• 제목/요약/키워드: 공동구 환기

검색결과 20건 처리시간 0.029초

초고층 공동주택의 환기효율 개선에 관한 연구 (A Study on the Improvement of Ventilation Effectiveness in High-rise Apartment Buildings)

  • 박진철
    • 한국태양에너지학회 논문집
    • /
    • 제26권2호
    • /
    • pp.87-94
    • /
    • 2006
  • The efficiency of ventilation system is one of the most important issues of designing ventilation in high-rise apartment buildings. The purpose of this study is to analyze the ventilation efficiency of ventilation system by experimental study using CO2 gas method. The results of this paper can be summarized as follows; (1) An appropriate ventilation including opening planning, mechanical and hybrid system are required. (2) The supply diffuser of ventilation system should be located near the contaminant source. (3) The return grill should be located along with supply diffuser for proper ventilation. and the return grill should be located near or right above the contaminant source. (4) However, the supply location right above the contaminant source has to be avoided. and the supply diffuser should be installed in module with return grill increase ventilation effectiveness.

공동주택의 하이브리드 환기시스템 성능평가 연구 (A Study on the Performance of the Hybrid Ventilation System for Apartment Houses)

  • 전주영;김길태;김상희
    • 토지주택연구
    • /
    • 제3권1호
    • /
    • pp.89-96
    • /
    • 2012
  • 본 연구는 공동주택에서 하이브리드 환기시스템의 적용성을 검토하고, 하이브리드 환기시스템의 성능을 향상하기 위해 CFD시뮬레이션을 이용하여 설계방안을 제시하고자 하였다. 연구대상으로는 전용 $51m^2$, $84m^2$의 공동주택을 선정하였으며, 하이브리드 환기시스템은 창틀자연급기와 각실을 덕트로 연결하여 배기하는 시스템(Hybrid 1)과 창틀자연급기와 욕실 거실배기가 혼합된 시스템(Hybrid 2)을 적용하였다. 이때 각 시스템별 배기구의 위치를 변수로 하여 CFD를 수행하였다. $51m^2$, $84m^2$ 모두 Hybrid 2가 Hybrid 1보다 환기효율이 우수한 것으로 나타났으며, 평균공기연령 또한 낮은 것으로 나타났다. Hybrid 1의 경우, 덕트 배기구의 위치가 각 실 입구에 설치하는 것보다 실 안쪽 모서리에 설치하여 기류이동을 많이 유발할 수 있는 유형이 효과적인 것으로 나타났다. Hybrid 2의 경우, 욕실 고정압팬에 덕트를 연결하여 거실중심에 배기구를 설치하는 시스템이 환기효율이 가장 우수한 것으로 나타났다. 그러나 $51m^2$의 경우 Hybrid 2가 Hybrid 1보다 20%의 향상된 환기효율을 나타낸 반면, $84m^2$의 경우는 14%의 향상된 환기효율을 나타내 공동주택 규모에 따른 적정한 하이브리드 환기시스템에 대한 검토가 필요하다.

공동주택 단지의 실내 공기질 향상을 위한 수치 해석적 연구 (A numerical Study for Improvement of Indoor Air Quality of Apartment House)

  • 신미수;김혜숙;홍지은;장동순
    • 대한환경공학회지
    • /
    • 제31권7호
    • /
    • pp.521-530
    • /
    • 2009
  • 본 연구에서는 대전의 대규모 공동주택단지의 하나인 대덕테크노 밸리의 계절별 주풍향 및 풍속, 건물배치, 환기구 위치 등 다양한 외부 유동 변수에 따른 실내 환기 특성을 수치 해석적 방법을 활용하여 연구함으로써 실내 공기질 향상에 일조하기 위해 연구를 수행하였다. 계절별 주풍향은 여름과 겨울에 큰 차이를 나타냈는데, 여름철의 경우 주풍향은 남풍이며, 겨울철의 경우 주풍향은 10년 평균 주풍향과 동일한 북북서풍으로 나타났다. 풍향이 변화함에 따라 최대 압력차가 나타나는 단지도 변화하였으며 그에 따라 환기에도 차이를 나타냈다. 내부 환기량은 환기 우수지역의 경우는 자연환기만으로 기준치인 시간당 0.7ACH를 만족하였으나 환기 취약지역의 경우는 자연환기만으로는 기준치를 만족시키지 못하여 부수적으로 기계 환기를 병행해야 하는 것으로 나타났다. 이러한 외부유동 변화에 따른 내부 환기량의 연구결과를 바탕으로 향후 아파트의 배치나 환기구 위치 선정에 응용한다면 환기량 확보에 일조하여 기계환기에만 의존하지 않고 자연환기와 병행이 가능하므로 에너지 절감에 도움이 될 것으로 판단된다.

지하공간 환경 모니터링 시스템 개발 및 시험 (Development of Underground Conduits Eco-Monitoring System)

  • 박정권;한진우;강왕규;우병수
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 한국정보통신설비학회 2009년도 정보통신설비 학술대회
    • /
    • pp.40-44
    • /
    • 2009
  • 지하구는 도시의 신경망이라 할 수 있는 통신, 전력, 상수도, 난방, 쓰레기 처리시설 등 도시 운용/관리를 위한 주요시설물을 안전하게 수용하고, 유지 관리하기 위한 시설로 IT기술을 이용하여 수용된 시설을 효과적으로 유지/관리하고, 재난으로부터 안전하게 보호함과 동시에 최소의 비용과 에너지로 수용된 시설물을 유지관리하기 위한 연구가 많이 진행되고 있다. 따라서 본 논문에서는 지하구(공동구, 통신구, 전력구)의 운용 및 유지관리와 지하구에서 발생될 수 있는 각종 재난에 대응하기 위한 지하구 운용 및 유지관리에 대해 알아보고, 지하구 내부에 수용된 시설물을 효과적으로 유지관리하고 재난에 신속히 대응하기 위한 지하구 환경모니터링 시스템에 대해 기술 하고자 한다. 지하구 환경모니터링 시스템은 지하구 내부에는 전력, 상수도, 통신, 난방 등 다양한 시설물이 수용되어 있으며, 이러한 시설물의 부식, 고장 등으로부터 보호하기 위해 지하구내부의 환기시스템의 송풍기와 지하수와 기상재해로 인한 지하구 및 수용시설물의 침수를 막기 위한 양수펌프에 대해 실시간 상태모니터링 통해 송풍기 및 펌프의 고장여부를 판단하여 관리자에게 알림으로써 관리자가 신속하게 대응 할 수 있도록 하였다. 송풍기의 제어는 지하의 내부와 외부에 설치된 온/습도 센서를 통해 지하구 내부환경을 최적으로 유지할 수 있도록 함으로써 쾌적한 지하 내부환경 유지하고, 급/배기가 필요할 경우에만 송풍기를 가동함으로써 에너지를 절약 할 수 있으며, 화재, 침수 등에 대한 재난시 환풍기의 급/배기, 정지 등을 신속하게 제어할 수 있도록 하였다. 또한 지하구내부에서 발생된 재난을 유/무선을 이용하여 신속하게 지하구 주변의 장치(U-Pole 또는 통합컨트롤러)를 통해 경보를 전파함으로써 주변 시민들이 안전하게 대피할 수 있도록 하였다. 그리고 지하구 환경모니터링 시스템을 검증하기 위해 실제 지하구 및 실험실에 시스템 및 Test Board을 설치하여 운용시험을 실시 하였다.

  • PDF

공동주택 지하주차장의 풍력환기 성능에 관한 연구 - 환기구 면적 및 주변건물의 영향 - (A Study on Ventilation Performance driven by Wind Force in Underground Parking Lots of Apartment - Influence of Opening Size and Surrounding Building -)

  • 노지웅
    • KIEAE Journal
    • /
    • 제12권1호
    • /
    • pp.29-34
    • /
    • 2012
  • As a series of studies about natural ventilation driven by wind in basement parking lots of apartment, the influence of opening size and surrounding buildings on ventilation rate was analyzed. Natural ventilation in underground parking lots almost rely on wind than temperature difference. To investigate natural ventilation driven by wind, wind tunnel tests by using scale model and tracer gas method were conducted. $CO_2$-gas concentration was measured, natural ventilation rates were calculated. The experimental results showed that the natural ventilation rate is more reliable to wind direction and surrounding building than opening size and distance between buildings. It was verified that surrounding buildings play a principal role in increasing air flow rate by accelerating wind speed, and growing turbulence intensity. And it showed that ventilation performance is able to be increased by oblique wind to entrance ramp than head on wind in underground parking lots with surrounding buildings.

초고층 공동주택의 하이브리드 환기시스템의 성능평가에 관한 연구 (A study on the Performance of Hybrid ventilation system in High-rise Apartment Houses)

  • 김옥;박창봉;박진철;김남규;이언구
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.113-118
    • /
    • 2007
  • As the economic living standards are higher, the demands for more comfortable living space are also larger. In the response of this requirements, studies for improving indoor air environment have been conducted. In case of newly-built apartment buildings, the standard for the minimum ventilation to improve their indoor air quality was made. This study analysed the experimental results from the mock-up test of the hybrid ventilation system which is composed of natural and mechanical ventilation.

  • PDF

공동주택에서의 실외 급.배기구 위치에 따른 환기효율 향상 연구 (A study on the Improvement of Ventilation Performance in Apartment House According to the Location of Exterior Air-Vents)

  • 박진철;유형규;차진영
    • 한국태양에너지학회 논문집
    • /
    • 제25권2호
    • /
    • pp.71-79
    • /
    • 2005
  • In this study, the ventilation performance of mechanical ventilation system in apartment House was analyzed through model test according to characteristics of air-vent. Then adequate interval of air-vent was suggested using computer simulation which will create comfort environment through improvement of ventilation performance in apartment house. The result of experiment with separation plate to prevent mixture of contaminated exhaust air with fresh supply air, the ventilation efficiency improved about 10%. The result of simulation with horizontal location of exterior air-vent, contaminated exhaust air is mixed regardless of interval variation. Consequently, mixture of the exhaust air can be prevented through locating the supply air vent on the top side and exhaust air vent on the lower side.

CO2 추적가스 농도감소법을 이용한 공동주택의 급·배기구 조합에 따른 환기 성능 분석 (Evaluation of Ventilation Performances for Various Combinations of Inlets and Outlets in a Residential Unit through CO2 Tracer-Gas Concentration Decay Method)

  • 이상윤;이수만;김종엽;김길태;곽병창
    • 토지주택연구
    • /
    • 제14권4호
    • /
    • pp.111-120
    • /
    • 2023
  • 주거 공간에서의 시간 증가와 외부 미세먼지, 황사 등의 영향 그리고 코로나 19 이후에 실내 공기질에 대한 중요성이 점차 중요해지고 있다. 이를 해결하기 위해 주거 공간에서 기계환기의 영향이 중요해지고 있고, 국내에서는 시간당 환기횟수 0.5회에 대한 법적 기준이 있다. 하지만, 급배기구의 위치는 구체적인 기준이 없어서 관습적으로 사용되고 있다. 본 연구에서는 급배기구 위치에 따른 주거 공간의 환기 성능 영향을 분석하고자 하였다. 실험은 외부 영향을 최소화할 수 있는 대형 챔버안에 있는 목업주택에서 추적가스법 중 농도감소법을 이용해서 실제 현장시험을 진행하여 실험을 진행했다. 실험 결과 거실 공간에서 일반적으로 사용하는 급기구 2개, 배기구 2개 조합은 급기 1개 배기 2개 조합보다 공기연령이 낮았으며, 급기와 배기를 1개씩 사용하는 것보다 급기나 배기를 여러개 사용하는 것이 측정점에서 오차율이 적어 실내 환기성능이 유사한 것을 확인했다.