• Title/Summary/Keyword: 단상 열전달

Search Result 37, Processing Time 0.027 seconds

Experimental Study on Heat Transfer Characteristics for Single-phase Flow in Plate & Shell Heat Exchangers by Using Wilson Plot Method (Wilson plot법을 이용한 Plate & Shell 열교환기의 단상유동 열전달 특성에 관한 실험적 연구)

  • Seo, M.K.;Kim, Y.S.;Lee, S.K.
    • Journal of Power System Engineering
    • /
    • v.3 no.4
    • /
    • pp.22-27
    • /
    • 1999
  • Single phase heat transfer coefficients were measured for turbulent water flow in a plate & shell heat exchangers by using Wilson plot method. An experiment for counterflow heat exchange between the plate and shell was performed. The shell side heat transfer resistance was varied and the overall heat transfer coefficients were measured. The single-phase heat transfer coefficients in a plate side were obtained by Wilson plot method. Single-phase heat transfer correlations based on projected heat transfer area have been proposed for a plate & shell heat exchanger.

  • PDF

Heat Transfer Characteristics of Carbon Dioxide in a Inclined Helical Coil Type Heat Exchanger with Inner Diameter Tube of 4.55 mm (내경 4.55 mm의 경사진 헬리컬 코일형 열교환기내 이산화탄소의 열전달 특성에 관한 연구)

  • Son, Chang-Hyo
    • Journal of the Korean Institute of Gas
    • /
    • v.11 no.3
    • /
    • pp.1-6
    • /
    • 2007
  • The heat transfer coefficient and pressure drop during gas cooling process of $CO_2$ (R-744) in inclined helical coil copper tubes were investigated experimentally. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and a inclined helical coil type gas cooler (test section). The test section consists of a smooth copper tube, which is specified as the inner diameter of 4.55 mm. The refrigerant mass fluxes were varied from 200 to $600kg/m^2s$ and the inlet pressures of gas cooler were done 7.5 to 10.0 (MPa). The heat transfer coefficients of $CO_2$ in the inclined helical coil tubes increase with the increase of mass flux and gas cooling pressure of $CO_2$. The pressure drop of $CO_2$ in the gas cooler shows relatively good coincidence with those predicted by Ito's correlation developed for single-phase in a helical coil tube. The local heat transfer coefficient of $CO_2$ is well coincident with the correlation by Pitla et al. However, at the region near pseudo-critical temperature, the experiments indicate higher values than the Pitla et al. correlation.

  • PDF

Experimental measurements on Single-Phase Local heat transfer coefficients in $6{\times}6$ rod bundles with LSVF mixing vanes (LSVF 혼합날개를 이용한 $6{\times}6$ 연료봉 다발에서의 단상 국부적 열전달계수의 실험적 측정)

  • Bae, Kyenug-Keun;Choi, Young-Don
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.300-305
    • /
    • 2005
  • The present experimental study investigates single-phase heat transfer coefficients downstream of support grid in $6{\times}6$ rod bundles. Support grid with split mixing vanes enhance heat transfer in rod bundles by generating it make turbulence. But this turbulence is confined to short distance. Support grid with LSVF mixing vanes enhanced heat transfer to longer distance. The corresponding Reynolds number investigated in the present study is Re=30,000. The heat transfer coefficients are measured using heated and unheated copper sensor.

  • PDF

The Performance in Shell-and-Tube Heat Exchangers with Configuration and Surface Characteristics of Tube (Tube의 형상 및 표면특성에 의한 Shell-and-Tube 열교환기의 열전달 성능)

  • Kim, Sung-Il;Park, Ki-Ho;Chun, Won-Pyo
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.2316-2321
    • /
    • 2008
  • This paper presents an improved performance of heat transfer for shell-and-tube and thermal analysis based on the Bell-Delaware method for single tube. Heat transfer has been compared for a smooth tube, helical tube and surface-coated tube. In general, the results showed that properly designed helical tube and surface-coated tube offer a significant improvement in heat transfer. The numerical results derived from the Bell-Delaware method for the shell-side heat transfer coefficient were verified with experimental results. The thermal analysis aids significantly in the solution of the design problem.

  • PDF

Analysis on condensation heat transfer and pressure drop to develop design program for plate heat exchangers (판형열교환기 설계프로그램 개발을 위한 응축열전달 및 압력강하 분석)

  • Ko, Jea-Hyun;Song, Young-Ho;Park, Kweon-Ha
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.38 no.4
    • /
    • pp.376-382
    • /
    • 2014
  • The purpose of this study is to get the formulas of condensation heat transfer coefficient and pressure drop about the water to develop design program for plate type heat exchangers. The single phase flow of cold side was calculated with the correlation of Ko. Condensation heat transfer coefficient model proposed by Annaiev was used and Lockhart model was used to analyze the pressure drop. The calculation algorithm was proposed to calculate heat transfer rate and pressure drop simultaneously. The prediction errors remained within 20% compared to the commercial code in the working range of the plate heat exchangers.

Measurement of Single Phase and Condensation Heat Transfer Coefficients of Ammonia in a Horizontal Tube (암모니아의 수평관내 단상 및 응축 열전달계수의 측정)

  • 백영진;장영수;김영일
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.6
    • /
    • pp.561-569
    • /
    • 2000
  • Single phase and condensation heat transfer characteristics of ammonia in a horizontal tube have been investigated experimentally The horizontal test section is composed of smooth SUS316 tube for refrigerant flow, surrounding annulus for water flow, and temperature and Pressure measuring sensors. For single phase test, subcooled ammonia mass flux was varied from 320 to 501 kg/mrs and temperature was varied from 18 to $47^{\circ}C$. For condensation test, mass flux and saturation temperature were varied from 86 to 128 kg/$m^2$s and 34 to $47^{\circ}C$, respectively. The equations of Gnielinski Soliman et al., Traviss et at., Cavallini and Zecchin, Shah, Chen et al., Tandon et al., and Chilli and Anand were compared with the experimental data. New correlations are proposed based on the experimental results and the absolute mean deviation of the experimental data becomes 1.0% for single phase test and 4.9% for condensation test.

  • PDF

A study on the single-phase heat transfer in a counter-flow double-pipe heat exchanger by Wilson plot technique (Wilson plot기법을 이용한 2중관식 대향류 열교환기의 단상 열전달에 관한 연구)

  • Ohm, Ki-Chan
    • Journal of the Korean Solar Energy Society
    • /
    • v.26 no.4
    • /
    • pp.93-100
    • /
    • 2006
  • An experimental study of a counterflow heat exchanger was performed. The heat exchanger had an effective heat transfer length of 1000mm and was operated in a counterflow arrangement with hot water($30{\pm}0.5^{\circ}C$, $Re_i=3500{\sim}20000$) in the inner tube(copper tube, $d_0=9.52mm$) and cold water($15{\pm}0.5^{\circ}C$, $Re_{DH}=10700{\sim}39000$) in the annulus(copper tube, $D_0=19.05mm$). Overall heat transfer coefficients were calculated and heat transfer coefficients in the inner tube and the annulus were determined using Wilson plots. The inner Nusselt number was compared with that of Gnielinski's correlation and they agreed within ${\pm}10%$ error. The trends were typical for a fluid-to-fluid heat exchanger with the overall heat transfer coefficient increasing with both inner and annulus flow rates. In the range of this experiment, Nusselt numbers for the inner tube flow were almost identical with those of the annulus flow at the same Reynolds number.

Study on Single-Phase Heat Transfer, Pressure Drop Characteristics and Performance Prediction Program in the Oblong Shell and Plate Heat Exchanger (Oblong 셀 앤 플레이트 열교환기에서의 단상 열전달, 압력강하 특성 및 성능예측 프로그램 개발에 관한 연구)

  • 권용하;김영수;박재홍
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.28 no.6
    • /
    • pp.1026-1036
    • /
    • 2004
  • In this study, single-phase heat transfer experiments were conducted with Oblong Shell and Plate heat exchanger using water. An experimental water loop has been developed to measure the single-phase heat transfer coefficient and pressure drop in a vertical Oblong Shell and Plate heat exchanger. Downflow of hot water in one channel receives heat from the cold water upflow of water in the other channel. Similar to the case of a plate heat exchanger, even at a very low Reynolds number, the flow in the Oblong Shell and Plate heat exchanger remains turbulent. The present data show that the heat transfer coefficient and pressure drop increase with the Reynolds number. Based on the present data, empirical correlations of the heat transfer coefficient and pressure drop in terms of Nusselt number and friction factor were proposed. Also, performance prediction analyses for Oblong Shell and Plate heat exchanger were executed and compared with experiments. $\varepsilon$-NTU method was used in this prediction program. Independent variables are flow rates and inlet temperatures. Compared with experimental data, the accuracy of the program is within the error bounds of $\pm$5% in the heat transfer rate.