• Title/Summary/Keyword: 난방 능력

Search Result 46, Processing Time 0.024 seconds

Investigation of Heating Performance of Kerosene Fan Heater (석유 홴 히터의 난방 능력 고찰)

  • Kim, Jang-Kweon;Jeong, Kyu-Jo
    • Journal of Power System Engineering
    • /
    • v.1 no.1
    • /
    • pp.51-60
    • /
    • 1997
  • In this paper, we investigated the heating performance and the basic characteristics required for normal combustion of kerosene fan heater. And also the iso-velocity contours and the iso-temperature contours of hot gas discharged from the exit of kerosene fan heater were analyzed. The experiment was carried out with kerosene fan heater attached to the blow-down-type subsonic wind tunnel with a test section of $240mm{\times}240mm{\times}1200mm$. The purpose of this paper was to obtain the basic data for new design from conventional kerosene fan heater. Consequently it was found that (i) the pressure ratio $P_2/P_1$ had a comparatively constant value of 0.844 according to the increase of the revolution of turbo fan, (ii) the primary excess air ratio had a range of $0.84{\sim}1.11$ during normal combustion, and (iii) the heating performance of kerosene fan heater had a range of $1,494{\sim}3,852kcal/hr$.

  • PDF

Study on the Performance of Heat Pump Using Non-azeotropic Refrigerant Mixtures R-22+R-114 (비공비혼합냉매 R-22+R-114를 이용한 열펌프의 성능에 관한 연구)

  • 박기원;구학근;오후규
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.17 no.9
    • /
    • pp.2131-2137
    • /
    • 1993
  • This study, examines the performance and the heat pump cycle systematizing characteristics for non-azeotropic refrigerant systems. In order to conduct such an examination, the cycle characteristics of heat pumps for pure R-22, R-114, and their mixtures were experimentally investigated. The results show that cooling/heating capacities for the mixtures was more suited at the evaporating temperature of $5^{\circ}C$ than that of $0^{\circ}C$, $-5^{\circ}C$, and $-10^{\circ}C$. The C.O.P of the 50 wt% mixtures was considerably higher than for pure R-22, and the compression power of the 25 wt% was as much as 60% lower than that of pure R-22. Even small fractional mixture variations can lead to significant changes in the characteristics of the heat pump cycle. This experiment verified the importance of accurate weight fractions of refrigerant mixtures.

Development of Simulation for Vuilleumier Cycle Heat Pump (VM 사이클 히트펌프 설계프로그램의 개발)

  • 박병덕;이기우
    • Journal of Energy Engineering
    • /
    • v.10 no.2
    • /
    • pp.105-113
    • /
    • 2001
  • 지구환경문제와 에너지문제를 해소하는 한 방법으로서 Vuilleumier 사이클 기관(VM)을 이용한 공조기형 열구동형 히트펌프시스템(VMHP)이 각광을 받고 있다. VMHP의 제작에 있어서는 VM의 각 부분의 이론적 검토 및 최적설계를 위한 해석프로그램의 개발이 필수적이고 최적설계를 위한 설계 기본서의 도출 및 설계자료의 확보가 필요하다. VMHP의 상세한 성능해석이나 설계에 활용 가능한 성능해석프로그램을 개발하였다. 해석은 VM의 시스템의 각 부분을 11개 부분으로 나누어 단열모델해석으로 수행하였다. 열교환기에서의 열전달 성능과 재생기손실, 열전도손실, 셔틀손실, 유동에 의한 압력손실과 열압축측과 열펌프측 사이의 마찰손실, 피스턴실 및 로드실의 마찰손실을 고려한 해석을 수행하였다. 해석에 의한 계산치의 정확성을 본 해석결과를 이용하여 제작한 시험기에 의해 비교하였다. 계산치와 시험기에 의한 전체성능을 비교하였고 또한 각각의 손실에서 고유한 파라미터를 추출하여 그 파라미터의 변화에 따른 열손실 전체의 변화 정도를 파악하여 실험치와 계산치의 정상적인 비교로부터 성능해석의 정도를 비교하였다. 비교결과에 의해 난방능력은 8%, 냉방능력은 19%의 최대오차로서 본 해석결과가 VMHP의 설계를 위해 유용한 수단으로 사용될 수 있음을 확인하였다.

  • PDF

Design and performance analysis of water-to-air heat pump system using double-tube heat exchanger (이중관 열교환기를 사용한 물 대 공기 열펌프 시스템의 설계와 성능해석)

  • Han, D.Y.;Park, K.J.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.9 no.4
    • /
    • pp.462-471
    • /
    • 1997
  • The water-to-air heat pump system requires relatively lower energy consumption and less installation space. The heat exchangers used for this system are the finned-tube type for the indoor unit and the double-tube type for the outdoor unit. Mathematical models for this system are developed and programmed in computer. Experimental data from various conditions are obtained and compared with calculated values from the computer simulation program. Differences of cooling capacity and COP are 1.25% and 0.47%, and those of heating capacity and COP are 0.51% and 0.13%, respectively. Simulation results are in good agreement with test results. Therefore, the developed program is effectively used for the design and the performance prediction of water-to-air heat pump system.

  • PDF

A Study on the Improvement of Performance for Centralized Air Conditioning System by Using Air-Cooled Air Conditioner - The Case of Mokpo National Maritime University - (공랭식 에어컨을 이용한 중앙 집중 공조시스템의 성능 개선에 관한 연구 - 실습선 새누리호를 중심으로 -)

  • Kim, Hong-Ryel;Han, Seung-Hun
    • Journal of the Korean Society of Marine Environment & Safety
    • /
    • v.19 no.2
    • /
    • pp.207-212
    • /
    • 2013
  • In this study, distributed the ship's Centralized Air Conditioning System the way an individual to replace the air conditioning system by using Air-cooled air conditioner. Research results, Individually separated air conditioning system complement the heat source control and thermal efficiency problems and improves the efficiency of the device was confirmed. In addition, under the same conditions refrigeration capacity and coefficient of performance of the device, an average of about 3 %, 23 ~ 26 %, higher, Chilled Water Plants Compressor power consumption is about 12 % lower. Also while heating under the same conditions, power consumption is about 33.5 % lower. Therefore Individually Separated Air Conditioning System greatly contributed to the improved performance of the device and living spaces for comfortable temperature and humidity control as well as heating source could be obtained.

Characteristic Analysis of Hybrid Desiccant Cooling System for District Heating in Residential Environment (지역난방에 연계된 하이브리드 제습냉방시스템의 주거환경에서의 성능 분석)

  • Ahn, Joon;Kim, Jaeyool;Kang, Byung Ha
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.38 no.7
    • /
    • pp.571-579
    • /
    • 2014
  • A series of field tests on hybrid desiccant cooling systems were conducted in July-August, 2013. The temperature and humidity of the supply and return air, power, and heat consumption were monitored and transferred in real time through the Internet. The performance parameters of the cooling system, namely, cooling capacity and COP (coefficient of performance), were evaluated from the measured data and their variations under outdoor conditions was analyzed. It was found that with increase in the outdoor temperature, the total energy decreases and cooling capacity increases whereas the latter decreases with increase in the outdoor humidity. The COP was also found to increase with the increase in outdoor temperature.

Theoretical approach on the heating and cooling system design for an effective operation of Li-ion batteries for electric vehicles (전기구동 자동차용 리튬이온 배터리의 고효율 운전을 위한 냉방 및 난방 시스템 설계에 대한 이론적 접근법)

  • Kim, Dae-Wan;Lee, Moo-Yeon
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.15 no.5
    • /
    • pp.2545-2552
    • /
    • 2014
  • This study is aiming to suggest the effective thermal management system design technologies for the high voltage and capacity battery system of the electricity driven vehicles and introduce the theoretical designing methods. In order to investigate the effective operation of the battery system for the electricity driven vehicles, the heat generation model for Li-ion battery system using the chemical reaction while charging and discharging was suggested and the thermal loads of the heat sources (air or liquid) for cooling and heating were calculated using energy balance. Especially, the design methods for the cooling and heating of the battery system for maintaining the optimum operation temperature were investigated under heating, cooling and generated heat (during charging and discharging) conditions. The battery thermal management system for the effective battery operation of the electricity driven vehicles was suggested reasonably depending on the variation of the season and operation conditions. In addition, at the same conditions under summer season, the cooling method using the liquid and active cooling technique showed a relatively high capacity, while cooling method using the passive cooling technique showed a relatively low capacity.

An Experimental Study on the Performance of a Heat Pump for the Cold Climate (한랭지용 열펌프의 저온난방 성능에 관한 실험적 연구)

  • Ju Jeong-Dong;Bae Kyung-Su;Hwang Young-Kyu;Lee Yun-Yong;Jeong Gyoo-Ha;Oh Sang-Kyong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.1
    • /
    • pp.39-46
    • /
    • 2005
  • The present study concerns an experimental study of a R-22 heat pump system consisted of liquid and liquid heat exchangers. The test was performed for various systems of a single-, tandem-, and two stage-cycle at the same environmental conditions of temperature. Various experiments of the heat pump system were peformed to compare the heating capacity and COP, when the outdoor temperature is near $-15^{\circ}C$ and the indoor temperature is $20^{\circ}C.$ As the results of the present study, the system of Tandem(parallel) cycle showed the best heating performance, while the discharge temperature of refrigerant was too high. In case of the system of two stage cycle, the performance characteristics were significantly improved by employing the inter cooler.

Improvement of Heat Pump Heating Performance by Selective Heat Storage Using Air Heat of Inside and Outside Greenhouse (온실 내외부 공기열의 선택적 축열에 의한 히트펌프 난방성능 개선)

  • Kwon, Jin Kyung;Kim, Seung Hee;Jeon, Jong Gil;Kang, Youn Koo;Jang, Kab Yeol
    • Journal of Bio-Environment Control
    • /
    • v.26 no.4
    • /
    • pp.353-360
    • /
    • 2017
  • In this study, the design and performance test of the air to water heat pump capable of producing hot water for greenhouse heating by using the surplus solar heat inside the greenhouse and the air heat outside greenhouse as the selective heat source were conducted. The heat storage operations using the surplus solar heat and the outside air heat were designed to be switched according to the setting temperature of the greenhouse in consideration of the optimum temperature range of the crop. In the developed system, it was possible to automatically control the switching of heat storage operation, heating and ventilation by setting 12 reference temperatures on the control panel. In the selective heat storage operation with the surplus solar heat and outside air heat, the temperature of thermal storage tank was controlled variably from $35^{\circ}C$ to $52^{\circ}C$ according to the heat storage rate and heating load. The heat storage operation times using the surplus solar heat and outside air heat were 23.1% and 30.7% of the experimental time respectively and the heat pump pause time was 46.2%. COP(coefficient of performance) of the heat pump of the heat storage operation using the surplus solar heat and outside air heat were 3.83 and 2.77 respectively and was 3.24 for whole selective heat storage operation. For the comparative experiment, the heat storage operation using the outside air heat only was performed under the condition that the temperature of the thermal storage tank was controlled constantly from 50 to $52^{\circ}C$, and COP was analyzed to be 2.33. As a result, it was confirmed that the COP of the heat storage operation using the surplus solar heat and outside air heat as selective heat source and the variable temperature control of the thermal storage tank was 39% higher than that of the general heat storage operation using the outside air heat only and the constant temperature control of the thermal storage tank.

Performance of the Geothermal Heat Pump using Vapor Injection for Hot Water (증기분사를 적용한 고온수용 지열 히트펌프의 성능특성)

  • Park, Yong-Jung;Park, Byung-Duck
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.25 no.3
    • /
    • pp.297-304
    • /
    • 2014
  • The purpose of this study is to evaluate the experimental performance characteristics of a water-to-water geothermal heat pump featuring a vapor refrigerant injection for the production of hot water. The performance of geothermal heat pump with a vapor injection was evaluated by comparing with that of a conventional geothermal heat pump without a vapor injection. For heating operation, the geothermal heat pump with a vapor injection is superior in COP and heating capacity. The vapor injection was more effective for supplying hot water while overloading. The vapor injection was effective for the improvement of the cooling capacity. However, the vapor injection was not effective for the increasing of COP according to the increased input of a compressor. The advantage of vapor injection in water-to-water geothermal heat pump become disappeared while cooling operation with lower part loading.