• Title/Summary/Keyword: 루버휜

Search Result 6, Processing Time 0.02 seconds

Louvered Fin Heat Exchanger : Optimal Design and Numerical Investigation of Heat and Flow Characteristics (루버휜 최적 설계 및 최적 모델의 열유동 특성 분석)

  • Ryu, Kijung;Lee, Kwan-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.12
    • /
    • pp.654-659
    • /
    • 2013
  • This paper presents a numerical optimization of louvered fins to enhance the JF factor in terms of the design parameters, including the fin pitch, the number of louvers, the louver angle, the fin thickness, and the re-direction louver length. We carried out a parametric study to select the three most important parameters affecting the JF factor, which were the fin pitch, number of louvers, and the louver angle. We optimally designed the louvered fin by using 3rd-order full factorial design, the kriging method, and a micro genetic algorithm. Consequently, the JF factor of the optimum model increased by 16% compared to that of the base model. Moreover, the optimum model reduced the pressure drop by 17% with a comparable heat transfer rate.

Numerical Analysis on Flow and Heat Transfer Characteristics in Louver Fin Heat Exchanger (루버휜형 열교환기내 유동 및 열전달 특성에 관한 해석적 연구)

  • 한진호;박상록;김일겸;임장순
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.4
    • /
    • pp.398-403
    • /
    • 2000
  • Numerical analysis was conducted to investigate flow and heat transfer characteristics in louver fin exchanger, which were influenced by louver pitch, fin pitch, louver angle and inlet velocity. Standard $k-\varepsilon$ turbulent modelling was used in this study, and compared with laminar modelling. As a result of this study, Nusselt number became smaller as louver pitch or fin pitch was greater. Drag coefficient became smaller as louver pitch or fin pitch was greater, but it was little affected by inlet velocity.

  • PDF

The Experimental Study on Performance Improvement under frost conditions of the Heat Pump with Corrugate Shaped Fin and Two Compressors (저 착상 휜과 두 대 압축기 사이클을 이용한 히트펌프 난방성능 개선에 관한 연구)

  • Hwang Yoon-Jei;Cho Eun-Jun;Chung Baik-Young;Lee Gam-gue
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.3
    • /
    • pp.201-208
    • /
    • 2005
  • This study presents the experimental study on improvement of frost/defrost performance in an heat pump system with newly developed fin and multiple compressors. As multiple compressors system, the variable and single speed compressor combinations has been introduced and compared with single speed 1-compressor system in a view point of improvement of frost/defrost performance. Also, newly developed corrugate shaped fin has been compared with conventional louver shaped fin. The frost/defrost performance is defined and some parameters are compared to discuss the effect of each combination. From this experimental study, it is known that if the variable and single speed compressor combination system equipped with corrugate shaped fin, the system performance has greatly improved not only for heating capacity, but also for frost performance.

Effect of Inclination Angle on the Heat Transfer and Pressure Drop Characteristics of Parallel Flow Heat Exchanger (경사각이 PF 열교환기의 열전달 및 압력 손실에 미치는 영향)

  • Kim, Do-Young;Ham, Jung-Ho;Kim, Nae-Hyun;Park, Nae-Hyun;Hwang, Jun-Hyun
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.222-228
    • /
    • 2007
  • The effect of inclination angle on the heat transfer and pressure drop characteristics of brazed aluminum heat exchangers is experimentally investigated. Three samples having different fin pitches (1.25, 1.5 and 2.0 mm) were tested. Results show that heat transfer coefficient is not affected by the inclination angle. However, the friction factor increases as the inclination angle increases with negligible difference between the forward and backward inclination. Both the heat transfer coefficient and the friction factor are the smallest at $P_f$=1.5mm, followed by $P_f$=2.0mm and 1.25mm. Possible explanation is provided considering the louver layout. Comparison with existing correlations is also mad.

  • PDF

Air-side Performance of Louver-Finned Flat Aluminum Heat Exchangers at a Low Velocity Region (저속 영역에서 루버휜이 장착된 평판관형 알루미늄 열교환기의 공기측 전열 성능에 대한 실험적 연구)

  • Cho, Jin-Pyo;Oh, Wang-Kyu;Kim, Nae-Hyun;Youn, Baek
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.26 no.12
    • /
    • pp.1681-1691
    • /
    • 2002
  • The heat transfer and pressure drop characteristics of heat exchangers with louver fins were experimentally investigated. The samples had small fin pitches (1.0 mm to 1.4 mm), and experiments were conducted up to a very low frontal air velocity (as low as 0.3 m/s). At a certain Reynolds number (critical Reynolds number), the flattening of the heat transfer coefficient curve was observed. The critical Reynolds number was insensitive to the louver angle, and decreased as the louver pitch to fin pitch ratio (L$_{p}$F$_{p}$) decreased. Existing correlations on the critical Reynolds number did not adequately predict the data. It is suggested that, for proper assessment of the heat transfer behavior, the louver pattern in addition to the flow characterization need to be considered. The heat transfer coefficient increased as the fin pitch decreased. At low Reynolds numbers, however, the trend was reversed. Possible explanation is provided considering the louver pattern between neighboring fins. Different from the heat transfer coefficient, the friction factor did not show the flattening characteristic. The reason may be attributed to the form drag by louvers, which offsets the decreased skin friction at a low Reynolds number. The friction factor increased as the fin pitch decreased and the louver angle increased. A new correlation predicted 92% of the heat transfer coefficient and 90% of the friction factor within $\pm$10%.10%.

An Experimental Study on the Performance of the Louver Fin Type Heat Exchanger by the Change of the Driving Condition (운전조건 변화에 따른 루버휜 열교환기 성능변화에 관한 실험적 연구)

  • Kim, Jung-Kuk;Koyama, Shigeru;Kuwahara, Ken;Kim, Dong-Hwi;Park, Byung-Duck
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.440-445
    • /
    • 2008
  • The present study was investigated the effect of the driving condition on the performance of a louver fin and tube type heat exchanger under frosting condition. Heat transfer rate and pressure drop by frost were experimentally investigated. Effects of the wet blub temperature and the shape of a fin on heat transfer performances has been also investigated. The key parameters were fin type(louver and corrugate fin) and the wet blub temperature of air (0.5, 1.0, $1.5^{\circ}C$). The heat transfer performance of the louver fin and tube type heat exchanger was higher by 0.89% than the corrugate fin type. As the wet blub temperature of air were increased, the heat transfer rate, pressure drop and mass of frost of three test models(Type A, B, C) were increased. Especially, the maximum heat transfer rate and maximum pressure drop were shown for the louver fin and tube type heat exchanger. As a experimental result, the enhancement factor(EF) of louver fin and tube type heat exchanger was $0.2{\sim}0.4$ due to the high pressure drop.

  • PDF