• 제목/요약/키워드: 공냉형 시스템

검색결과 6건 처리시간 0.022초

공냉형 흡수식 냉방 시스템에서 LiBr 수용액의 과열도가 증기 흡수에 미치는 영향 (Effect of degree of superheat of LiBr aqueous solution on the vapor absorption process for an air-cooled absorption cooling system)

  • 김선창;오명도;이재헌
    • 설비공학논문집
    • /
    • 제9권2호
    • /
    • pp.122-133
    • /
    • 1997
  • Numerical analysis using finite volume method has been carried out to examine the effect of degree of superheat of LiBr aqueous solution on heat and mass transfer occurred in absorption process. According to the result of this study, it was found that refrigerant vaper was generated at the entrance region of absorber when LiBr aqueous soltion was superheated. As the degree of superheat increases, heat transfer rate increases and vapor absorption rate decreases. The increase in averaged Nusselt and Sherwood numbers could be found as film Reynolds number increases. The larger the degree of superheat, the greater the averaged Nusselt and Sherwood numbers.

  • PDF

H2O/LiBr+HO(CH2)3OH계 공냉형 이중효용 흡수식 냉방시스템의 사이클 해석 (Cycle Analysis of Air-Cooled Double-Effect Absorption Cooling System Using H2O/LiBr+HO(CH2)3OH)

  • 권오경;문춘근;윤정인
    • 대한기계학회논문집B
    • /
    • 제23권2호
    • /
    • pp.272-280
    • /
    • 1999
  • A cycle analysis was achieved to predict the characteristics by comprehensive modeling and simulation of an air-cooled, double-effect absorption system using a new $H_2O/LiBr+HO(CH_2)_3OH$ solution. The simulation results showed that the new working fluid may provide the crystallization limit 8% higher than the conventional $H_2O/LiBr$ solution. With a crystallization margin of 3wt%(weight%), the optimal solution distribution ratio was found in the range of 36 to 40%. Variation of cooling air Inlet temperature has a sensitive effect on the cooling COP and corrosion problem. The simulation of heat exchangers with UA value revealed that the absorber and the evaporator are relatively important for an air-cooled system compared with the condenser and the low temperature generator. The effect of cooling air flow rate, circulation weak solution flow rate and chilled water inlet temperature were also examined. The new working fluid may provide the COP approximately 5% higher than the conventional $H_2O/LiBr$ solution.

공냉형 수직 흡수식 시스템의 적용에 관한 연구 (A study on The Application of a Vertical Absorption System Cooled by Air)

  • 김정국;조금남
    • 한국에너지공학회:학술대회논문집
    • /
    • 한국에너지공학회 2003년도 춘계 학술발표회 논문집
    • /
    • pp.351-357
    • /
    • 2003
  • In absorption system, the performance of the absorber is critical the overall system performance, size, and first-cost. The objective of this paper is to provide a comprehensive review of the significant effects that researchers have made to numerically analysis model the coupled heat and mass transfer process that occur during falling-film absorption and experimental researches. This study includes experimental work in the enhancement of absorption performance, the effect of the geometry of a vertical absorber, and the effect of configuration of absorption system. This paper is used to highlight key areas which need attention such as film ans vapor hydrodynamics, especially the non-periodicity, instability, and recirculatory motion of waves in the vertical absorber case.

  • PDF

통신장비용 공냉형 냉각시스템의 성능 특성에 대한 실험적 연구 (Experimental Study on the Performance of an Air-Cooling System for Telecommunication Equipment)

  • 전종욱;최종민;허재혁;김용찬
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.323-328
    • /
    • 2005
  • The objective of this study is to analyze the cooling performance of an air- cooling system for telecommunication equipment. Temperature variation and capacity were measured in an actual unit for telecommunication equipment. In addition, the cooling performance was measured by installing a silicon rubber heater as a heat source in a cabinet. The standard thermal load for telecommunication equipment was approximately 293 W, and the maximum temperature of the heated surface was $64.5^{\circ}C$. The average and maximum temperatures of the heated surface were proportional to the inlet air temperature. When the heat load increased from 293 W to 400 W, the maximum temperature of the heated surface was higher than $64.5^{\circ}C$ even though the inlet air temperature decreased from 25 to $11^{\circ}C$.

  • PDF

꽃 저장용 냉장시스템과 태양열 복합형 급탕기 개발연구(I) (The R&D of hot water production by the combination of solar thermal and a large sized flower cooling system(I))

  • 정현채;김기선;선경호
    • 태양에너지
    • /
    • 제12권3호
    • /
    • pp.84-93
    • /
    • 1992
  • 본 연구에서는 꽃저장용 냉장시스템 등에 태양열을 이용할 수 있는 난방시스템을 조합하여 충분한 양의 고온을 확득하여 주택의 난방을 가능케 하는 시스템을 설계, 제작했다. 압축기는 기존의 압축기 냉각방식을 공냉식에서 수냉식으로 전환시켜 적절한 냉각효과의 증대는 물론 냉열을 회수하여 고온의 온수를 빠른 시간 내에 획득할 수 있는 시스템을 개발했다.

  • PDF

유도 결합 플라즈마원의 외부 냉각에 관한 수치 모델링

  • 주정훈;조정희;박상종
    • 한국진공학회:학술대회논문집
    • /
    • 한국진공학회 2016년도 제50회 동계 정기학술대회 초록집
    • /
    • pp.218-218
    • /
    • 2016
  • 실린더 형태의 유전체 관에 나선형으로 도전체 안테나를 설치하는 타입의 유도 결합 플라즈마원은 간단한 구조로 화학 조성 분석용부터 나노 분말 제조, 반도체용 식각/증착, 표면 처리, 자동차 및 일반 산업 부품용 증착 보조원등으로 널리 사용되고 있다. 고밀도 라디칼/이온의 공급을 위해서 투입 전력을 증가시키는 경우 높은 전력 밀도로 인해서 유전체 관에 인가되는 열응력이 대기압 및 관 고정용 구조물에 의한 구조 응력에 더해져서 파손에 이르는 경우가 발생될 수 있다. 실제 실린더 길이 전체를 안테나 코일로 감는 경우에도 플라즈마 발생 밀도가 높은 지역은 중심 일부 영역에 국한 되는 공정 영역도 있어서 이에 대한 분석이 필요하다. CFD-ACE+를 이용하여 플라즈마의 생성, 냉각수의 열전도, 외부 공냉식 팬의 역할등에 대해서 수치 모델을 작성하여 검토하였다. 나선형 냉각코일의 경우 냉각수량을 일정값 이상으로 증가시키는 경우 유속이 지나치게 빨라져서 열원이 있는 내경쪽 표면에서 열전도가 유속에 비례해서 증가하지 못하는 단점이 발생할 수 있으며 냉각팬의 경우 일반적으로 장치 내부에 대해서만 모델링을 하는 데 실제로 전체 시스템의 주변에서 공기의 흐름을 넓게 해석해야 실제 냉각 효과를 파악할 수 있다. 심한 경우 냉각용 공기 흡입구와 토출구의 간격이 좁아서 열원에 의해서 가열된 공기의 상당량이 다시 냉각용 공기 흡입구로 재순환 되는 경우도 발생하기 쉽다.

  • PDF