The Performance Evaluation of Natural Smoke Ventilators Due to Stack Effect and Wind Velocities in High-rise Buildings (고층건물에서 연돌효과 및 외기풍속에 따른 배연창의 배연성능 평가)

  • Lim, Chae-Hyun;Kim, Bum-Gyu;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.23 no.6
    • /
    • pp.82-90
    • /
    • 2009
  • Natural smoke ventilator is one of domestic prescriptive methods to be used to exhaust smoke in case of fire in a high-rise buildings. The goal of this study is to evaluate the stack effect and the smoke exhaust performance in high-rise buildings with the opening of natural smoke ventilators using computer modeling technology, thus to estimate its effectiveness as a tool of smoke exhaust. For this purpose, the pressure differential in a domestic high-rise building with natural smoke ventilators was experimentally measured to analyze the stack effect with the closure or the opening of natural smoke ventilators and to calculate compensated air leakage of the building. Computer modeling based on experimentally measured data was carried out to estimate effectiveness of natural smoke ventilators in high-rise buildings using CONTAMW network program.

Scaled model tests for improvement and applicability of the transverse smoke control system on tunnels (횡류식 제·배연 시스템의 개선 및 적용성 분석을 위한 모형실험 연구)

  • Kim, Hyo-Gyu;Baek, Doo-San;Kim, Jae-Hyun;Lee, Seong-Won;Yoo, Ji-Oh
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.22 no.5
    • /
    • pp.563-574
    • /
    • 2020
  • Currently, road tunnels and railroad tunnels are building smoke control systems to emit toxic gases and smoke from fires. Among the various smoke control systems, the transverse smoke control system has the disadvantage that air supply or exhaust is performed on only half of the cross-section, rather than air supply or exhaust on the entire cross-section of the tunnel as air is supplied or exhausted by partitioning the wind path. Therefore, this study analyzed the effect of exhaustion through numerical analysis and scaled model tests on the zoning smoke control system, which improved the limitations of the transverse smoke control system. As a result of the scaled model test, the transverse ventilation system exhibited a 25.6% smoke control rate based on the state where no smoke was controled, and zoning smoke control system showed a smoke control rate of 40.8%. In addition, as a result of numerical analysis, it was found that transverse ventilation system did not control fire smoke spreading from the tunnel and continued to spread. On the other hand, zoning smoke control system was found to be smoke controled within a certain section due to the air curtain effect and the flue gas effect.

Experimental study on the effect of exhaust ventilation by shafts for case of fire in long traffic tunnels (장대 교통터널 화재시 수직갱의 배연효과에 관한 실험적 연구)

  • Yoo, Yong-ho;Yoon, Chan-hoon;Yoon, Sung-wook;Kim, Jin
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.7 no.1
    • /
    • pp.27-36
    • /
    • 2005
  • The objective of this study was to analyze the smoke movement and to investigate the effect of exhaust ventilation using by shafts for case of fire in long tunnels. Based on Froude modeling, the 1/50 scaled model tunnel (20 m long) was constructed by acrylic tubes and test were carried out systematically. The results of the shaft height test show that the effect on exhaust ventilation by a shaft delays the propagation time of backlayering, and the temperature decreases as the shaft height increases. If the fire occurs downstream of the shaft, the backlayering develops to get stronger by the shaft exhaust effect and then the propagation of CO and temperature increase along with propagation of CO. That is to say, in the case of fire downstream of the shaft, the shaft has the advantage of smoke exhaust effects, but it might result in a dangerous situation for the escaping passengers due to the more developed backlayering.

  • PDF

A Study on the Effectiveness to the Life Safety by Enlarging Smoke Vent Size and/or Sprinklered System (배연창 크기와 스프링클러 작동이 인명안전에 미치는 영향 연구)

  • Kim, Hak-Joong;Park, Yong-Hwan;Lim, Choe-Hyun;Kim, Bum-Kyu
    • Fire Science and Engineering
    • /
    • v.24 no.2
    • /
    • pp.133-138
    • /
    • 2010
  • Recently, evacuation safety of a resident of building become the major concern, because building has been higher and more complicated. Buildings in Korea should install the natural smoke venting or mechanical smoke exhaust equipment according to the building law. The smoke control is the most important to guarantee the evacuation safety. This study evaluate the influence to the height and temperature of smoke layer by enlarging smoke vent size and operating sprinkler system using CFAST (Version 6). Smoke venting size is larger, the effect to height and temperature of smoke layer is increased in below 5 MW fire. But, the correlation of these is decreased in above 10 MW fire. The case that opened smoke vent and sprinklered are applied, life safety criteria are satisfied regardless of fire size. After design the fire scenario according to the service and size of building. Install the smoke vent suitable for the fire size and verify that by experiment or simulation.

The Influence of Natural Smoke Ventilators and Wind Velocities on the Stack effect in High-rise Buildings (배연창 및 외기풍속이 초고층 건축물의 연돌효과에 미치는 영향)

  • Lim, Chae-Hyun;Kim, Bum-Gyu;Yeo, Yong-Ju;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.22 no.4
    • /
    • pp.20-26
    • /
    • 2008
  • The performance of natural smoke ventilators in High-rise buildings was analyzed by investigating the stack effect depending on the wind velocities using CONTAMW tool. The results showed that the opening of smoke ventilators can influence on the stack effect in the building thus moving the position of the neutral plane toward the opened smoke ventilators. The outside wind velocities can move up the neutral plane toward the top of the building thus increasing pressure differentials at the bottom of the building. The smoke ventilators can maintain its normal performance without outside wind, however, strong outside wind can prevent natural smoke exhaust due to the infiltration of outside air at the ventilators.

A Study on the Application of Ventilation Equipment in an Underground Fire (지하공간 화재시 배연장비의 활용에 관한 연구)

  • Lee, Sung-Ryong;Han, Dong-Hoon
    • Tunnel and Underground Space
    • /
    • v.20 no.2
    • /
    • pp.92-96
    • /
    • 2010
  • In this study, experiments were conducted to evaluate the effectiveness of ventilation equipment in underground fires. Two type of Ventilators were used in experiments. Experiments were carried out using ethanol square pool fire. Maximum heat release rate was about 460kW. Visibility and temperature distribution were evaluated according to mechanical ventilation. In blower type ventilation, visibility was increased and temperature was lowered.

The Effect of the Combined Operation of Sprinkler and Vent Systems on the Smoke Control in a Horizontal Corridor (스프링클러와 배연설비의 통합작동이 수평통로의 연기제어에 미치는 영향)

  • Jeon Heung-Kyun;Choi Young-Sang;Choo Hong-Lok;Jang Jun-Young
    • Fire Science and Engineering
    • /
    • v.19 no.1 s.57
    • /
    • pp.70-89
    • /
    • 2005
  • Fire scenarios in a space $20.0m\;\times\;4.0m$ floor and 3.0m high were simulated by using computational fluid dynamics program (FDS 4.0.3) to investigate the effect of the combined operation of both sprinkler and vent systems, which are installed for cooling and blocking smoke which propagates beneath the ceiling of a horizontal corridor, on the temperature and smoke density of it. It was shown that the combined operation both sprinkler and vent systems was more effective than each operation for cooling and blocking smoke, the number of operating sprinklers was two because of corner effect of wall, and over-installed sprinklers deteriorated the effect of cooling and blocking smoke. This study showed that the case of two sprinklers and vent flow rate $3.0m^3/s$ in fire scenario was the most effective for cooling and blocking smoke. It was confirmed that the smoke downdrag occurs in operating sprinkler system, and the more smoke droplets produced by increasing fire size, the greater smoke downdrag occurred.

Use of Flue Gas Desulfurization Gypsum as an Activator for a Ground Granulated Blast Furnace Slag (고로슬래그 자극재로써 건식 및 습식 배연탈황석고의 활용가능성 평가)

  • Lee, Hyun-Suk;Kim, Ji-Hyun;Lee, Jae-Yong;Chung, Chul-Woo
    • Journal of the Korea Institute of Building Construction
    • /
    • v.17 no.4
    • /
    • pp.313-320
    • /
    • 2017
  • Flue gas desulfurization gypsum(FDG) is produced when removing sulfur oxides from combustion gas generated by coal power plant. However, the recycling of FDG is still limited to the certain purposes. In order to expand the possible application of FDG, this study aims to utilize FDG as an activator for ground granulated blast furnace slag. FDG produced by dry- and wet-process were used for the experiments. Slag paste specimens were produced by mixing with deionized water and simulated pore solution, and the role of FDG as an activator for blast furnace slag was evaluated using hydration study by XRD analysis and compressive strength development. According to the results, dry-type FDG was found to work as an activator for blast furnace slag without the presence of soluble alkalis. However, wet-type FDG needs assistance by soluble alkalis in order to work as an activator for blast furnace slag. It was also found that the substitution of dry- and wet-type FDG into blast furnace slag can increase the 28 day compressive strength of slag paste. It is expected that efficient and economical recycling of FDG will be possible if quantitative analysis of strength enhancement according to substitution rate of both dry- and wet-type FDG.

An Experimental Study on Mechanical Ventilation Using an Exhaust Engine in Corridor Fires (복도공간 화재 시 배연차를 활용한 배연에 관한 실험적 연구)

  • Lee, Sung-Ryong;Han, Dong-Hoon
    • Fire Science and Engineering
    • /
    • v.24 no.3
    • /
    • pp.99-105
    • /
    • 2010
  • Ventilation fans utilized correctly can increase the effectiveness of fire fighters and survivability of occupants. It is possible to increase the pressure of a corridor to prevent the infiltration of smoke. In this study, experiments were carried out to evaluate ventilation effectiveness in corridor fires. Corridor used in the experiment was 20 m long. Heptane was used as a fuel. Temperature and visibility were measured in order to evaluate ventilation effectiveness according to the position of a vent. Vent distance ranged from 0 m to 4 m and height varied from 0 m to 1.5 m. When the vent was positioned 2 m long and 0.75 m high the result was most effective.

A Basical Study about Ventilation Performance of Natural Smoke Ventilators through Stack Effect in High-rise Building (고층건축물에서의 연돌효과에 따른 배연창의 배연성능에 관한 기초적 연구)

  • Kim, Hye-Won;Jin, Seung-Hyun;Koo, In-Hyuk;Kwon, Young-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2017.11a
    • /
    • pp.54-55
    • /
    • 2017
  • The High-rise building has a problem the ventilation performance of natural ventilator by stack effect that it occurs by pressure difference. For that reason the study about natural smoke ventilator of High-rise building consistently needs. Therefore on this study does analysis of difference with abroad through investigate of Natrual smoke ventilator's law, it conducts of natural smoke ventilator's research on the actual condition. As a result on this study, in the case of abroad that it states more specific standards than domestic. Also the result of a field study, it shows that the natural smoke ventilator is installed same size and the number regardless of building's pressure difference.

  • PDF