Browse > Article
http://dx.doi.org/10.5370/KIEEP.2011.60.4.267

Insulation Characteristics and Thermography Diagnosis of Porcelain Insulators for the Distribution Systems  

Joung, Jong-Man (한국전력공사 설비진단센터)
Kim, Dong-Myeong (한국전력공사 설비진단센터)
Choi, Myung-Ho (한국전력공사 충남본부)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers P / v.60, no.4, 2011 , pp. 267-271 More about this Journal
Abstract
The insulating characteristics and temperature rise behaviors of porcelain suspension insulators were investigated. The testing insulators had used in the distribution systems normally and were sampled. Firstly, leakage current was measured and its impedance was calculated. The leakage current of good insulators is 0.2 mA and its impedance is 66 $M{\Omega}$. The worse insulators have lower impedance and the insulators having below 15 $M{\Omega}$ take place flashover at the high frequency voltage flashover test. Secondly, the temperature rise characteristics were analyzed depending on leakage current and its impedance. Surface temperature of insulators was measured for 30 minutes and until its saturation after voltage was applied. The temperature rise of insulators having 15 $M{\Omega}$ is about $14.5^{\circ}C$ above the ambient temperature. Lastly, the heating behaviors of 3 insulators in a string was analyzed. Any insulator in the string does not generate heat so far as it has at least one sound insulator. On the other hand, all the insulators in the string are bad if the string have any heating insulator.
Keywords
Thermography; Diagnosis; Insulating Characteristics; Porcelain; Insulators;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Rawat.A, Gorur.R., "Microstructure based evaluation of field aged and new porcelain suspension insulators", IEEE Trans. on Dielectric and Electrical Insulation, Vol.16, pp.107-115, 2009.   DOI   ScienceOn
2 Vaillancourt.G.H., "New live line tester for porcelain suspension insulators on high-voltage power lines", IEEE Trans. on Power Delivery, Vol.9, pp.208-219, 1994.   DOI   ScienceOn
3 한전표준규격 ES-5970-0006, 배전용 볼소켓형 현수애자, 2010.
4 대한전기학회, 최신 배전시스템 공학, (주)북스힐, pp. 58-62, 2006.
5 한전표준규격 ES-5970-0010, 애자시험방법, 2011
6 ESMOL Subcommitee 15.07, "Minimum number of goo(healthy) porcelain of glass insulator units in a string for live work", IEEE Trans. on Power Delivery, Vol.17, pp.809-814, 2001.
7 Forrest. J.S., "The characteristics and performance in service of high-voltage porcelain insulators", Electrical Engineers-Part II: Power Engineering, Journal of the institution of, pp.60-80. 2010.
8 정종만, 곽현관, 김한홍, "자기애자 누설전류 불량판정기준", 2010년도 대한전기학회 전기설비전문위원회 추계학술대회, pp.413-418, 2010.
9 한전 배전전략실, 배전설비 정전분석 및 예방대책, 한전, pp.8-13, 2010.