DOI QR코드

DOI QR Code

Fundamental Study for the Development of a Ventilation System using Thermoelectric element and Adsorbent

열전소자와 흡착제를 이용한 환기시스템 개발을 위한 기초연구

  • Jik-Su Yu (Kunsan National University, Department of ship Engine Engineering)
  • 유직수 (국립군산대학교 기관공학과)
  • Received : 2024.09.11
  • Accepted : 2024.10.08
  • Published : 2024.10.31

Abstract

In this study, fundamental research was conducted on the development of an adsorption-desorption ventilation system incorporating thermoelectric elements to improve indoor air quality (IAQ) and energy efficiency. The experiment was conducted using a thermoelectric module and silica gel as a commonly used adsorbent to evaluate the cooling and heating effects during the adsorption and desorption process. The main experimental results show that applying 3W power to the thermoelectric module reduces the outlet air temperature and improves the adsorption efficiency, while excessive power (4-5W) reduces the adsorption efficiency due to increased heat load. Additionally, when the flow rate on the adsorption side is increased, the completion time decreases. On the other hand, if the flow rate on the desorption side is increased, the completion time is also shortened. It was confirmed that as the flow rate increases, the movement of heat and moisture generated during the adsorption and desorption process becomes faster, and the reaction progresses more quickly.

Keywords

References

  1. E. Belyanovskaya, R. D. Lytovchenko, K. Sukhyy, O. Prokopenko, O. Yeromin, I. V. Sukha, "Choice Criteria of Adsorbents for Heat Energy Converters in Ventilation Systems," Scientific Works, vol. 83, pp. 4-9, (2019).
  2. C. J. Lu, E. T. Zellers, "A Dual-Adsorbent Preconcentrator for a Portable Indoor- VOC Microsensor System," Analytical Chemistry, vol. 73, no.14, pp. 3449-3457, (2001).
  3. S. Poojeera, A. Srichat, N. Naphon, P. Naphon, "Study on Thermal Performance of the Small-Scale Air Conditioning with Thermoelectric Cooling Module," Mathematical modeling of engineering problems, vol. 9, pp. 1143-1151, (2022).
  4. O. Toru, R. Radermacher, Y. Hwang, "A Novel Application of Thermoelectric Modules in an HVAC System Under Cold Climate Operation," Joural of Electronic Materials, vol. 41, pp. 1749-1758, (2012).
  5. K. Irshad, "Performance Improvement of Thermoelectric Air Cooler System by Using Variable-Pulse Current for Building Applications," Sustainability, vol. 13, pp. 9682, (2021).
  6. G. Li, X. Meng, X. Zhang, L. Zhang, C. Du, N. Li , W. Yu, J. Xiong, S. Zhang, B. Li, "An innovative ventilation system using piston wind for the thermal environment in Shanghai subway station," Journal of Building Engineering, vol. 32, pp. 101276, (2020).
  7. M. J. Kim, J. S. Yu, "Fundamental Study on the Probability of Oyster Shell Desiccant Cooling System Driven by Renewable Energy of Photo-Voltaic Effect", Journal of the Korean Society of Marine Engineering, vol. 32, pp. 387-393, (2008).
  8. M. J. Kim, G. H. Chea, "Study on the PV Driven Dehumidifying System with Oyster Shell and Thermoelectric Device", Journal of the Korean Society of Marine Environment and Safety, vol.18, pp.287-293, (2012).
  9. M. J. Kim, "Study on the Adsorption and Desorption Enhance Effect of Oyster Shell Using Peltier Element", Journal of the Korean Society for Power System Engineering, Vol.17, pp.71-76, (2013).