• 제목/요약/키워드: 난방성능계수

검색결과 81건 처리시간 0.023초

지열히트펌프 냉매자동조절에 따른 냉·난방 성능실험에 관한 연구 (A Study on the Cooling Heating Performance Experiment by Refrigerant Auto Control of Geothermal Heat Pump)

  • 구남열;서승일
    • 한국지열·수열에너지학회논문집
    • /
    • 제11권1호
    • /
    • pp.1-6
    • /
    • 2015
  • This study presents analysis of the experimental data meeting conditions of several applications in real time. The results of this experimental study are as follows: Respectively in cooling and heating performance, a refrigerant charge tank can take automatic control of variation of the refrigerant quantity by controling pressure and temperature of system and outlet water temperature. The COP shows 3.5 in cooling operation and 3.2 in heating operation. The refrigerant quantity increases 0.69 kJ/h. When the outdoor temperature decreases $1^{\circ}C$, Therefore if the temperature become lower from $25^{\circ}C$ to $-16^{\circ}C$, the refrigerant quantity increases about 9.5%. Compared to the normal state experiment results, the COP in automatic control of the refrigerant quantity rises roughly 10%.

증기분사를 적용한 고온수용 지열 히트펌프의 성능특성 (Performance of the Geothermal Heat Pump using Vapor Injection for Hot Water)

  • 박용정;박병덕
    • 한국수소및신에너지학회논문집
    • /
    • 제25권3호
    • /
    • pp.297-304
    • /
    • 2014
  • The purpose of this study is to evaluate the experimental performance characteristics of a water-to-water geothermal heat pump featuring a vapor refrigerant injection for the production of hot water. The performance of geothermal heat pump with a vapor injection was evaluated by comparing with that of a conventional geothermal heat pump without a vapor injection. For heating operation, the geothermal heat pump with a vapor injection is superior in COP and heating capacity. The vapor injection was more effective for supplying hot water while overloading. The vapor injection was effective for the improvement of the cooling capacity. However, the vapor injection was not effective for the increasing of COP according to the increased input of a compressor. The advantage of vapor injection in water-to-water geothermal heat pump become disappeared while cooling operation with lower part loading.

지열원 멀티 열펌프 시스템의 시설원예 적용 난방성능 특성 실증 연구 (Heating Performance of a Ground Source Multi-Heat Pump for a Greenhouse)

  • 강신형;최종민;문제명;권형진
    • 설비공학논문집
    • /
    • 제22권6호
    • /
    • pp.337-344
    • /
    • 2010
  • Good plant-growth conditions can be achieved by means of using greenhouses. One of the main issues in greenhouse cultivation is energy savings through the development of high efficient heating and cooling system. GSHPs are one of the recommended systems to cope with this pending need. The aim of this study is to investigate the heating performance of ground source multi-heat pump system installed in a greenhouse under part load conditions. Daily average heating COP of the heat pump unit was very high by at least 7.4, because of relatively large condenser, evaporator, and mass flow rate through ground loop heat exchanger. However, the system COP, overall heating coefficient of the performance of the system with heat pump unit and GLHX, decreased drastically due to relatively large power consumption of circulating pump under part load condition. It is suggested that the technology to enhance the performance of the ground source multi-heat pump system for a greenhouse under part load conditions should be developed.

건물일체형 지열히트펌프시스템의 난방 성능 분석 (Heating Performance Analysis of Building Integrated Geothermal System)

  • 김상진;이진욱;김태연;이승복
    • 한국태양에너지학회:학술대회논문집
    • /
    • 한국태양에너지학회 2012년도 춘계학술발표대회 논문집
    • /
    • pp.206-210
    • /
    • 2012
  • Ground source heat pump is a central heating and cooling system that pumps heat to or from the ground. Building Integrated Geothermal system used in this experiment is one of the Ground Source Heat Pump Systems which utilize energy pile. The purpose of this study is to evaluate heating performance of the system. The building is a low-energy experiment apartment in Yonsei University Songdo Campus and the subject is one of the energy reduced houses in this apartment. In the experiment, indoor temperature, outdoor temperature and the inlet and outlet temperature of ground heat exchanger and subject model, were measured. Then the heat pump's Coefficient of performance(COP) of the heat pump was calculated. As a result, the COP of heat pump is 4-5. Although the depth of the ground heat exchanger in this experiment is shallower than usual heat exchanger, the result of heating performance of this system was good as well.

  • PDF

지열원 멀티 히트펌프의 동절기 난방성능에 관한 실증 연구 (Verification experiment of a ground source multi-heat pump at heating season)

  • 최종민;임효재;강신형;최재호;문제명;권영석;권형진;김록희
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.52-57
    • /
    • 2009
  • This paper describes the multi-heat pumps applied in an ground source heat pump system for an actual building. The performance of a ground source multi-heat pump installed in the field was investigated at heating season. The average COP of the systems with single U-tube and double tube type GLHXs were 4.8 and 5.0, respectively. It is needed to investigate the long term performance of double tube type GLHX, because the reduction of inlet temperature of OD HX for this GLHX was larger than it for U-tube GLHX.

  • PDF

2단 승온 캐스케이드 히트펌프의 성능 특성에 관한 연구 (Study on the Performance of a Cascade Heat Pump with Two-stage Water Heating Process)

  • 장한별;최종민
    • 한국지열·수열에너지학회논문집
    • /
    • 제12권4호
    • /
    • pp.27-32
    • /
    • 2016
  • It is estimated that only heating and cooling take about one third of the total energy consumption worldwide. However, the conventional heating and cooling systems have low efficiencies. Also, boilers and electric heaters that are mostly used to generate both domestic and industrial hot water are inefficient and high energy consumers. For this reason, cascade heat pumps which are known to be very energy efficient and have less environmental impact are being promoted to replace conventional heating, cooling and hot water systems. In this study, a newly designed cascade heat pump by two-stage water heating method has been experimentally investigated. By adopting the auxiliary heat exchanger, the performance of the system was increased. The performance enhancement rate of the system could be maximized by adjusting the low stage compressor speed rather than the high stage compressor speed. The performance of the system with the auxiliary heat exchanger was enhanced by 16.5%.

R22/R142b 혼합냉매를 사용한 열펌프의 성능 (Experimental Study on the Performance of Heat Pump Using Refrigerant Mixture R22/R142b)

  • 김민수;장세동;노승탁
    • 설비공학논문집
    • /
    • 제4권1호
    • /
    • pp.33-47
    • /
    • 1992
  • Experimental investigation on the performance of a heat pump system using refrigerant mixtures is done. The condenser and the evaporator are double pipe heat exchangers of counter flow type and the compressor is driven by a variable speed motor. The refrigerant mixture used in the experiment is R22/R142b. Experiments are performed by changing the compressor speed, composition on ratio of mixture, and the average temperatures of condenser and evaporator. The compressor work, heating capacity and the coefficient of performance are calculated. Results show that the heating capacity can be changed by varying the mass flow rate of refrigerant mixtures to meet the heating load. It is shown that the capacity control by changing the composition ratio is more effective than by changing the compressor speed. Under the condition where the external conditions are fixed and the heating loads are equal, the coefficient of performance has its maximum value near 50 : 50 mass fraction of the refrigerant mixture in this study.

  • PDF

과부하 및 착.제상 조건에서 히트펌프 칠러의 난방성능에 관한 실험 연구 (Experimental Study on Heating Performance of Heat Pump Chiller under Overload, Frost and Defrost Conditions)

  • 김정석;권영철;전종균;박삼진;한화택
    • 설비공학논문집
    • /
    • 제23권7호
    • /
    • pp.477-482
    • /
    • 2011
  • In the present study, the performance characteristics of the heat pump chiller under heating conditions were experimentally investigated. Capacity, input power and COP under overload, frost and defrost conditions were obtained. The experimental data for the heat pump chiller were measured using the air-enthalpy calorimeter and the constant temperature water bath. At overload condition, the heating capacity and COP increase about 25.7% and 19.1%, respectively. The variations of the evaporator, the compressor outlet and the condenser temperature were obtained under frost and defrost conditions. The frost and defrost period of the heat exchanger decreases about 36.0~56.1%.

무공해 자동차용 수열원 히트펌프 시스템의 난방 성능에 관한 실험적 연구 (An Experimental Study on the Heating Performance of Coolant Heat Source Heat Pump System for Zero Emission Vehicles)

  • 이대웅
    • 한국자동차공학회논문집
    • /
    • 제22권7호
    • /
    • pp.57-62
    • /
    • 2014
  • This study presented the feasibility of a coolant heat-source heat pump system as an alternative heating system for electrically driven vehicles. Heat pumps are among the most environmentally friendly and efficient heating technologies in residential buildings. In various countries, electric mobiles devices such as EV, PHEV, and FCEV, have been mainly concerned with heat pumps for new mobile markets. The experiments herein were conducted for various ambient temperatures and coolant temperatures to reflect the winter season. The system, a coolant heat-source heat pump, consisted of an inside heat exchanger, an outside heat exchanger, a motor driven compressor, an electronic expansion valve, and plumbing parts. For the experimental results, the maximum heating capacity and air discharge temperature are up to 6.3 kW and $62^{\circ}C$ respectively at an ambient temperature of $10^{\circ}C$, and coolant at $10^{\circ}C$. However, at $-20^{\circ}C$ ambient temperature and $-10^{\circ}C$ coolant temperature, conditions were insufficient to warm the cabin as the air discharge temperature was $13^{\circ}C$.

지중열원 열펌프 시스템의 난방성능 해석 (A Study on the Heating Performance of Ground Source Heat Pump System)

  • 우정선;김대기;이세균
    • 설비공학논문집
    • /
    • 제16권12호
    • /
    • pp.1175-1182
    • /
    • 2004
  • Installations of vertical boreholes for the ground source heat pump system are expensive to install. One way to reduce the initial cost is to increase the specific heat extraction rate of borehole system. However, as the specific heat extraction rate increases the temperature of borehole fluid decreases with the resultant lower Coefficient Of Performance in Heating(COPH) of heat pump system. The purpose of this study is to provide the basic informations about the performance of heat pump system with the specific heat extraction rate and soil thermal properties such as thermal conductivity and temperature. It is shown that the specific heat extraction rate is the most important parameter for the ground source heat pump system. To obtain the reasonable COPH value (COPH > 3) the heat extraction rate should be about 25 W/m or less. Accurate measurements of soil thermal properties are also very important to design the system properly. The effects of borehole thermal resistances are also examined in this study.