• Title/Summary/Keyword: 배관계통

Search Result 168, Processing Time 0.031 seconds

Optimization of pipeline Operation for Stable Landfill Gas Collection Using Numerical Analysis (안정적 매립가스 포집을 위한 배관망 최적운용 분석)

  • 김인기;김세준;허대기;김현태;성원모;배위섭
    • Journal of Soil and Groundwater Environment
    • /
    • v.6 no.3
    • /
    • pp.43-52
    • /
    • 2001
  • It is important that the gas collected from wells completed in waste landfill should be continuously and stably transported to pre-treatment stage through pipelines. The transport is generally affected by fluid flow characteristics of landfill, gas reserves, leachate moisture holdup in pipeline, structures and dimensions of pipeline network, etc. This paper analyzes the pipeline transport and collection mechanism for gas generated in a durable waste landfill. From the results, the optimal controlled scheme of blower inlet pressure is proposed for the prevention of trapped gas pocket zones.

  • PDF

An Analysis on Thermal Stratification in Residual Heat Removal System Piping of Nuclear Power Plant (가동원전 잔열제거계통 배관에서의 열성층유동 해석)

  • Park, M.H.;Kim, K.C.;Kim, K.H.
    • Proceedings of the KSME Conference
    • /
    • 2003.04a
    • /
    • pp.1597-1602
    • /
    • 2003
  • Numerical analysis is carried out to assess the temperature distribution on the mixing tee line of Residual Heat Removal System (RHRS). In RHRS, hot and cold fluids of main and bypass piping are mixed and unmixed by the flow rate or piping layout. Thermal stratification phenomenon is a cause of major degradation on RHRS piping. According to the analysis for each operation modes, maximum temperature difference between top and bottom of piping were evaluated about 60K when the flow rate of main and bypass lines is same. Temperature difference will be decreased at the elbow on RHRS piping if the length of vertical piping is increased.

  • PDF

Evaluation the Impact of Installing a Isolation Valve on Condensate System of Nuclear Power Plan (원자력발전소 복수기 수실 차단밸브 설치 영향 평가)

  • Lee, Sun-Ki
    • Journal of Industrial Convergence
    • /
    • v.18 no.4
    • /
    • pp.15-21
    • /
    • 2020
  • Because there are no isolation valves in condensate system of nuclear power plants, circulating water pump was shutdown for the condenser repair. When circulating water pump was shutdown, power plant output decreased about 45%. These output decreasing can minimize by establishing isolation valves. In this paper, evaluated effect to flow conditions change of condensate system, structural integrity of system, condenser pressure of in case of establish isolation valves to condensate system. Results of the evaluation, the flow rate due to the installation of the isolation valve decreased 0.3% when the valve was fully opened and 4.5% when fully closed. In addition, it was found that the vacuum degree of the condenser decreased with decreasing flow rate, but the integrity of the system was maintained.

원자로 냉각재계통 RTD SCOOP내부 유속계산

  • 윤덕주;이창섭
    • Proceedings of the Korean Nuclear Society Conference
    • /
    • 1996.05b
    • /
    • pp.42-47
    • /
    • 1996
  • 기존의 우회배관을 제거하고 원자로냉각재배관에 직접 RTD를 삽입하여 온도를 측정할 경우 취수부내의 유속이 기존에 비해 어떻게 변하는지 고찰하고자 한다. 이는 RTD응답시간 요건을 만족하기 위해서는 RTD SCOOP 내부유속이 3ft/sec이상이 되어야만 하기 때문에 중요하다. 이러한 유속을 계산하기 위해 취수부를 단순화하고 보수적인 가정에 의해 유체역학적으로 계산한 결과 이러한 요건을 만족하는 결과를 얻을 수 있었다. 또한 흡입구와 출구 Hole에서 차압의 대부분이 발생하므로 이부분의 부차계수가 유량계산에 절대적으로 영향을 미치고 있으며 아울러 원자로냉각재유량의 크기에 따라 미치는 영향을 계산한 결과 거의 비례적으로 증가하고 있으며 출구직경을 확대하므로 유량을 3.5 ft/sec까지 증가시킬 수 있다는 결과를 얻었다.

  • PDF

유한요소의 형태 및 경계 조건이 Applied J 적분값에 미치는 영향

  • 라인식;조인득;지계광
    • Proceedings of the Korean Nuclear Society Conference
    • /
    • 1996.05c
    • /
    • pp.123-130
    • /
    • 1996
  • 탄소성파괴역학의 발달과 함께 원자력 발전소의 설계시 고려해야 하는 고에너지 배관의 양단파단사고와 같은 극한 가정 대신 파단전누설(LBB : Leak Before Break)개념을 배관설계시 고려할 수 있도록 관련 규제 요건이 완화되어 원자력 발전소 고에너지 계통 설계에 새로운 설계 개념으로 적용할 수 있게 되었다. 파단전누설개념 적용시 균열 안정성 평가에 가장 널리 사용되는 방법은 J-T 방법이다. 본 연구에서는 유한요소법 사용시 균열 선단에서 요소의 크기 및 경계 조건 (Boundary Condition)이 변화할 때 Applied J 적분값에 미치는 영향을 ABAQUS 전산 프로그램을 이용하여 조사하였다.

  • PDF

Preventive Measure for Water Hammering (수격소음의 방지대책)

  • Peak, Choon Kee
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.20 no.1
    • /
    • pp.39-45
    • /
    • 1991
  • 건축물(建築物)의 설비(設備)를 관리(管理)하는 과정에서 향후(向後) 심각히 검토될 관심사로는 소음(騷音)과 진동(振動)을 들 수 있다. 배관계통(配管系統)에서 발생하는 워터햄머는 소음(騷音)과 진동(振動)의 주된 원인이 되고 있으므로 본(本) 고(稿)에서는 특히 주택부문(住宅部門)에서의 워터햄머에 대한 발생원인(發生原因)과 대책(對策)을 제시(提示)하였다.

  • PDF