• Title/Summary/Keyword: $CO_2$ trans-critical cycle

Search Result 2, Processing Time 0.02 seconds

Performance Analysis for CO2 System with Sub-cooling loop (과냉 회로를 갖는 이산화탄소 냉동시스템에 대한 성능 해석)

  • Kim, Jin-Man;Ko, Sung-Gyu;Kim, Moo-Geun
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.31 no.6
    • /
    • pp.723-728
    • /
    • 2007
  • In order to evaluate the performance of carbon dioxide cycle with a sub-cooling loop. a simulation system was developed to predict the steady state of $CO_2$ trans-critical cycle. Mathematical models are derived to describe the relationships between the system's coefficient of performance and other operating parameters The mathematical models are based entirely on the basic mass and energy conservation law and thermodynamic and transport properties of carbon dioxide A parametric study has been conducted in order to investigate the effect of sub-cooling loop and various operating conditions on the cycle performance. An optimal mass fraction of a refrigerant flowing through sub-cooling cycle existed for the given evaporating temperature, high pressure and air inlet temperature through gas cooler.

Performance Analysis of Scroll Expander-Compressor Unit for $CO_2$ Transcritical Cycles ($CO_2$ 초임계 사이클을 위한 일체형 스크롤 팽창기-압축기 성능해석)

  • Kim Hyun-Jin;Nam Bo-Young;Ahn Jong-Min
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.5
    • /
    • pp.434-442
    • /
    • 2006
  • In a two-stage compression $CO_2$ transcritical cycle, application of a scroll expander-compressor unit has been considered in order to improve the cycle COP. For both expander and 1st stage compressor, scroll wrap profile which was originally designed for a R410A air-conditioning cycle mechanism was used with minor modifications: wrap height and involute end angle were adjusted for required displacement volume and built-in volume ratio. For pressure condition of 10 Mpa/3.5 MPa and expander inlet temperature of $35^{\circ}C$, 25% improvement in COP was obtained by using expander-compressor unit. As evaporator pressure increased, COP improvement was lowered mainly due to decreasing compressor peformance.