Study on establishment of emission cell test method for liquid phase building materials  

Lim, Jungyun (Indoor Air Quality Division, National Institute of Environmental Research)
Jang, Seongki (Indoor Air Quality Division, National Institute of Environmental Research)
Seo, Sooyun (Indoor Air Quality Division, National Institute of Environmental Research)
Publication Information
Analytical Science and Technology / v.22, no.3, 2009 , pp. 191-200 More about this Journal
Abstract
The aim of this study was to evaluate and establish of emission test method for liquid phase building materials such as paint, adhesive, sealant by emission cell. A small-scale emission chamber and emission cell were used to evaluate emission of TVOC from paint, adhesive, sealant. The quantity of TVOC emission were measured by a gas chromatography/mass spectrometry (GC/MS). Background concentration of TVOC was below $10{\mu}g/m^3$ in the emission chamber and cell. Air tightness and recovery in chamber and cell showed good results. The recovery of thermal desorber for toluene and n-dodecane were about 120%. The repeatability of response factor and retention time in GC/MS below 30%. The method detection limit of VOCs ranged 0.04~8.82 ng. The concentration of TVOC emission using emission cell was 1.35~1.41 times higher than emission chamber. The correlation of TVOC emission using chamber and cell method was significantly high (r=0.91~0.97).
Keywords
liquid phase building materials; TVOC; small-scale emission chamber; emission cell; correlation;
Citations & Related Records
연도 인용수 순위
  • Reference
1 M. D. Bortoli and A. Colombo, 'European Collaborative Action Report' No. 13. Determination of VOCs emitted from indoor materials and products - Interlaboratory comparison of small chamber measurements. Commission of the European Communities, Joint Research Centre - Institute for the Environment, 1993
2 M. D. Bortoli, S. Kephalopoulos, S. Kirchner, H. Schauenburg, H. Vissers, 'European Collaborative Action Report' No. 21. European Inter-laboratory Comparison on VOC emitted from building materials and products. European Commission, Joint Research Centre - Environment Institute, 1999
3 ENV 13419-1. Building Products - Determination of the emission of volatile organic compounds - Part 1 : Emission test chamber method. European Committee for Standardization, 1999
4 ISO 16000-10. Indoor air - Part 10 : Determination of the emission of volatile organic compounds - Emission test cell method. International Organization for Standardization. 2005
5 ISO 16000-9. Indoor air - Part 9 : Determination of the emission of volatile organic compounds - Emission test chamber method. International Organization for Standardization. 2005
6 A. Afshari, B. Lundgren and L. E. Ekberg, Comparison of three small chamber test methods for the measurement of VOC emission rates from paint. Indoor Air, 13, 156-165(2003)   DOI   ScienceOn
7 M. Risholm-Sundman, Determination of formaldehyde emission with field and laboratory emission cell (FLEC) - recovery and correlation to the chamber method. Indoor air, 9, 268-272(1999)   DOI   PUBMED   ScienceOn
8 R. Funaki and S. Tanabe, Measurements of emission rates from wall covering adhesives - comparing with FLEC and a small scale chamber ADPAC-. International FLEC symposium 2001, 65-70(2001)
9 O. Jann and O. Wilke, Comparison of FLEC with other climate chambers, German experiences. International FLEC symposium 2001, 18-27(2001)
10 장성기, 임정연, 이우석, 서수연, 임준호, 박민규, 류정민, 천재영, 고형건축자재 오염물질 방출시험방법 최적화 연구, 한국실내환경학회 학술지, 3(3), 298-312(2006)
11 M. D. Bortoli, S. Kephalopoulos and H. Knoppel, 'European Collaborative Action Report' No. 16. Determination of VOCs emitted from indoor materials and products - Second interlaboratory comparison of small chamber measurements. European Commission, Joint Research Centre - Environment Institute, 1995