DOI QR코드

DOI QR Code

ESS equipped DFIG wind farm with coordinated power control under grid fault conditions

  • 투고 : 2020.05.10
  • 심사 : 2020.10.26
  • 발행 : 2021.01.20

초록

A new structure for doubly fed induction generator (DFIG) wind farms with coordinated power control under grid fault conditions are proposed in this paper. The proposed structure uses one grid side converter (GSC) and one energy storage system (ESS) for the entire wind farm unlike conventional structures, which have one GSC for each of the DFIGs. A converter loss decrease and a reliability enhancement are some of the advantages of the proposed wind farm, under normal operating conditions. The proposed wind farm follows the new grid codes to remain connected to the grid. In addition, it supports the network voltage and frequency stability by generating reactive and active power during and after faults. The ESS is coordinated with the wind farm to generate smooth active power under normal operation. This improves the low voltage ride-through capability of the wind farm under-voltage fault conditions and enhances the frequency response of the wind farm under frequency faults. MATLAB/Simulink software was used to simulate the proposed wind farm structure. An experimental setup was also provided to test the operation of the proposed power circuit topology.

키워드

참고문헌

  1. FERC Order No. 819: Third-Party Provision of Primary Frequency Response Service. (2015)
  2. ENTSO-E, Network Code for Requirements for Grid Connection Applicable to all Generators, (2013)
  3. Al Riyami, H.A.S., et al.: Grid code compliance for integrating 50 MW wind farm into Dhofar power grid. In: Proceedings of the 12th GCC Cigre International Conference for Electrical Equipment, GCC Power, pp. 152-161, 8-10 November (2016)
  4. Liu, Y., Jiang, L., Smith, J.S., Wu, Q.H.: Primary frequency control of DFIG-WTs using bang-bang phase angle controller. IET Gen. Trans. Dis. 12(11), 2670-2678 (2018) https://doi.org/10.1049/iet-gtd.2017.0282
  5. Arani, M.F.M., El-Saadany, E.F.: Implementing virtual inertia in DFIG-based wind power generation. IEEE Trans. Power Syst. 28(2), 1373-1384 (2013) https://doi.org/10.1109/TPWRS.2012.2207972
  6. Yang, J., Chen, Y., Hsu, Y.: Small-signal stability analysis and particle swarm optimization self-tuning frequency control for an islanding system with DFIG wind farm. IET Gen. Trans. Dis. 13(4), 563-574 (2019) https://doi.org/10.1049/iet-gtd.2018.6101
  7. Lee, W.-J., Xie, H., Yue, C., Wen, J., Miao, L.: Coordinated control strategy of wind turbine generator and energy storage equipment for frequency support. IEEE Trans. Ind. Appl. 51(4), 2732-2742 (2015) https://doi.org/10.1109/TIA.2015.2394435
  8. Tohidi, S., Behnam, M.I.: A comprehensive review of LVRT of doubly fed induction wind generators. Ren. Sustain. Energy Rev. 57, 412-419 (2016) https://doi.org/10.1016/j.rser.2015.12.155
  9. Nian, H., Cheng, Ch., Song, Y.: Coordinated control of DFIG system based on repetitive control strategy under generalized harmonic grid voltages. J. Power Electron. 17(3), 733-743 (2017) https://doi.org/10.6113/JPE.2017.17.3.733
  10. Zhang, W., Ma, H., Zhang, J., Chen, L., Qu, Y.: Multi-objective Fuzzy-optimization of crowbar resistances for the low-voltage ride-through of doubly fed induction wind turbine generation system. J. Power Electron. 15(4), 119-1130 (2015)
  11. Haidar, A.M.A., Muttaqi, K.M., Hagh, M.T.: A coordinated control approach for dc link and rotor crowbars to improve FRT of DFIG-based wind turbine. IEEE Trans. Ind. Appl. 53(4), 4073-4086 (2017) https://doi.org/10.1109/TIA.2017.2686341
  12. Yang, L., Xu, Z., Ostergaard, J., Dong, Z.Y., Wong, K.P.: Advanced control strategy of DFIG wind turbines for power system fault ride through. IEEE Trans. Power Syst. 27(2), 713-722 (2012) https://doi.org/10.1109/TPWRS.2011.2174387
  13. Wessels, C., Gebhardt, F., Fuchs, F.W.: Fault ride-through of a DFIG wind turbine using a dynamic voltage restorer during symmetrical and asymmetrical grid faults. IEEE Trans. Power Electron. 26(3), 807-815 (2011) https://doi.org/10.1109/TPEL.2010.2099133
  14. Du, K.-J., Xiao, X.-Y., Wang, Y., Zheng, Z.-X., Li, C.-S.: Enhancing fault ride-through capability of DFIG-based wind turbines using inductive SFCL with coordinated control. IEEE Trans. Appl. Superconduct. 29(2), 1-6 (2019)
  15. Shiddiq Yunus, A.M., Abu-Siada, A., Masoum, M.A.S.: Application of SMES unit to improve DFIG power dispatch and dynamic performance during intermittent misfre and fre-through faults. IEEE Trans. Appl. Superconduct. 23(4), 5-8 (2013)
  16. Saadat, N., Choi, S.S., Vilathgamuwa, D.M.: A statistical evaluation of the capability of distributed renewable generator-energy-storage system in providing load low-voltage ride-through. IEEE Trans. Power Delivery 30(3), 1128-1136 (2015) https://doi.org/10.1109/TPWRD.2014.2360340
  17. Chen, L., et al.: Combined use of a resistive SFCL and DC-link regulation of a SMES for FRT enhancement of a DFIG wind turbine under different faults. IEEE Trans. Appl. Superconduct. 29(2), 1-8 (2019)
  18. Xiao, X.Y., Yang, R.H., Chen, X.-Y., Zheng, Z.X.: Integrated DFIG protection with a modified SMES FCL under symmetrical and asymmetrical faults. IEEE Trans. Appl. Superconduct. 28(4), 1-6 (2018)
  19. Marhaba, M.S., Farhangi, S., Iman-Eini, H., Iravani, R.: Reactive power sharing improvement of droop-controlled DFIG wind turbines in a microgrid. IET Gen. Trans. Dis. 12(4), 842-849 (2017)
  20. Al Riyami, H.A.S., et al.: Grid impact study of the frst wind farm project in Dhofar transmission system. In: The 4th International Conference on Renewable Energy: Generation and Applications (ICREGA16), Belfort, France, February 8-10, 2016
  21. Desingu, K., Selvaraj, R., Chelliah, T.R., Khare, D., Joshi L.P.: Thermal loading of multi-megawatt medium-voltage power converters serving to variable speed large pumped storage units. In: 2018 IEEE International Conference on Power Electronics, Drives and Energy Systems (PEDES), pp. 1-6, Chennai, India, (2018)
  22. Hitachi Power Semiconductor Device: High voltage IGBT module. App.Manual, IGBT-HI-00002 (2009)
  23. Mohsenzade, S., Zarghani, M., Kaboli, S.: A high voltage series stacked IGBT switch with active energy recovery feature for pulsed power application. IEEE Trans. Ind. Electron. 67, 3650-3661 (2019) https://doi.org/10.1109/tie.2019.2921297
  24. Zhou, Y., Zhao, L., Matsuo, I.B.M., Lee, W.: A dynamic weighted aggregation equivalent modeling approach for the DFIG wind farm considering the Weibull distribution for fault analysis. IEEE Trans. Ind. Appl. 55(6), 5514-5523 (2019) https://doi.org/10.1109/tia.2019.2929486
  25. Madhusoodhanan, S., et al.: Solid-state transformer and MV grid tie applications enabled by 15 kV SiC IGBTs and 10 kV SiC MOSFETs based multilevel converters. IEEE Trans. Ind. Appl. 51(4), 43-60 (2015)
  26. Li, H., et al.: Thermal coupling analysis for a multi-chip paralleled IGBT module in a doubly fed wind turbine power converter. IEEE Trans. Energy Convers. 8969, 1-11 (2016)
  27. Lee, J., Muljadi, E., Srensen, P., Kang, Y.C.: Releasable kinetic energy-based inertial control of a DFIG wind power plant. IEEE Trans. Sustain. Energy 7(1), 279-288 (2016) https://doi.org/10.1109/TSTE.2015.2493165

피인용 문헌

  1. Optimal Sizing of Energy Storage System for Operation of Wind Farms Considering Grid-Code Constraints vol.14, pp.17, 2021, https://doi.org/10.3390/en14175478