DOI QR코드

DOI QR Code

Explosion Characteristics Analysis of Low-Density Polyethylene Dust

저밀도 폴리에틸렌 분진의 폭발특성 분석

  • Hyun-gil, Kwon (Department of Safety Engineering, Korea National University of Transportation) ;
  • Kyeong-seok, Oh (Department of Safety Engineering, Korea National University of Transportation) ;
  • Jong-bae, Baek (Department of Safety Engineering, Korea National University of Transportation) ;
  • Dong-hyun, Seo (Occupational Safety & Health Research Institute, KOSHA)
  • 권현길 (한국교통대학교 안전공학과) ;
  • 오경석 (한국교통대학교 안전공학과) ;
  • 백종배 (한국교통대학교 안전공학과) ;
  • 서동현 (한국산업안전보건공단 산업안전보건연구원)
  • Received : 2022.07.01
  • Accepted : 2022.08.08
  • Published : 2023.02.01

Abstract

Ensuring safety in the designing of manufacturing and handling facilities for low-density polyethylene (LDPE) is difficult because there are no standards for the dust explosion characteristics of LDPE. In this study, a dust explosion test was performed on two dust samples collected from a bag filter (LDPE 1) during the LDPE manufacturing process and sedimentary dust (LDPE 2) leaked outside a facility such as a silo, and the LDPE 2 explosion test results were summarized. Particle size analysis showed that the volume-based particle diameter (median) was 95.04 ㎛ and the number density was 0-1 ㎛. The maximum explosion pressure (Pmax) was 6.6 bar, and the maximum rate of explosion pressure rise was 366 [bar/s] at 1500 g/m3. Accordingly, the dust explosion index (Kst) was 99.4 bar·m/s, which was confirmed as ST-1 grade. Moreover, the minimum ignition energy and minimum ignition temperature was 10 mJ and 450 ℃, respectively. Currently, manufacturing and handling design is based on the characteristic values of high-density polyethylene (HDPE). However, as the test results show that LDPE 2 dust has a higher risk than HDPE (particle diameter 61.6 ㎛), caution is required when using the HDPE design criteria in the LDPE manufacturing process.

저밀도 폴리에틸렌(Low-density polyethylene, LDPE)은 분진폭발 관련 특성치에 대한 기준이 제시되고 있지 않아 제조 및 취급설비의 안전한 설계가 어렵다. 이 연구에서는 LDPE 제조공정 중 Bag Filter에서 채취한 분진(LDPE 1)과 Silo 등의 설비 외부에 누설된 퇴적 분진(LDPE 2)에서 채취한 2개 시료에 대하여 분진폭발 시험을 수행하였고 그 중 LDPE 2 분진에 대하여 요약하였다. 입도분석 결과, 체적기준 평균입경은 95.04 ㎛, 수밀도는 0~1 ㎛로 나타났다. 최대폭발압력(Pmax)은 6.6 bar, 최대폭발압력상승속도는 1500 g/m3에서 366 [bar/s]로 분진폭발지수(Kst)는 99.4 bar·m/s로 ST-1 등급임을 확인하였다. 또한, 최소점화에너지는 10 mJ이며 최소점화온도는 450 ℃로 나타났다. 현재, 제조 및 취급 설계는 고밀도 폴리에틸렌(HDPE)의 특성값을 기초로 한다. 그러나, 시험 결과 LDPE 2 분진이 HDPE(입자지름 61.6 ㎛)보다 위험성이 높은 것으로 나타나 LDPE 제조공정에서 HDPE 설계기준을 적용할 때는 주의가 필요하다.

Keywords

Acknowledgement

이 논문은 광운대학교 고재욱 교수님의 정년을 기념하여 투고되었습니다.

References

  1. Kwon, H. G., "A Study on the Characteristics of Dust Explosion for LDPE," RISS Ph.D thesis, Korea National University of Transportation, p.5~16(2018).
  2. Korea Occupational Safety Health Agency (KOSHA), Handbook of Audit Technology for Petrochemical Process (2006).
  3. Korea Occupational Safety Health Agency (KOSHA), Fire & explosion risk assessment of HDPE powder for chemical accident prevention and investigation (2013).
  4. Han, O. S. and Lee, J. S., "Pyrolysis Characteristic and Ignition Energy of High-Density Polyethylene Powder," Korean Institute of Gas., 18(3), 31-37(2014). https://doi.org/10.7842/kigas.2014.18.3.31
  5. KOSHA Guide P-41, "Technical guidelines on how to install detonation outlets to prevent dust explosion," Korea Occupational Safety Health Agency Standard (2015).
  6. NFPA 68 : Standard on Explosion Protection by Deflagration Venting (2007).
  7. KS A ISO 13320, Particle size analysis - Laser diffraction methode, Korean Industrial Standard (2014).
  8. EN 14034-1, "Determination of explosion characteristics of dust clouds-Part 1: Determination of the maximum explosion pressure Pmax of dust clouds," European Standard (2011).
  9. EN 14034-2, "Determination of explosion characteristics of dust clouds-Part 1: Determination of the maximum rate of explosion pressure rise (dp/dt)max of dust clouds," European Standard (2011).
  10. EN 14034-3, "Determination of explosion characteristics of dust clouds-Part 1: Determination of the lower explosion limit LEL of dust clouds," European Standard (2011).
  11. ASTM E 1515-14, Standard Test Method for Minimum Explosible Concentration of Combustible Dusts (2014).
  12. EN 13821, "Potentially explosive atmospheres-explosion prevention and protection-Determination of minimum ignition energy of dust/air mixtures," European Standard (2002).
  13. ASTM E 1491-06, Standard Test Method for Minimum Autoignition Temperature of Dust Clouds (2006).
  14. KS C IEC 61241-2-1, Electrical apparatus for use in the presence of combustible dust-Test method for determination the minimum ignition temperature of dust, Korean Industrial Standard (2003).
  15. Eckhoff, R. K., Dust explosions in the process industries-3rd, Gulf professional publishing (2003).
  16. Lee, J. Y., Lee, K. W., Park, S. Y. and Han, I. S., "Explosion Hazard Assessment of Pharmaceutical Raw Materials Powders," Korean Chem. Eng. Res., 55(5), 600-608(2017).
  17. Siwek 20-L apparatus manual 7.0, Kuhner AG (2015).