A New Control Scheme of the Line-Interactive UPS Using the Series Active Compensator  

Jang, Hoon (한양대 공학 전기공학과)
Lee, Woo-Cheol (한양대 전기공학과)
Hyun, Dong-Seok (한양대 공학 전기공학과)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers B / v.52, no.8, 2003 , pp. 405-412 More about this Journal
Abstract
This paper presents a three-phase Line-Interactive uninterruptible power supply (UPS) system with series-parallel active power-line conditioning capabilities, using synchronous reference frame (SRF) based controller, which allows an effective power factor correction, source harmonic voltage compensation, load harmonic current suppression, and output voltage regulation. The three-phase UPS system consists of two active power compensator topologies. One is a series active compensator, which works as a voltage source in phase with the source voltage to have the sinusoidal source current and high power factor under the deviation and distortion of the source voltage. The other is a parallel active compensator which works as a conventional sinusoidal voltage source in phase with the source voltage, providing to the load a regulated and sinusoidal voltage with low THD (total harmonic distortion). The control algorithm using SRF method and the active power flow through the Line-interactive UPS systems are described and studied. The simulation and experimental results are depicted in this paper to show the effect of the proposed algorithm.
Keywords
Series Active Compensator; Parallel Active Compensator; Unified Power Quality Compensator; Synchronous Reference Frame;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Soren Rathmann, Henry A. Warner, 'New generation ups technology, The delta conversion principle.' IAS 96, Conference Record of the 1996 IEEE, vol.4, pp.2389-2395, 1996   DOI
2 S. Karve, 'Three of a Kind', IEE REVIEW, vol. 46, pp.27-31, March 2000   DOI   ScienceOn
3 W. J. Ho, et al, 'A Line-interactive UPS Structure with Built-in Vector-Controlled Charger and PFC', in Power Electronics and Drive Systems, vol. 1, pp. 127-132, 1997   DOI
4 Oliveria da Silva, S.A.; Donoso-Garcia, p.: Cortizo, D.C.; 'A Three-Phase Line-Interactive UPS System Implementation with Series-Parallel Active Power-Line Conditioning Capablilites.' IAS, Conference Record of the 2001 IEEE, vol.4, pp.2389-2396, 2000   DOI
5 Dougls C. Folts, 'The response of Advanced Single-Conversion UPS to Power Disturbances.' Seventh International Power Quality Conference, October 1993, Proceedings. pp. 93-105
6 Doglas S. Dorr and Douglas C. Folts, 'UPS Response to Power Disturbances, A Proposed Method for Determination of UPS Response to Power Disturbances' IEEE, APEC Conference Proceedings, 1994. pp. 675-682. IEEE 0-7803-1456-5/94   DOI
7 Sergio augusto Oliveira da Silva, Pedro F. Donoso Garcia, 'A comparative analysis of control algorithms for three phase line interactive ups systems with series parallel active power line conditioning using SRF method.' PESC00. IEEE vol.2, pp.1023-1028, 2000   DOI
8 Hirofumi Akagi, 'New Trends in Active Filters for Power Conditioning.', IEEE Trans. on Industry Applications, vol.29, on.1 pp. 144-152, 1993, January/February   DOI   ScienceOn
9 Seong-Jeub Jeon: Gyu-Hyeong Cho, 'A series-parallel compensated uninterruptible power supply with sinusoidal input current and sinusoidal output voltage' PESC '97 Record, IEEE vol.1, pp.297-303, 1997   DOI