• Title/Summary/Keyword: 룸코너 실험

Search Result 4, Processing Time 0.126 seconds

Study on Horizontal and Vertical Temperature Analysis of Cable Fire in Common Duct using Room Corner Experiment (룸코너 실험을 이용한 공동구 케이블 화재 시 수평·수직 방향 온도 분석에 관한 연구)

  • JaeYeop Kim;SeHong Min
    • Journal of the Society of Disaster Information
    • /
    • v.19 no.3
    • /
    • pp.634-643
    • /
    • 2023
  • Purpose: Underground common duct fires are steadily occurring, and the proportion of property damage is particularly large among property and human casualties caused by fires. Especially, cable fires that occur in common areas can spread vertically quickly and pose a great risk. This paper aims to scientifically analyze the nature of the fire by reproducing the fire through experiments. Method: To analyze the characteristics of cable fires in underground common duct, heat release rate and temperature changes were measured through Room-corner (ISO 9705) test, and the vertical and horizontal propagation of cable fires was quantitatively compared and analyzed. Result: The Room Corner Test (ISO 9705) was used to compare the temperature changes at each data logger point. The results showed that the time it took for the fire to reach the ignition temperature in the horizontal and vertical directions from the center point of the first-tier cable was 589 seconds and 536 seconds, respectively, which means that the vertical fire propagation is 53 seconds faster than the horizontal propagation. This proves that the vertical propagation of fire is relatively faster than the horizontal propagation. The horizontal propagation speed of the fire was also compared for each floor cable tray. The results showed that the third-tier cable propagated at 3.4 times the speed of the second-tier cable, and the second-tier cable propagated at 1.5 times the speed of the first-tier cable. This means that the higher the cable is located, the faster the fire spreads and the larger the fire becomes. Conclusion: This study identified the risks of cable fires and analyzed the risks of vertical fire propagation during cable fires based on the results of the Room Corner Test. Studies to prevent the spread of fire and fire response policies to prevent vertical fire propagation are required. The results of this study are expected to be used to assess the fire risk of common areas and other fires.

An Experimental Study on the Warehouse Mock-up Fire Test (창고 모델 실물화재 특성에 대한 실험적 연구)

  • Kweon, Oh-Sang;Yoo, Yong-Ho;Kim, Heung-Youl
    • Fire Science and Engineering
    • /
    • v.24 no.4
    • /
    • pp.47-54
    • /
    • 2010
  • This study is analyze the damage of warehouse fire accident be made through the fire characteristic database of combustibles and real scale fire test of warehouse mock-up. Combustibles fire tests are carried out for database using RCT (Room Corner Tester) to predict fire growth the goods. A mockup ($3m{\times}3m{\times}2.4m$) of clothes warehouse was built and real scale fire test by LSC (Large Scale Calorimeter) base on the fire characteristic DB. The mock-up of clothes warehouse is made of two type sandwich panels (Glass wool, EPS foam sandwich panel). As a mock-up test result, test 1 (Glass wool sandwich panel) and test 2 (EPS foam sandwich panel) indicating fire growth such as 5 MW, 11 MW of maximum HRR (Heat Release Rate).

Investigation of the Relationship Between Wall Thermal Conductivity and Inner Room Temperature in Compartment Fires (구획화재에서 벽면의 열전도 계수와 내부 온도의 상관관계 분석)

  • You, Woo Jun;Ko, Gwon-Hyun
    • Fire Science and Engineering
    • /
    • v.32 no.2
    • /
    • pp.17-23
    • /
    • 2018
  • In this study, the relations of the wall thermal conductivity and surface temperature in a compartment fire are investigated using Buckingham Pi theorem. The dimensionless parameters of the previous study are analyzed in order to correlate the dimensionless groups of the heat release rate, the thermal conductivity, the volume of compartment and the convective heat transfer coefficient. In addition the reduced scale of compartment, which has 1/6 size of ISO 9705 Room Corner Tester, is manufactured and the oxygen concentration and the maximum temperature in the space are measured for the gasoline pool fire ($10cm{\times}10cm$, $15cm{\times}15cm$ and $20cm{\times}20cm$). Finally, the criterion of the wall temperature increase are suggested in accordance with the thermal conductivity and the convective heat transfer coefficient. In addition, the dimensionless empirical equation using Buckingham Pi theorem considering the heat release rate are presented suggested. The results of this study will be useful especially for the fire phenomenon investigation of the wall thermal conductivity coefficient and shape in the compartment space.

A Study on the Application Scheme of Fire Identification Considering the Heat Release Rate Characteristics of Inflammable Material (가연물의 발열량 특성을 고려한 화재감식 적용방안에 관한 연구)

  • Kang, Jung-Ki;Oh, Jin-Hee;You, Woo-Jun;Ryou, Hong-Sun;Choi, Don-Mook
    • Fire Science and Engineering
    • /
    • v.28 no.6
    • /
    • pp.52-57
    • /
    • 2014
  • The present study suggests the fundamental method for the prediction time of the fire origin by analyzing the combustion phenomenon of inflammable material in the building structure. The heat release rate (HRR) with time variant is evaluated for the interphone as a inflammable material, which is opted from the fire incidents in the stairwell. the fire dynamics simulator (FDS ver. 6.1) is applied in order to analyze the difference of the smoke inflow time to the downstair from the fire event area with various fire pattern. The results show that the maximum inflow time difference for the case of the interphone made from ABS materials is about 4.93 times with the input conditions of heat flux values and the environment in the FDS for the fixed stairwell which composed of total volume $291.3m^3$, floorage $23.3m^2$ and the height of each floor 2.5 m. This research can be practical information for the application method of simulation scheme with experimental data to the fire Identification.