• 제목/요약/키워드: 고낙차 장배관 조건

검색결과 1건 처리시간 0.015초

동시냉난방 시스템 에어컨의 냉매량 변화에 따른 고낙차 장배관 운전 신뢰성 평가 (Evaluation of the operating reliability on the concurrent heating-cooling system air conditioner for different refrigerant flow rates with high-head and long-line conditions)

  • 이승찬;김태안;태상진;정규하;문제명;김윤제
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 동계학술발표대회 논문집
    • /
    • pp.304-309
    • /
    • 2008
  • The heating and cooling performances of system multi-air conditioner for various refrigerant flow rates with high-head and long-line conditions are experimentally investigated. The maximum head and tube length were 110 m and 1000 m, and the two different adjustments of refrigerant flow rates were +20 % and -20 %, respectively. The experimental system was composed of 4 outdoor units with module systems, and 13 indoor units which were joined with the mode change unit by single-tube circuit. Field tests without indoor and outdoor temperature control were performed in a general office building with two different refrigerant flow rates. Especially, the oil level in the compressor was normally maintained at the safety zone. Experimental results were prepared on the p-h diagram.

  • PDF