달리 지속적인 냉방운전 중의 양수 온도의 증가는 발생하지 않아 안정적인 성능을 나타냈다. 주입정에 인접한 모니터링 홀의 온도는 심도가 깊은 곳의 온도가 낮은 곳보다 높게 나타났다. 이는 냉방 운전 시 열펌프 유닛의 실외열교환기에서 지중 순환수가 냉매로부터 열을 취득하여 온도가 상승하면서 주입정측에 온열이 축열이 진행되었기 때문으로 분석되며, 하절기의 냉방 운전 시간이 증가할 경우 축열 효과는 더욱 증가할 것으로 예상된다. 양수정과 주입정 중간의 모니터링 홀의 온도는 2009년 8월 가동 중에 온도변화는 없었는데, 이는 양수정과 주입정 사이의 열간섭이 발생하지 않았기 때문으로 분석된다. 일자별로 운전 중의 열펌프 유닛 COP는 차이가 없었지만, 운전 및 정지 시간을 모두 포함한 시스템 소비전력과 냉방용량을 모두 합산하여 산정한 일일 평균 냉방 열펌프 유닛 COP와 냉방 시스템 COP는 일자별로 다소 차이가 발생하였는데, 이는 각 일자별로 열펌프 유닛 가동율의 차이로 인하여 열펌프 유닛 가동 전에 먼저 작동되는 지중순환펌프의 운전 소비전력의 차이와 열펌프의 단속운전 시의 열손실과 추거 소비전력의 차이 때문이다.

  • PDF

"위험한 이야기"에서 오인된 지식

  • 한국원자력산업회의
    • 원자력산업
    • /
    • 제8권9호통권67호
    • /
    • pp.17-27
    • /
    • 1988
  • 최근 일본의 원자력 비판운동은 이방원전의 부하추종운전시험 반대를 계기로 새로운 전개를 보이고 있는데, 이 반대움직임은 선동적인 내용으로 원자력발전에 대한 반대감정을 자극한 광뢰 륭씨 저 ${\ulcorner}$위험한 이야기${\lrcorner}$에 의해서 시작되었다고 할 수 있다. 그러나 이 책의 내용에는 과학적인 지식을 잘못 인식한 주장과 신문기사 및 논문의 인용에 모순과 의문이 많으며, 또한 불확실한 정보에 근거를 둔 내용도 많다. 따라서 일본원자력문화진흥재단에서는 이러한 부분을 분석정리하여 ${\ulcorner}'$위험한 이야기'의 오인${\lrcorner}$이란 자료를 발간하였다. 다음은 이 자료를 요약한 것이다.

  • PDF

2MWe 순환유동상 보일러의 부분 부하 운전 성능 모사 (Performance Simulation of Part Load Operation for 2MWe Circulating Fluidized Bed Boiler)

  • 김태현;최상민;현주수
    • 한국연소학회:학술대회논문집
    • /
    • 한국연소학회 2012년도 제44회 KOSCO SYMPOSIUM 초록집
    • /
    • pp.35-36
    • /
    • 2012
  • Part load operation usually covers large periods of the total operation time on the economic ground and electricity demand in small-scale boilers. Performance analysis of part load behavior is very important for the purpose of boiler operation optimization. A simple thermal calculation approach is applied to predict performance of a pilot-scale circulating fluidized bed (CFB) boiler at part load operation. Verification has been carried out by comparing between calculation results an operation data of the boiler.

  • PDF

ITER AC/DC Converter Control 검증을 위한 Hardware-in-the-Loop Simulation(HILS) System 구축 및 실험 (Implementation and Experiment Result of Hardware-in-the-Loop Simulation(HILS) System for The Verification of ITER AC/DC Converter Control)

  • 서재학;오종석;최정완;신현국;차한주;박인권
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2015년도 추계학술대회 논문집
    • /
    • pp.221-222
    • /
    • 2015
  • ITER AC/DC Converter의 부하는 초전도 코일이며 이에 필요한 컨버터는 총 6종류(2상한:TF, 4상한:PF, CS, VS, CCU/L, CCS)가 있다. 이중 VS 컨버터(${\pm}1050V$, ${\pm}22.5kA$)는 6대가 직렬로 접속되어 운전되고 CS 컨버터(${\pm}1050V$, ${\pm}4.5kA$)는 4대가 직렬로 접속되어 운전한다. 이들 컨버터용 제어기의 개발 단계에서 실 부하상태를 준비하는 것은 어렵기 때문에 $RTDS^{TM}$ (Real Time Digital Simulator)를 이용하여 제어 대상인 High Power 부분과 초전도 코일의 동적 시스템 모델을 HILS(Hardware-in-the-Loop Simulation)로 구축하였다. 본 논문에서는 HILS 구축에 대한 상세한 내용과 이를 활용하여 Control 시스템을 검증한 결과를 서술하였다.

  • PDF

마이크로 가스터빈의 탈설계 운전 성능특성 (Performance Characteristics for Off-design Operation of Micro Gas Turbines)

  • 김동섭;황성훈
    • 한국유체기계학회 논문집
    • /
    • 제7권3호
    • /
    • pp.39-47
    • /
    • 2004
  • Micro gas turbines are designed with low turbine inlet temperature and pressure ratio. To overcome the efficiency defect of the simple cycle, adoption of the recuperator is an inevitable choice. In addition to the design performance, we should also pay attention to the off-design performance of gas turbines since they usually operate at part-load conditions lot a considerable amount of their lifetime. This study analyzes off-design performance characteristics of micro gas turbines and addresses the importance of the recuperation process doting the part load operation. Comparative analyses have been performed to evaluate the part load performance differences among various design and operating options : simple vs recuperative cycles, single vs two shaft configurations, various operating strategies for the single shaft configuration, and current vs advanced engines. Major finding is that maintaining high turbine exhaust temperature is crucial for efficient operation of micro gas turbines.

마이크로 가스터빈 발전시스템의 운전성능 분석 (Analysis of Operation Performance of a Micro Gas Turbine Generator System)

  • 이종준;김동섭
    • 한국유체기계학회 논문집
    • /
    • 제8권5호
    • /
    • pp.13-21
    • /
    • 2005
  • This study aims to analyze operating performance of a micro gas turbine with the aid of detailed measurements of various system parameters. In addition to embedded measurements, parameters such as exhaust temperatures, engine inlet temperatures and fuel flow rates are measured. Variations in measured data and estimated performance parameters are analyzed. Those data are processed to calculate losses along the power transmission line and the net gas turbine performance (power and efficiency based on the gas turbine shaft end) is isolated from the overall system performance. A method to estimate characteristic parameters such as component efficiencies, based on the comparison between measured and predicted performance data, is suggested and exemplified for the full load condition.

마이크로 가스터빈 발전시스템의 운전성능 분석 (Analysis of Operation Performance of a Micro Gas Turbine Generator System)

  • 이종준;김동섭
    • 유체기계공업학회:학술대회논문집
    • /
    • 유체기계공업학회 2004년도 유체기계 연구개발 발표회 논문집
    • /
    • pp.132-139
    • /
    • 2004
  • This study aims to analyze operating performance of a micro gas turbine with the aid of detailed measurements of various system parameters. In addition to embedded measurements, parameters such as exhaust temperatures, engine inlet temperatures and fuel flow rates are measured Variations in measured data and estimated performance parameters are analyzed. Those data are processed to calculate losses along the power transmission line and the net gas turbine performance (power and efficiency based on the gas turbine shaft end) is isolated from the overall system performance. On the basis of the measured data, analytical approach is tried to estimate design characteristic and performance parameters such as component efficiencies and unmeasured temperatures.

  • PDF

마이크로 가스터빈의 탈설계 운전 성능특성 (Performance Characteristics for Off-design Operation of Micro Gas Turbines)

  • 황성훈;김동섭
    • 유체기계공업학회:학술대회논문집
    • /
    • 유체기계공업학회 2003년도 유체기계 연구개발 발표회 논문집
    • /
    • pp.80-87
    • /
    • 2003
  • Micro gas turbines are designed with low turbine inlet temperature and pressure ratio. To overcome the efficiency defect of the simple cycle, adoption of the recuperator is an inevitable choice. In addition to the design performance, we should also pay attention to the off-design performance of gas turbines since they usually operate at part-load conditions for a considerable amount of the time. This study aims at analyzing off-design performance characteristics of micro gas turbines and addressing the importance of the recuperator in the part load operation. Comparative analyses have been performed to evaluate the part load performance differences among various design and operating options : simple vs recuperative cycles, single vs two shaft configurations, various operating strategies for the single shaft configuration (fuel only control, variable speed operation, variable inlet guide vane control), and current vs advanced engines. Major finding is that maintaining turbine at high level is crucial in efficient operation of micro gas turbines.

  • PDF