DOI QR코드

DOI QR Code

제3종 분말소화기의 내용연수에 따른 소화약제의 미세도 실험

The A Test of Physical Property of Fire Extinguishing Agent according to Durable Years of the Third-class Powder Extinguisher

  • 손주달 (우석대학교 일반대학원 소방.안전공학과) ;
  • 공하성 (우석대학교 소방방재학과)
  • Ju-Dal, Son (Fire Protection & Safety Engineering, Woosuk University) ;
  • Ha-Sung, Kong (Fire and Disaster Prevention, Woosuk University)
  • 투고 : 2022.11.09
  • 심사 : 2022.12.14
  • 발행 : 2022.12.31

초록

This study collected powder extinguishers with 6-10 years of elapsed life from January 2012 to January 2017 in market, factory, and apartment areas to experiment with changes in fineness and to examine the characteristics of extinguishing power. First, in the case of ABC powder, 98.3 wt% of the 8-year market area and 98.6 wt% of the 10-year apartment complex were found to be inappropriate in the first, second, and third arithmetic average analysis of the powder extinguisher from 6 to 10 years. That is, the fine distribution and size of the powder extinguishing agent particles should be managed within an appropriate range. It is analyzed that the powder fire extinguisher may experience a change in the fineness of the powder depending on the external environment exposure, placement, management status, and age of use, resulting in a decrease in digestive power or inability to radiate. Second, the fire extinguisher cannot be used in the initial fire suppression depending on the place of deployment, the environment of deployment, the progress of the number of years of use, and maintenance, so it is necessary to strengthen the device that enables fire extinguisher maintenance and inspection. Third, in the manufacturing process, the charging method should also be reviewed in consideration of the conditions of the workplace, the humid season, and the rainy environment.

키워드

참고문헌

  1. H. H. Heo(2020), "A study on the installation of fire safety and fire safety of fire extinguishers and single alarm sensors in general housing: Focused on Gyeyang-gu, Incheon." Master's thesis, Gachon University Graduate School, pp. 7-8.
  2. S. S. Kim(2021), "Safety-pin-free fire extinguisher for early fire suppression and experiment and analysis of image output evacuation guidance facilities." Doctoral dissertation, Wooseok University General School, pp. 11-12.
  3. B. S. Son(2015), "A study of recycling standard for dry chemical power extinguisher." Department of Industrial Engineering, Graduate School, Pusan National University, pp. 88-89.
  4. Y. B. Jean(2020), "Development and effect of environmentally friendly fire extinguishing agent based on recycling system of lung powder fire extinguisher." Doctoral dissertation, Hanse University, pp. 118-120.
  5. E. P. Lee(2012), "Analysis of the precautionary measures and causes on explosion accidents of a old dry chemical powder extinguisher." J. Kor. Inst. Fire Sci. Eng, 26(3):91-99. https://doi.org/10.7731/KIFSE.2012.26.3.091
  6. S. W. Lee(2020), "Methods to improve the design of household fire extinguishers through an empirical analysis of consumer compatibility." Fire Science and Engineering, 34(3):58-66. https://doi.org/10.7731/KIFSE.d72f3d22
  7. W. Y. Ko, S. J. In(2018), "Study on the effect of the ABC dry chemical on wood in pyrolysis." Fire Sci. Eng, 32(3):1-7.
  8. H. J. Park(2011), "The extinguishing characteristics of zeolite adsorbed dry chemical powder." Master's thesis, Chungbuk National University, pp. 65-66.
  9. M. J. Jeong, J. M. Yeon(2015), "Assessment of hazard and recycling for discarded agent in powder fire extinguisher." J. of Korea Society of Waste Management, 32(3):238-246.
  10. J. S. Kim, Y. T. Han(2020), "Performance of recycled fire-extinguishing agents in terms of fire-fighting performance management." Fire Science and Engineering, 34(5):34-41.
  11. https://www.law.go.kr/admRulSc.do