• Title/Summary/Keyword: 배연

Search Result 495, Processing Time 0.034 seconds

A study on the optimal ventilation and smoke exhaust systems in case of fire in subway stations installed with PSD (PSD가 설치된 지하철 역사 내 화재 시 최적 배연시스템 연구)

  • Kim, Hyo-Gyu;Yoo, Ji-Oh;Kim, Doo-Young
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.20 no.2
    • /
    • pp.527-539
    • /
    • 2018
  • The subway used by many passengers is required to maintain a safe and comfortable environment and PSD (Platform Screen Door) must be installed in the platform after reinforcing the standard in 2003. In the previous research, in case of subway fire to control it, it is necessary to design the optimal ventilation and smoke exhaust system according to equipment capacity of the smoke exhaust system. Therefore, in this study, based on the results of previous research, three-dimensional numerical analysis was performed for the CO gas and smoke flow by the subway ventilation system in case of platform fire. As a result of this study, it was found that in case of emergency, if only the upper-level smoke exhaust system is activated, the risk of evacuation is high due to CO gas (653.8 ppm) and smoke concentration ($768.4mg/m^3$). And when all the smoke exhaust systems are activated and only the fire side PSD is opened, CO gas (36.0 ppm) and smoke concentration ($26.2mg/m^3$) are detected and the propagation range of smoke flow was reduced. When all the smoke exhaust systems are activated and only the fire side PSD is closed, it was analyzed as the most effective ventilation mode in the evacuation environment due to the absence of smoke-recirculation.

Study on Heat and Smoke Behavior Due to the Natural Wind and the Forced Smoke Ventilation for the Fire in an Underground Subway Station (지하역사에서 화재발생시 자연풍 및 강제배연의 유무에 따른 열 및 연기거동 특성 연구)

  • Chang Hee-Chul;Kim Tae-Kuk;Park Won-Hee;Kim Dong-Hyeon
    • Fire Science and Engineering
    • /
    • v.19 no.1 s.57
    • /
    • pp.80-86
    • /
    • 2005
  • In this study effects of the natural wind and the forced smoke ejection by operating the exhaust fan are studied numerically to examine the flow characteristics of the smoke and heat generated from a fire on the platform of an underground subway station. Three different situations, including 1) the case with no natural wind and no exhaust fan operation, 2) the case with natural wind but no exhaust fan operation and 3) the case with no natural wind but exhaust fan operation, are considered for the numerical analyses. The numerical results show that the natural wind causes a rapid spread of the fire along the tunnel resulting in rapid spread of the smoke and heat over the platform which affects the escape. The operation of the exhaust fan also results in the rapid spread of smoke and heat over the platform, but the time required for reaching the safe escaping height of the smoke layer with the exhaust fan operation is much longer than that without the exhaust fan operation. The numerical results also show that the required capacity of the exhaust fan becomes larger when the effect of the natural wind is included.

A Numerical Study on Characteristics of Smoke Exhaust in Road Tunnel Fires for Different Ventilation System (터널 화재 시 환기 방식에 따른 배연 특성의 수치해석 연구)

  • Kim, Jong-Yoon;Yoo, Ji-Oh
    • Fire Science and Engineering
    • /
    • v.22 no.3
    • /
    • pp.201-207
    • /
    • 2008
  • In this study, three Dimensional CFD simulations were carried out to investigate the effective smoke extraction system in bi-directional road tunnel fires using FLUENT. Characteristics of transverse system with big size extraction port or with uniform extraction port, semi-transverse system and longitudinal system for smoke extraction system were analyzed. Air velocity, port size, and operating method were used with variable. Distributions of smoke spread, CO was analyzed. As a result, the transverse ventilation system with big size port was found to be more effective than the uniform ports for bi-directional road tunnel.

The Analysis on the Effect of Supply Air Velocities by Location of Supply Air Damper on the Performance Efficiency of the Smoke Exhaust Systems (공기유입구 위치에 따른 유입공기의 풍속이 배연시스템 성능효율에 미치는 영향 연구)

  • Yeo, Yong-Ju;Lim, Chae-Hyun;Kim, Hak-Jung;Kim, Bum-Gyu;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.24 no.6
    • /
    • pp.20-27
    • /
    • 2010
  • In smoke control systems the amount of air supply is almost the same as that of smoke exhaust. This study analyzed the effect of supply air velocity on the smoke exhaust behavior using FDS tool. The results showed that fire plume can be disheveled by the rapid air velocities developed when the air supply inlet is located near the fire plume. Disheveled smoke caused the rapid descent of smoke layer level and the reduced visibility. To increase the efficiency of smoke exhaust systems supply air inlet should be located sufficiently far from the location of the fire plume.

A Study of smoke control mode for subway station fire (승강장 화재시 제연운전 모드에 관한 연구)

  • Rie, Dong-Ho;Kim, Ha-Young;Kim, Jung-Yup
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.11a
    • /
    • pp.178-183
    • /
    • 2008
  • 본 연구에서는 대피자의 최적 배연조건 확립을 위하여 CFD모델을 이용한 수치해석을 통해 지하철 승강장 내에서의 화재 시 다양한 배연조건에서의 화재 위험성을 검토하였다. 결과로 스크린도어를 설치한 경우가 설치하지 않은 경우보다 온도의 상승폭이 최대 $65.37%{\sim}74.97%$ 낮게 나타났다. 또한 급기나 압인 배기시 승강장에 난류가 발생함에 따라 온도 및 연기층이 교란되어 하락됨에 따라 탈출시 위험을 유발할 수 있는 것으로 판단되었다. 따라서 배연용량 및 승강장 공간 설정시 배연조건에 따른 화재 특성을 고려한 설계가 필요하다.

  • PDF

Reduced-Scale Tests of A Intelligent Tunnel Smoke-Control System (지능형 터널 배연시스템 축소모형 실험)

  • Son, Yun-Suk;Park, Won-Hee;Kim, Chi-Hun;Jung, Woo-Sung
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.04a
    • /
    • pp.378-383
    • /
    • 2011
  • 지능형 터널 배연시스템은 터널상부의 온도를 감지하는 온도감지부에서 들어오는 신호를 해독하여 화재위치 및 화재크기를 선정하고 제연설비의 운전방향 및 배연량을 조절함으로써 연기를 효율적으로 제어할 수 있는 시스템이다. 지능형 터널 배연시스템의 성능을 검증하기 위하여 실물터널의 크기를 1/60로 축소한 모델에서 두가지의 화원위치에 따라 실험을 수행하였다. 화재 발생 후 초기에는 온도가 상승하다가 제연팬이 작동하면 온도가 급격히 낮아진 후 일정하게 유지되면서 서서히 증가한다. 터널화재시 승객의 피난 장애를 주는 연기의 제어를 통해 터널의 안전성을 향상시킬 수 있는 것을 확인하였다.

  • PDF

성능위주의 배연설비를 위한 지하철 승강장 화재시뮬레이션에 관한 연구

  • 김용주;이동호;김종원;조정훈
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2001.11a
    • /
    • pp.225-231
    • /
    • 2001
  • 최근 인구 증대 및 도시 집중화에 따른 지상공간 부족의 대안 및 택지 이용도 효율 방안으로 지하공간 개발의 필요성이 증대되고 있다 특히 날로 증대되고 있는 지하공간에서의 문제점으로 설계 및 용도에 적합한 환기 시스템의 도입 및 운영의 미흡으로 공기질 악화 현상과 국민 보건상의 문제로 노출되고 있는 실정이다. 환기시스템은 일상적 공간환기는 물론 화재시의 배연기능을 포함한다. 따라서, 정상적인 작동(일반 환기)과는 별도로 비정상 환경(화재시의 배연)에서의 중요성이 인식되고 있다. 따라서, 시스템 설계 오류는 화재발생시 중대한 인명피해로 연결됨으로서 그 중요성은 아무리 강조하여도 지나침이 없다 이미 미국, 일본, 노르웨이 등의 선진 외국에서는 지하공간의 최적환경 개선은 국민 삶의 질 향상이라는 관점 하에 꾸준히 진행되어오고 있다. $^{(1~3)}$ 우리나라에서도 서울1기 지하철을 시작으로 교통난의 해소를 위하여 2005년까지 총연장 60km에 이를 것으로 전망됨에 따라 지하공간의 공기질 개선 및 화재시의 배연설비의 최적화가 요구된다.(중략)

  • PDF