• Title/Summary/Keyword: 단독운전방지기법

Search Result 30, Processing Time 0.029 seconds

Output Power Analysis of Active Frequency Drift Method for Anti-Islanding (단독운전방지를 위한 능동적 주파수 변환기법의 출력전력 분석)

  • Lee, Ki-Ok;Choi, Ju-Yeop;Choy, Ick;Yu, Gwon-Jong;An, Jin-Ung
    • Journal of the Korean Solar Energy Society
    • /
    • v.29 no.6
    • /
    • pp.75-80
    • /
    • 2009
  • Recently, as the grid-connected photovoltaic power conditioning systems (PVPCS) are installed in many residential areas, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. In this paper, active frequency drift (AFD) method, one of the anti-islanding methods which is analyzed by current magnitude compensation and calculation of RMS value of the output power is proposed and verified by simulation.

Characteristics Analysis of RPV and AFD for Anti-Islanding in Active Method (단독운전방지를 위한 능동 방식 중 AFD 및 RPV에 대한 특성해석)

  • Choe, Gyu-Ha;D, Bayasgalan;Lee, Young-Jin;Han, Dong-Ha;Jeong, Byong-Hwan;Kim, Hong-Sung
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.14 no.2
    • /
    • pp.160-167
    • /
    • 2009
  • To detect islanding mode when the grid is being tripped is a major safety issue in the Utility Interactive Photo Voltaic (UIPV) system. In this paper, analytical design method is suggested for AFD & RPV method under IEEE 929-2000 recommended islanding test condition. We have discussed that there is a same point. we injected reactive component of the current by AFD & RPV methods, but the current reference generated is other waveform. Possible if amount of reactive components in this methods are same each method, there is happened same rates frequency variation. To verify the validity of the analytical comparison, this paper presents simulation and experimental results from single phase, 3[kW] inverter for the transformerless UIPV system.

Simulation of Non-Detection Zone using AFD Method applied to Utility-Connected Photovoltaic Systems for a Variety of Loads (다양한 부하에 따른 계통연계형 태양광발전 시스템에 적용된 AFD 기법의 단독운전 불검출영역 시뮬레이션)

  • Ko, Moon-Ju;Choy, Ick;Choi, Ju-Yeop;Won, Young-Jin
    • 전자공학회논문지 IE
    • /
    • v.43 no.2
    • /
    • pp.63-69
    • /
    • 2006
  • Islanding phenomenon of utility-connected PV power conditioning systems(PV PCS) can cause a variety of problems and must be prevented. If the real and reactive powers supplied by PV PCS are closely matched to those of load, islanding detection by passive methods becomes difficult. The active frequency drift(AFD) method, called the frequency bias method, enables islanding detection by forcing the frequency of the voltage in the islanding to drift up or down. In this paper, non-detection zone(NDZ) of AFD is analyzed for the islanding detection method of utility-connected PV PCS by simulation tool PSIM.

Characteristics Analysis and Control method of RPV for Anti-Islanding (단독운전방지를 위한 RPV 방식의 특성분석 및 제어기법)

  • Bayasgalan, Bayasgalan;Heo, H.S.;Zayabaatar, Zayabaatar;Kim, H.S.;Lee, J.P.;Choe, G.H.
    • Proceedings of the KIPE Conference
    • /
    • 2007.11a
    • /
    • pp.202-205
    • /
    • 2007
  • 현재 태양광, 풍력 및 연료전지 즉, 신재생에너지를 많이 사용하게 됨으로써 이를 계통과 병렬로 연결하여 쓰고 있다. 그러나 계통에 연결할 경우 여러 가지 문제가 발생할 수가 있는데 그중에서 대표적으로 단독운전을 들 수가 있다. 이를 방지하기 위한 검출기능은 시스템의 안전성 및 전기적 안전성 측면에서 매우 중요하다. 본 연구에서는 단독운전 검출을 위한 RPV 방식 및 제어알고리즘을 제안하였으며, 계통의 전압 위상을 기준으로 전류위상각도에 따른 주파수 변동 특성을 해석하였다. 해석 및 제안된 방법의 타당성은 EMTP 및 Matlab 을 이용하여 검증하였다.

  • PDF

Frequency Shift Scheme with Positive-feedback for Anti-islanding of Grid-connected PVPCS Modeling and Analysis (계통 연계형 태양광 발전 시스템의 단독운전 방지를 위한 Positive-feedback을 가지는 주파수 변동 기법의 모델링 및 분석)

  • Jo, Yeong-Min;Choi, Ju-Yeop;Choy, Ick;Lee, Dong-Ha
    • Proceedings of the KIPE Conference
    • /
    • 2014.07a
    • /
    • pp.225-226
    • /
    • 2014
  • 본 논문에서는 최악의 상황에서도 계통 연계형 태양광 발전 시스템에서의 단독운전 현상을 신속히 검출하여 시스템을 정지시킬 수 있게 하기 위해 Positive-feedback을 가지는 주파수 변동 기법에 대한 설계와 시뮬레이션을 바탕으로 단독운전 검출 성능 보장과 출력 전력의 품질 보장을 위한 제어기 설계 방법에 대하여 제시하고, 이를 시뮬레이션을 통해 타당성을 검증한다.

  • PDF

The Anti-islanding Scheme for a Number of Grid-connected Inverters Under Parallel Operation (병렬 연결된 다수 대 계통연계형 인버터를 위한 단독운전 방지 기법)

  • Kim, Dong-Kyune;Cho, Sang-Rae;Choy, Ick;Lee, Young-Kwoon;Choi, Ju-Yeop
    • Journal of the Korean Solar Energy Society
    • /
    • v.37 no.3
    • /
    • pp.13-22
    • /
    • 2017
  • Anti-islanding scheme of grid-connected inverter is a key function of standards compliance, since unintentional islanding results in safety hazards, reliability, and many other issues. Therefore, many anti-islanding schemes have been researched, however, most of them have problems, which deteriorate performance of islanding detection under parallel-operation. Therefore, this paper proves the reason of problems and proposes a new anti-islanding scheme that has precise islanding detection under parallel-operation in single-phase and three-phase system. Finally, both simulation and experimental result validate the proposed scheme.

Output Power Analysis for Active Frequency Drift Method (AFD 기법의 출력전력 분석)

  • Lee, Ki-Ok;Choi, Ju-Yeop;Choy, Ick;Yu, Gwon-Jong
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2009.11a
    • /
    • pp.297-302
    • /
    • 2009
  • As the grid-connected photovoltaic power conditioning systems (PVPCS) are installed in many residential areas, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. In this paper, active frequency drift (AFD) method, one of the anti-islanding analyzed by current magnitude compensation and calculation of RMS value of the output power.

  • PDF

Detection Performance and THD Analysis of Active Frequency Drift for Anti-Islanding (단독운전 방지를 위한 능동적 주파수 변환 기법의 검출 성능 및 THD 분석)

  • Jo, Yeong-Min;Choi, Ju-Yeop;Song, Seung-Ho;Choy, Ick;Lee, Young-Kwoun
    • Journal of the Korean Solar Energy Society
    • /
    • v.35 no.2
    • /
    • pp.11-19
    • /
    • 2015
  • Islanding is a phenomenon that EPS(Electric Power System) is continuously energized by PV PCS(Photovoltaic Power Conditioning System) even when EPS is isolated from the grid. Unintentional islanding will result in safety hazard, power quality degradation and many other issues. So, islanding protection of grid-connected PV PCS is a key function for standards compliance. Nowadays, many anti-islanding schemes are researched. But existing anti-islanding schemes used in PV PCS have power quality degradation and non-detection zone issues. This paper analyses not only detection performance of existed anti-islanding schemes using active frequency drift but also THD of PCS output current according to each value disturbance for anti-islanding. In addition, the lowest value of disturbance in each scheme was tabulated under guarantee of anti-islanding condition.

A Simulation for Anti-islanding Method in PV-AF System and Existing Anti-islanding Method (PV-AF시스템에서 단독운전 방지기법 및 기존 단독운전 방지기법의 시뮬레이션 해석 및 비교)

  • Kim, Gyeong-Hun;Seo, Hyo-Ryong;Lee, Soek-Ju;Park, Min-Won;Yu, In-Keun;Jeon, Jin-Hong;Kim, Seul-Gi;An, Jong-Bo
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.206-207
    • /
    • 2007
  • Islanding is the electrical phenomenon in a part of a power network disconnected from the utility, where the loads are entirely supplied by PV systems, and where the voltage and frequency are maintained around nominal values. But islanding may result in power-quality issues, interference to grid-protection devices, equipment damage, and even personnel safety hazards[4]. Therefore, islanding must be detected and stopped. The existing anti-islanding methods have NDZ(None-detection Zone) or power quality degradation. But PV-AF power generation system has the function of not only shunt active filter but also anti-islanding method without NDZ. In this paper, It is proved that PV-AF system has originally the function of anti-islanding without not only NDZ and but current distortion

  • PDF

THD Analysis of Output Current for Active Frequency Drift Method in Anti-islanding (능동적 주파수 변환기법의 출력전류 고조파 왜형율 분석)

  • Lee, Ki-Ok;Choi, Ju-Yeop;Choy, Ick;Yu, Gwon-Jong;An, Jin-Ung
    • Journal of the Korean Solar Energy Society
    • /
    • v.30 no.1
    • /
    • pp.7-12
    • /
    • 2010
  • As many grid-connected photovoltaic power conditioning systems (PVPCS)are installed in many residential areas simultaneously, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. In this paper, active frequency drift (AFD) method, one of the anti-islanding methods which is analyzed by current magnitude compensation and calculation of the fundamental component. Both harmonic component and RMS value of the output current for THD analysis are provided and verified by simulation.