• 제목/요약/키워드: 공냉형 흡수식 냉방 시스템

검색결과 2건 처리시간 0.021초

공냉형 흡수식 냉방 시스템에서 LiBr 수용액의 과열도가 증기 흡수에 미치는 영향 (Effect of degree of superheat of LiBr aqueous solution on the vapor absorption process for an air-cooled absorption cooling system)

  • 김선창;오명도;이재헌
    • 설비공학논문집
    • /
    • 제9권2호
    • /
    • pp.122-133
    • /
    • 1997
  • Numerical analysis using finite volume method has been carried out to examine the effect of degree of superheat of LiBr aqueous solution on heat and mass transfer occurred in absorption process. According to the result of this study, it was found that refrigerant vaper was generated at the entrance region of absorber when LiBr aqueous soltion was superheated. As the degree of superheat increases, heat transfer rate increases and vapor absorption rate decreases. The increase in averaged Nusselt and Sherwood numbers could be found as film Reynolds number increases. The larger the degree of superheat, the greater the averaged Nusselt and Sherwood numbers.

  • PDF

H2O/LiBr+HO(CH2)3OH계 공냉형 이중효용 흡수식 냉방시스템의 사이클 해석 (Cycle Analysis of Air-Cooled Double-Effect Absorption Cooling System Using H2O/LiBr+HO(CH2)3OH)

  • 권오경;문춘근;윤정인
    • 대한기계학회논문집B
    • /
    • 제23권2호
    • /
    • pp.272-280
    • /
    • 1999
  • A cycle analysis was achieved to predict the characteristics by comprehensive modeling and simulation of an air-cooled, double-effect absorption system using a new $H_2O/LiBr+HO(CH_2)_3OH$ solution. The simulation results showed that the new working fluid may provide the crystallization limit 8% higher than the conventional $H_2O/LiBr$ solution. With a crystallization margin of 3wt%(weight%), the optimal solution distribution ratio was found in the range of 36 to 40%. Variation of cooling air Inlet temperature has a sensitive effect on the cooling COP and corrosion problem. The simulation of heat exchangers with UA value revealed that the absorber and the evaporator are relatively important for an air-cooled system compared with the condenser and the low temperature generator. The effect of cooling air flow rate, circulation weak solution flow rate and chilled water inlet temperature were also examined. The new working fluid may provide the COP approximately 5% higher than the conventional $H_2O/LiBr$ solution.