• Title/Summary/Keyword: 난방모드

Search Result 25, Processing Time 0.019 seconds

Experimental Study on the Performance Improvement of a Simultaneous Heating and Cooling Heat Pump in the Heating-main Operating Mode (난방주체 운전모드에서의 동시냉난방 열펌프 성능향상에 관한 실험적 연구)

  • Kang, Hoon;Jung, Hyen-Joon;Joo, Young-Ju;Kim, Yong-Chan;Choi, Jong-Min
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.4
    • /
    • pp.245-251
    • /
    • 2008
  • The cooling load in winter is significant in buildings and hotels because of the usage of office equipments and the high efficiency of wall insulation. Hence, the development of a multi-heat pump that can cover heating and cooling simultaneously for each indoor unit is required. In this study, the operating characteristics and performance of a simultaneous heating and cooling heat pump in the heating-main operating mode were investigated experimentally. The system adopted a variable speed compressor with four indoor units and one outdoor unit with R-410A. In the heating-main mode, the cooling capacity was lower than the design cooling capacity due to the reduction of the flow rate in the indoor unit for the cooling, with the increase of the heating capacity. To solve these problems, the performance characteristics of the simultaneous heating and cooling heat pump in the heating-main mode were investigated by varying the flow rate to the indoor unit for the cooling and the compressor rotating speed. In addition, the adequate control methods were suggested to improve the system efficiency.

Verification experiment of a ground source multi-heat pump at heating season (지열원 멀티 히트펌프의 동절기 난방성능에 관한 실증 연구)

  • Choi, Jong-Min;Lim, Hyo-Jae;Kang, Shin-Hyung;Choi, Jae-Ho;Moon, Je-Myung;Kwon, Young-Seok;Kwon, Hyung-Jin;Kim, Rock-Hee
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.52-57
    • /
    • 2009
  • This paper describes the multi-heat pumps applied in an ground source heat pump system for an actual building. The performance of a ground source multi-heat pump installed in the field was investigated at heating season. The average COP of the systems with single U-tube and double tube type GLHXs were 4.8 and 5.0, respectively. It is needed to investigate the long term performance of double tube type GLHX, because the reduction of inlet temperature of OD HX for this GLHX was larger than it for U-tube GLHX.

  • PDF

A Study on Estimating Real-time Thermal Load During GHP Operation in Heating Mode (GHP 난방 모드 운전시 실시간 부하 추정방법에 관한 연구)

  • Seo, Jeong-A;Shin, Young-Gy;Oh, Se-Je;Jeong, Sang-Duck;Ji, Kyoung-Chul;Jeong, Jin-Hee
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.1
    • /
    • pp.32-37
    • /
    • 2011
  • The present study has been conducted to propose an algorithm regarding real-time load estimation of a gas engine-driven heat pump. In the study, thermal load of an indoor unit is estimated in terms of air-side and refrigerant-side. The air-side estimation is based on a typical heat exchanger model and is found to be in good agreement with experimental data. When it comes to the refrigerant-side load, a pressure difference across a valve must be estimated. For the estimation, it is assumed to be proportional to a bigger pressure difference that is available either by measurement or by estimation. Relative good agreement between the air- and refrigerant-sides suggests that the assumption may be plausible for the load estimation. The summed flow rate of all of indoor units is in good agreement with the throughput of the compressor which are calculated from the manufacturer's software. Accordingly, estimated thermal loads are also in good agreement. The proposed algorithm may be further developed for improved control algorithm and fault diagnosis.

Research on the Thermal Comfort Heating Mode Considering Psychological and Physiological Response of Automobile Drivers (운전자의 심리·생리 반응을 고려한 승용차 쾌적 난방 모드에 관한 연구)

  • Kim, Min Soo;Kum, Jong Soo;Park, Jong Il;Kim, Dong Gyu
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.30 no.3
    • /
    • pp.149-157
    • /
    • 2018
  • In this research, the psychological and physiological reactions of the driver were measured during winter to evaluate thermal comfort. The experiment was conducted using 3 different cases which are hot air heating, warm-wire seat heating and hot air & warm-wire seat heater operating simultaneously. With regard to psychological reaction, the warm-wire heating mode was the most preferred. The reason is that it is dry in other cases. With regard to EEG response, thermal comfort increased by 37% in warm air mode heating. In addition, when the warm-wire heating mode and the hot air & warm-wire heating mode were simultaneously operated, the thermal comfort continuously increased by between 17% and 20% for 20 minutes after boarding. Under the change of the autonomic nervous system, the thermal stress level increased by 23% after 15 minutes on board in the hot air heating mode and decreased continuously by 13% during the warm-wire seat heating mode. We recommended the hot air heating mode is only used for a short time to raise the inside temperature during the early boarding period and that warm-wire seat heating mode be actively utilized.

Impact of IODM and ENSO on the East Asian Monsoon: Simulations through NCAR Community Atmospheric Model (동아시아 몬순 지역에서 IODM과 ENSO의 영향 : NCAR Community Atmospheric Model을 이용한 모의 실험)

  • Oh J.-H.;Chaudhari H. S.;Kripalani R. H.
    • Korean Journal of Agricultural and Forest Meteorology
    • /
    • v.7 no.4
    • /
    • pp.240-249
    • /
    • 2005
  • The normal Indian Ocean is characterized by warmer waters over the eastern region and cooler waters over the western region. Changes in sea surface temperature (SST) over the western and eastern Indian Ocean give birth to a phenomenon now referred to as the Indian Ocean Dipole Mode (IODM). The positive phase of this mode is characterized by positive SST anomalies over the western Indian Ocean and negative anomalies over the southeastern Indian Ocean, while the negative phase is characterized by a reversed SST anomaly pattern. On the other hand, the normal Pacific Ocean has warm (cool) waters over the western (eastern) parts. Positive (negative) SST anomalies over the central/eastern (western) Pacific Ocean characterize the E1 Nino phenomenon. The reverse situation leads to the La Nina phenomenon. The coupled ocean-atmosphere phenomenon over the Pacific is referred to as the E1 Nino Southern Oscillation (ENSO) phenomenon. In this study the impact of IODM and ENSO on the East Asian monsoon variability has been studied using observational data and using the Community Atmospheric Model (CAM) of the National Center for Atmospheric Research (NCAR). Five sets of model experiments were performed with anomalous SST patterns associated with IODM/ENSO superimposed on the climatological SSTs. The empirical and dynamic approaches reveal that it takes about 3-4 seasons fur the peak IODM mode to influence the summer monsoon activity over East Asia. On the other hand, the impact of ENSO on the East Asian monsoon could occur simultaneously. Further, the negative (positive) phase of IODM and E1 Nino (La Nina) over the Pacific enhances (suppresses) monsoon activity over the Korea-Japan Sector. Alternatively, IODM appears to have no significant impact on monsoon variability over China. However, El Nino (La Nina) suppresses (enhances) monsoon activity over China. While the IODM appears to influence the North Pacific subtropical high, ENSO appears to influence the Aleutian low over the northwest Pacific. Thus, the moisture supply towards East Asia from the Pacific is determined by the strengthening/weakening of the subtropical high and the Aleutian low.