DOI QR코드

DOI QR Code

Prediction model of 4.5 K sorption cooler for integrating with adiabatic demagnetization refrigerator (ADR)

  • Received : 2022.02.22
  • Accepted : 2022.03.27
  • Published : 2022.03.31

Abstract

A sorption cooler, which utilizes helium-4 as a working fluid, was previously developed and tested in KAIST. The cooler consists of a sorption pump and a thermosyphon. The developed sorption cooler aims to pre-cool a certain amount of the magnetic refrigerant of an adiabatic demagnetization refrigerator (ADR) from 4.5 K to 2.5 K. To simulate the high heat capacitance of the magnetic refrigerant, liquid helium was utilized not only as a refrigerant for the sorption cooling but also as a thermal capacitor. The previous experiment, however, showed that the lowest temperature of 2.7 K which was slightly higher than the target temperature (2.5 K) was achieved due to the radiation heat leak. This excessive heat leak would not occur when the sorption cooler is completely integrated with the ADR. Thus, based on the experimentally obtained pumping speed, the prediction model for the sorption cooler is developed in this study. The presented model in this paper assumes the sorption cooler is integrated with the ADR and the heat leak is negligible. The model predicts the amount of the liquid helium and the required time for the sorption cooling process. Furthermore, it is confirmed that the performance of the sorption cooler is enhanced by reducing the volume of the thermosiphon. The detailed results and discussions are summarized.

Keywords

Acknowledgement

This research was supported by Basic Science Research Program through the National Research Foundation of Korea (NRF-2017R1A2B3003152) funded by the Ministry of Science, ICT & Future Planning (MSIP).

References

  1. Krinner, S., et al. "Engineering cryogenic setups for 100-qubit scale superconducting circuit systems." EPJ Quantum Technology 6.1 (2019): 2. https://doi.org/10.1140/epjqt/s40507-019-0072-0
  2. Shirron, P., et al. "Development of a cryogen-free continuous ADR for the constellation-X mission." Cryogenics 44.6-8 (2004): 581-588. https://doi.org/10.1016/j.cryogenics.2003.11.011
  3. Duband, L., et al. "Herschel flight models sorption coolers." Cryogenics 48.3-4 (2008): 95-105. https://doi.org/10.1016/j.cryogenics.2008.03.016
  4. Kidnay, A. J., and M. J. Hiza. "Physical adsorption in cryogenic engineering." Cryogenics 10.4 (1970): 271-277. https://doi.org/10.1016/0011-2275(70)90053-6
  5. Jeong, S., et al. "A review of magnetic refrigeration technology." Progress in Superconductivity and Cryogenics 8.2 (2006): 1-10. https://doi.org/10.9714/PSAC.2006.8.2.001
  6. Kwon, D., et al. "Development of the integrated sorption cooler for an adiabatic demagnetization refrigerator (ADR)." Cryogenics (2022): 103421.
  7. Dubinin, MMm. "The potential theory of adsorption of gases and vapors for adsorbents with energetically nonuniform surfaces." Chemical reviews 60.2 (1960): 235-241. https://doi.org/10.1021/cr60204a006
  8. Gallagher, G. R., "Analysis of a magnetically active regenerator", M.S. Thesis, Massachusetts Institute of Technology (1986)
  9. Barclay, J. A., and W. A. Steyert. "Materials for magnetic refrigeration between 2 K and 20 K." Cryogenics 22.2 (1982): 73-80. https://doi.org/10.1016/0011-2275(82)90098-4
  10. Smith, R. V. "Review of heat transfer to helium I." Cryogenics 9.1 (1969): 11-19. https://doi.org/10.1016/0011-2275(69)90251-3
  11. Kapitza, P., "Viscosity of liquid helium below the λ-point." Nature 141.3558 (1938): 74-74. https://doi.org/10.1038/141074a0
  12. Version, HePak. "3.40, Horizon Technologies, 7555 S." Webster St., Littleton, CO 128.