DOI QR코드

DOI QR Code

용해로의 공정상 온도상승 및 과전류에 따른 케이블의 절연저항 특성

Characteristics of Insulation Resistance of Cable according to Temperature Rise and Over-Current for Process of the Melting Furnace

  • Suk Bong Ko (Korea Industrial Safety Association) ;
  • Doo-Hyun Kim (Department of Safety Engineering, Chungbuk National University) ;
  • Sung-Chul Kim (Department of Safety Engineering, Chungbuk National University)
  • 투고 : 2024.02.14
  • 심사 : 2024.04.15
  • 발행 : 2024.04.30

초록

The purpose of this study is to explore the trend in insulation resistance values according to temperature and overcurrent by conducting an investigation on the actual condition and experiments on the electrical wiring during the melting furnace process. In addition, the Arrhenius equation is used to determine whether temperatures in the furnace operating process can be applied to the actual field. In the investigation of the actual condition, the insulation resistance started to decrease seven years after replacement, even though cables in oil pump A were replaced in 2010. Both the experimental and theoretical values of the insulation resistance obtained using the Arrhenius equation decreased with an increase in temperature. Errors in insulation resistance (MΩ) values between tests and the Arrhenius equation ranged from ±2 to ±10, demonstrating a high similarity. Results revealed that when the insulation resistance cannot be measured in a manufacturing workplace (quarterly analysis), it can be estimated by partially applying the Arrhenius equation.

키워드

참고문헌

  1. 2021 Edition of NFPA 921(Guide for Fire and Explosion Inv Estigations), Chapter 9 "Electricity and Fire", pp. 123-151, 2021. <https://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and-standards/detail ?code=921>
  2. B. S. Ko, D. H. Kim and S. C. Kim, "Analysis of the Insulation Resistance Trend according to the Installation Environment of the Electric Wiring of the Melting Furnace", J. Korean Soc. Saf., Vol. 38, No. 5, pp. 15-22, 2023.
  3. J. C. Lee, D. H. Kim and S. C. Kim, "Analysis of Installation Environment and Fire Risk of Induction Motors Installed in the Curing Process of a Rubber Product Manufacturing Plant", J. Korean Soc. Saf., Vol. 38, No. 5, pp. 23-29, 2023.
  4. K. C. Kim, D. H. Kim and S. C. Kim, "Analysis of Thermal Characteristics and Insulation Resistance based on Usage Environment and Current Value of Electrical Socket Outlet", J. Korean Soc. Saf., Vol. 34, No. 5, pp. 22-30, 2019.
  5. B. S. Ko, D. H. Kim and S. C. Kim, "Analysis of the Insulation Resistance Trend according to the Installation Environment of the Elect ric Wiring of the Melting Furnace", J. Korean Soc. Saf., Vol. 38, No. 2, pp. 15-22, 2023.
  6. Energy Usage Statistics", https://.index.go.kr, 2022
  7. KOSHA GUIDE (P-143-2014) furnace of the Korea Occup ational Safety and Health Agency, 2014.
  8. K. H. Eom and K. W. Lee, "The Arrhenius Equation Satisfying the Acceleration Factor Insulation Resistance Characteristics Cablel ife Evaluation Study based on Analysis", IIBC, Vol. 14, No. 5, pp. 231-236, 2014.
  9. S. G. Choi and S. G. Kim ,"PVC Tracking of Accelerated Deterioraion of Insulating Materials Characteristics on Research", KIFSE, Vol. 31, No. 6, pp. 91-98, 2017.
  10. H. K. Ji and J. Y. Sone, "Study on the Fire Risk in Locked Rotor Condition of Single-Phase Induction Motor", Fire Science and Engineering, Vol. 34, No. 2, pp 64-71, 2020.
  11. J. C. Lee, D. H. Kim snf S. C. Kim, "A Study on Fire Risk according to the Environment and Load Conditions of Motors used in Rubber Product Manufacturing Factories", FOURRAGES Journal, Vol. 254, No. 5, 2023.
  12. H. Bickel, "Analytical Approaches to Evaluate Residual Cable Lifetime", LLC.
  13. R. Polansky and M. Polanska, "Testing of the Fire-proof functionality of Cable Insulation Nuder Fire Conditions Via insulation Resistance Measurements", Engineering Failure Analysis, Vol. 57, pp. 334-349, 2015.