• Title/Summary/Keyword: 내진검증

Search Result 315, Processing Time 0.041 seconds

A Test Verified Model Development Study for Seismic Qualification(Safety) (내진검증(안전)을 위한 실험적 고찰을 이용한 해석 모델 개발연구)

  • Uk-Hwan Sur
    • Journal of the Korean Society of Safety
    • /
    • v.13 no.4
    • /
    • pp.286-291
    • /
    • 1998
  • This paper includes discussion on developing the test verified finite element model for one of the seismic qualification(safety) approaches. It presents a test verified finite element model of a UPS(Uninterruptible Power Supply System) to be used at KMRR, KAERI. The test verified model predicts natural frequencies within 5 percent error for all major modes below 50Hz. This model accurately represents the dynamic characteristics of the actual hardware and is qualified for its use in the final stress analysis for seismic verification.

  • PDF

Seismic Qualification of Class 1E Battery by Combined Analysis and Testing (수치해석과 실험을 통한 안전등급 축전지의 내진검증)

  • 김영중;박성환;정태영;정정훈
    • Proceedings of the Korean Society for Noise and Vibration Engineering Conference
    • /
    • 1992.10a
    • /
    • pp.87-91
    • /
    • 1992
  • 축전지를 탑재한 프레임형 랙에 대한 공진탐색시험결과를 이용하여 유한요 소에 의한 수치해석모형을 결정하였다. 내진검증시험은 에이징시험을 거친 3 개의 축전지를 포함하여 28개의 축전지를 탑재한 시험랙을 대상으로 수행되 었다. 공진탐색시험으로부터 구한 모달특성치를 이용하여 지진응답을 해석하 였으며 실험치와 부합함을 확인하였다. 시험랙의 지진응답이 실제 설치될 60 개의 축전지를 갖는 전체랙의 응답보다 크므로, 시험랙에 의한 내진검증이 보다 열악한 조건에서 수행되었다고 볼 수 있다. 시험랙에 대한 내진검증시 구조부재의 구조적 안정성과 축전지의 성능유지를 확인한 바 있으므로 전체 랙의 경우에도 내진검증이 이루어졌다고 판단된다.

  • PDF

UPS를 위한 내진검증 해석 모델 개발연구

  • 서욱환
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 1998.11a
    • /
    • pp.253-260
    • /
    • 1998
  • 원자력 안전과 관련된 시스템에서 요구되는 것 중에서 필수적인 것은 내진 발생에 대비하는 검증이 있다. 이 논문은 내진 검증을 증명하고 장차 사용을 위한 증명된 유한요소 해석모델을 개발하는 방법이 제시되었다. 여기서 사용된 모델은 한국원자력연구소의 KMRR에서 사용되기 위해 이화전기산업(주)에서 제작되었다. (중략)

  • PDF

Seimic Qualification of Safety Related Reactor Control Panel (원자로 안전관련 정지반의 내진검증)

  • Yoo, Bong;Ahn, Gyu-Seok
    • Proceedings of the Korean Society for Noise and Vibration Engineering Conference
    • /
    • 1990.10a
    • /
    • pp.129-133
    • /
    • 1990
  • 본 논문에서는 원자로정지반의 실제제작을 위한 예비단계로서 예비설계된 정지반의 전산모델을 이용하여 내진해석을 수행하였으며 이는 내진설계자료 및 내진시험에 대한 검증자료로 활용될 수 있을 것이다.

  • PDF

Seismic Qualification of Plant Protection System Cabinet for Nuclear Power Plant (원자력발전소 보호시스템 캐비넷의 내진검증)

  • 정명조;황원걸
    • Computational Structural Engineering
    • /
    • v.6 no.2
    • /
    • pp.79-86
    • /
    • 1993
  • A method to verify seismic qualification of the plant protection system cabinet for a nuclear power plant is presented. A finite element model of the cabinet is developed and the dynamic characteristics are obtained. The results of the modal analysis provide insight into the fundamental dynamic properties of the structure, which correspond to the frequency of the peak values of the input seismic spectrum. It necessitates the design modification of the reference cabinet. Techniques for verifying structural integrity and operability are exemplified by summarizing response spectrum and time history analyses of the structure.

  • PDF

초점 - 원자력연구원 하나로 건물 내진 보강 공사 현황

  • 한국원자력산업회의
    • Nuclear industry
    • /
    • v.37 no.1
    • /
    • pp.7-14
    • /
    • 2017
  • 작년 경주 지진으로 원자력 안전에 대한 시민들의 촉각이 예민해져 있는 가운데 최근 대전 지역에서 원자력연구원의 하나로 원자로 건물 외벽 내진 보강 공사 방식에 대한 검증을 요구하는 여론이 일고 있다. 그 동안 원자력연구원에서 진행한 하나로 건물 내진 보강 공사 배경과 주요 일정, 설계 개념, 구조 성능 검증 실험, 공사 현황, 건물 성능 점검, 안전 관리, 정보 공개 및 검증, 향후 계획 등을 정리하여 종합했다.

  • PDF

Seismic Performance Evaluation of Medium-and Low-rise R/C Buildings Strengthened with RCSF External Connection Method by Pseudo Dynamic Test (유사동적실험에 의한 RCSF 외부접합공법으로 내진보강 된 중·저층 철근콘크리트 건물의 내진성능 평가)

  • Lee, Kang-Seok
    • Journal of the Korea institute for structural maintenance and inspection
    • /
    • v.19 no.1
    • /
    • pp.13-22
    • /
    • 2015
  • In this study, a new RCSF (Reinforced Concrete Steel Frame) external connection method is proposed for seismic strengthening of medium-and low-rise reinforced concrete buildings. The RCSF method, proposed in this study, is capable of carrying out the seismic retrofitting construction while residents can live inside structures. The method is one of the strength design approach by retrofit which can easily increase the ultimate lateral load capacity of concrete buildings controlled by shear. The pseudo-dynamic test, designed using a existing school building in Korea, was carried out in order to verify the seismic strengthening effects of the proposed method in terms of the maximum load carrying capacity and ductility. Test results revealed that the proposed RCSF strengthening method installed in RC frame enhanced conspicuously the strength and displacement capacities, and the method can resist markedly under the large scaled earthquake intensity level.

A Proposal of Rapid-Screening Method for Seismic Capacity Evaluation of Low-Rise R/C Buildings - Part 3. Verification of Applicability of Rapid-Screening Method - (저층 철근콘크리트 건물의 간이 내진성능 평가법 제안 - Part 3. 내진성능 평가법의 타당성 검증 -)

  • Lee, Kang-Seok;Kim, Yong-In;Wi, Jeong-Doo
    • Proceedings of the Korea Concrete Institute Conference
    • /
    • 2009.05a
    • /
    • pp.467-468
    • /
    • 2009
  • In this study, seismic capacity of R/C school buildings are investigated on the basis of the 2nd and 3rd level procedures of the Japanese Standard for Evaluation of Seismic Capacity of Existing R/C Buildings, push-over analysis and nonlinear dynamic analysis, respectively. In order to verify the applicability of the new method proposed in this study, relationships between evaluation results of the proposed methods shown in Part-2 and detailed evaluation methods mentioned above are compared.

  • PDF

Development of Model for Seismic Qualification of Electronic Enclosure for Nuclear Power Plant (원자력발전소용 전자기기함을 위한 내진검증 해석 모델 개발연구)

  • Sur, Uk-Hwan
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.35 no.1
    • /
    • pp.47-52
    • /
    • 2011
  • In this paper, we describe the development of a finite-element model for seismic qualification. This paper presents finite-element analysis model of the electronic enclosure to be used at Arkansas nuclear power plant, USA. The verified model predicts natural frequencies within 5% error for all major modes below 50 Hz. The finite element lumped mass approach and the finite element stiffness approach using the COSMOSM finite element code is applied for static, eigenvalue, and dynamic analyses of the mathematical model of this system. The FEM model indicates that the stress levels corresponding to the specified loading conditions are below the allowable stress levels that have been specified in the AISC Code. The findings conclude that the electronic enclosure will withstand the seismic levels stated in the reference documents.