Application of Four-season Dedicated Outdoor Air Handling Unit in Central and Personal Air-conditioning (중앙공조 및 개별공조에서의 외조기 적용)

  • Park, Seung-Tae;Kim, Young-Il;Lee, Tae-Ho;Choi, Se-Young
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.591-596
    • /
    • 2008
  • The present study has been conducted to study the performance of dedicated outdoor air handling unit in central and personal air-conditioning. With conventional central and personal air-conditioning systems which are designed according to the maximum load, humidity increase above comfort level can not be avoided as the cooling load decreases. The adoption of dedicated outdoor air handling unit, however, can solve this problem. Moreover, the dedicated outdoor air handling unit has the characteristics of anti-bacteria due to dry coil, energy saving and good indoor air quality. During cooling seasons, dedicated outdoor air handling unit can save energy up to 30% than the conventional cooling+reheating system for controlling both temperature and humidity.