소방펌프의 운전상태에 따른 유도전동기의 이상 신호 분석

Analysis of Abnormal Signals for Induction Motor according to Operating Status of Fire Pumps

  • Ku, Bonhyu (Chungbuk Fire Protection Professional Engineer's Office) ;
  • Kim, Doo-Hyun (Department of Safety Engineering, Chungbuk National University) ;
  • Kim, Sung-Chul (Department of Safety Engineering, Chungbuk National University)
  • 투고 : 2022.05.25
  • 심사 : 2022.07.17
  • 발행 : 2022.08.31

초록

This article aims to develop an algorithm that detects fire pump defects by analyzing the current signals of an induction motor, which are triggered by changes in the flow rate and pressure of multistage volute pumps that are used for fire services. The operational status of the pumps was categorized into three: first, normal operation; second, a defect that is caused by a change in the current value; and third, a defect occasioned by a change in current, pressure, and flow rate. When a fire pump was in normal operation, the motor's operating current was measured between 5.06 A and 6.9 A, the flow rate was estimated at 0-0.27 m3/min, and the pressure ranged from 0 to 0.47 MPa. In the event that a defect was caused by an abnormal current value in the motor, it was attributed to the pump's adherence. Furthermore, if there was no source of water, the defect was considered to have been induced by phase-loss operation, no-load operation, or run-stop operation, with the current value of each scenario being measured at > 52.8 A, < 4.13 A, > 45.15 A, and < 3.8 A, respectively, placing its overall range between 0 and 50 A. The sources of defects were detected based on an analysis of the flow rate, pressure, and current, which represent the following causes: air inflow into the casing, inadequate suction of water, and reverse-phase operation, respectively. Each cause entailed the following values: when air seeped into the casing, the pressure was measured at 0.24 MPa irrespective of changes in the flow rate; when there was inadequate suction of water, the pressure was recorded between 0 and 0.05 MPa despite changes in the flow rate; and when the power line's reverse-phase loss was the cause of the defect, the pressure was measured at 0.33 MPa for a flow rate of 0 L/min, and a higher flow rate decreased the pressure to nearly 0 MPa. The results of this study will enable engineers to develop a pump defect detection algorithm that is based on an analysis of current, and this algorithm will facilitate the execution of a program that will control a fire pump defect detection system.

키워드

참고문헌

  1. NFPA, "Standard for the Installation of Stationary Pumps for Fire Protection", NFPA 20, 2016.
  2. National Fire Agency, "Act on Fire Prevention, Installation and Maintenance of Firefighting Facilities, and Safety Management", Article 25, 2019.
  3. NFPA, "Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems", NFPA 25, 2017 edition.
  4. NFSC103, National Fire Safety Code.
  5. P. Zhang, Y. Du, T. G. Habetler and B. Lu, "A Survey of Condition Monitoring and Protection Methods for Medium-voltage Induction Motors", IEEE Transactions on Industry Applications, Vol. 47, No. 1, pp. 34-46, 2010.
  6. E. Elbouchikhi, V. Choqueuse, F. Auger and M. El. H. Benbouzid, "Motor Current Signal Analysis based on a Matched Subspace Detector", IEEE Transactions on Instrumentation and Measurement, Vol. 66, No. 12, pp. 3260-3270, 2017. https://doi.org/10.1109/TIM.2017.2749858
  7. Fire Statistical Year book 2020 "https://www.nfds.go.kr/"
  8. NFPA, "The SFPE Hhand Book of Fire Protection Engineering", 2020 edition.
  9. NFPA, "Standard for Electrical Safety in the Workplace®", NFPA 70E®, 2015 edition.
  10. D. H. Kim, E. J. Kim and S. C. Kim, "A Study on Intelligent Technique for Correlation Application of Overcurrent and Leakage Current Signals in the Indoor Wiring", J. Korean Soc. Saf., Vol. 30, No. 4, pp. 14-19, 2015.
  11. E. J. Kim, D. H. Kim and S. C. Kim, "Analysis for Electrical Fire Possibility Using Fuzzy Logic with Input Variables of Overcurrent and Saturation Time in the Indoor Wiring", J. Korean Soc. Saf., Vol. 30, No. 6, pp. 34-39, 2015.
  12. D. H. Kim and H. S. Lee, "Detection of Current Signal and Thermal Characteristics of Electric Fan Operated in Various Situations" J. Korean Soc. Saf., Vol. 29, No. 3, pp. 20-27, 2014. https://doi.org/10.14346/JKOSOS.2014.29.3.020