스파이럴리 인덴티드 전열관 내부에서의 압력 강하 및 전열 특성에 관한 고찰 (Investigation on Characteristics of Pressure Drop and Heat Transfer in the Spirally Indented Tubes)

  • 김도형;김익생;김균석;유병훈;김춘동
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2001년도 춘계학술대회논문집D
    • /
    • pp.440-446
    • /
    • 2001
  • The pressure drop and heat transfer of the spirally indented tubes were measured and analyzed. Eight sample tubes of indentation depth 0.4, 0.7mm and indentation pitch 10, 14, 20, 26mm were used in this experimental tests. And all the tubes have same outer diameter of 16mm, and same indentation start number of I. Air was used as the internal fluid from 10000 to 50000 for Reynolds Number. The friction factors and heat transfer coefficients have increased when indentation depths increase and indentation pitches decrease. Finally, the correlations were made between the effect of the tube geometry and characteristics of tubes for the pressure drop and heat transfer.

  • PDF

공조용 알루미늄 납작관 내의 R-410A 대류 비등 (Convective Boiling of R-410A in an Aluminum Flat Tube for Air-Conditioning Application)

  • 김내현
    • 한국산학기술학회논문지
    • /
    • 제16권5호
    • /
    • pp.3006-3013
    • /
    • 2015
  • 원관 열교환기보다 납작관 열교환기를 사용하면 전열성능을 한층 향상시킬 수 있다. 납작관 열교환기를 적절히 설계하기 위해서는 관 내측 열전달계수를 알아야 한다. 본 실험에서는 수력직경 1.41mm인 알루미늄 납작관 내 R-410A 대류 비등 열전달계수를 구하였다. 실험범위는 질량유속 $200{\sim}600kg/m^2s$, 열유속 $5{\sim}15kg/m^2$, 포화온도 $5{\sim}15^{\circ}C$이다. 실험 결과 열전달계수는 임계 건도를 기점으로 감소함을 보였다. 임계 건도는 열유속이 증가할수록 감소하고, 질량유속이 감소할수록 감소하였다. 이는 높은 열유속 또는 낮은 질량유속에서 대류의 영향이 작게 되고 따라서 조기에 dryout이 발생되기 때문에 나타나는 현상으로 판단된다. 열전달계수는 질량유속이 증가할수록 증가하였다. 그러나 낮은 건도에서는 질량유속의 영향은 미미하였다. 열전달계수는 포화온도가 증가할수록 증가하였다. 하지만 이런 경향은 열유속이 작아지면 감소하였다. Shah와 Kaew-On et al. 상관식은 본 실험자료를 적절히 예측하였다.