DOI QR코드

DOI QR Code

Conservativeness Evaluation of Response Acceleration Method used in Seismic Response Analysis of Power Cable Tunnel

전력구의 지진응답해석에 사용되는 응답진도법의 보수성 평가

  • Lim, Jae-Sung (Department of Architecture and Civil Engineering, Chonnam National University) ;
  • Kim, Gi-Bae (Department of Architecture and Civil Engineering, Chonnam National University) ;
  • Chun, Nak-Hyun (Structural & Seismic Tech. Group, KEPCO Research Institute) ;
  • Kim, Jae-Min (Department of Civil Engineering, Chonnam National University)
  • 임재성 (전남대학교 건축토목공학과) ;
  • 김기배 (전남대학교 건축토목공학과) ;
  • 전낙현 (한국전력공사 전력연구원 차세대송변전연구소 구조내진연구실) ;
  • 김재민 (전남대학교 토목공학과)
  • Received : 2021.07.13
  • Accepted : 2021.08.02
  • Published : 2021.10.31

Abstract

In this paper, we present the evaluation results for the conservatism of the response acceleration method (RAM), for seismic response analysis of box-type power cable tunnels. We studied 50 examples, considering the cross sections of 25 power cable tunnels, and two soil conditions for each power cable tunnel. A refined dynamic analysis method considering the soil-structure interaction was further employed to evaluate the conservatism of the RAM. The comparison revelated that the seismic responses computed using the RAM were consistent with those obtained using the refined method, since the averages of response ratio (defined as the ratio of the response by RAM to that of the refined method) approached 1.0, and the standard deviations of the response ratio were less than 5%. Finally, we found that applying a load factor of 1.1 to the response of the RAM allowed for a conservative design for seismic loads.

이 논문에서는 박스형 전력구의 지진응답해석에 사용되는 응답진도법의 보수성을 평가하였다. 이를 위해 25가지 전력구 단면과 각 전력구에 대한 2개의 지반조건을 고려한 총 50개 예제를 선정하였다. 응답진도법의 보수성을 평가하기 위해 동적 지반-구조물 상호작용을 고려한 정밀해석법에 의한 응답과 비교하였다. 비교결과, 정밀해석 응답에 대한 응답진도법에 의한 응답의 비로 정의한 응답비의 평균이 1.0에 근접하며, 응답비의 표준편차도 5% 이내로 매우 작아서, 응답진도법에 의한 해석이 정밀해석법과 일관됨을 알 수 있었다. 마지막으로 응답진도법에 의한 응답에 하중계수 1.1을 적용하면 전력구의 보수적인 내진설계가 가능할 것으로 나타났다.

Keywords

Acknowledgement

이 연구는 한국전력공사의 "송배전설비의 내진설계 실무지침서 개정" 연구과제의 지원을 받아 수행되었습니다.

References

  1. Ariman, T., Muleski, G.E. (1981) A Review of The Response of Buried Pipelines Under Seismic Excitations, J. Earthq. Eng. & Struct. Dyn., 9(2), pp.133~152. https://doi.org/10.1002/eqe.4290090204
  2. Katayama, I. (1990) Studies on Fundamental Problems in Seismic Design Analyses of Critical Structures and Facilities, Ph.D. Dissertation, Kyoto University, Japan.
  3. Katayama, I., Adachi, M., Shimada, M., Tsuzuki, T., Seshimo, Y. (1985) A Quasi-Static Analysis Method for Buried Structures - A Proposal of Response Acceleration Method, Abstracts, 40th Annual Meeting of Japan Society of Civil Engineers, Part 1, pp.737~738.
  4. Kawashima, K. (2000) Seismic Design of Underground Structures in Soft Ground: A Review, In: Fujita and Miyazaki (eds), Geotechnical Aspects of Underground Construction in Soft Ground, Balkema, Rotterdam.
  5. KEPCO (Korea Electric Power Cooperation) (2021) Seismic Design Code of Transmission and Distribution Facilities (DS-0050), Korea.
  6. Kim, D.G., Seo, H.Y., Park, J.W., Choe, I.J. (2006) Earthquake Response Analyses of Underground Structures Using Displacement Responses of Soil, J. Korea Inst. Struct. Maint. Insp., 10(6), pp.133~142.
  7. Kim, J.M. (2010a) Seismic Design of Underground Structures and Directions for Further Improvement, Proc. Earthq. Eng. Soc. Korea Conf., pp.272~311.
  8. Kim, J.M., Kim, D.A. (2010) A Study on Conservativeness of Seismic Deformation Method for Earthquake Analysis of Underground Structures, Proc. Earthq. Eng. Soc. Korea Conf., pp.83~86.
  9. Kim, J.M., Lee, E.H., Chung, K.Y., Seo, C.G. (2012) An Applicability of KIESSI-3D Program for Soil-Structure Interaction Analysis, Proc. Civil Eng. Soc. Korea Conf., pp.334~337.
  10. Kim, J.W. (2010b) Ground Response Seismic Coefficient Method for Earthquake Analysis of Underground Structure, Master Thesis, Chonnam National University, Korea.
  11. Kim, Y.M., Jeong, S.S., Lee, Y.H., Jang, J.B. (2010) Seismic Design of Vertical Shaft using Response Displacement Method, J. Korean Soc. Civil Eng., 30(6), pp.241~253.
  12. Lim, J.S., Yang, D.S., Hwang, K.M., Kim, J.M. (2021) Conservativeness of Response Displacement Method used in the Seismic Response Analysis of Power Cable Tunnel, J. Comput. Struct. Eng. Inst. Korea, 34(4), pp.243~254. https://doi.org/10.7734/COSEIK.2021.34.4.243
  13. MOCT (Ministry of Construction and Transportation) (1999) Manual on Tunnel Design, Korean Tunnelling Association, Korea.
  14. MOCT (Ministry of Construction and Transportation) (2004) Seismic Design Standards for Underground Tunnels, Ministry of Construction and Transportation, Korea.
  15. MOCT (Ministry of Construction and Transportation) (2005) Seismic Design Standard for Urban Railway, Ministry of Construction and Transportation, Korea.
  16. MOIS (Ministry of the Interior and Safety) (2017) Seismic Design Criteria Common Application, Ministry of the Interior and Safety, Korea.
  17. MOLIT (Ministry of Land, Infrastructure and Transport) (2018) General Seismic Design (KDS 17 10 00), Ministry of Land, Infrastructure and Transport, Korea.
  18. MOTIE (Ministry of Trade, Industry and Energy) (2018) Requests for Detailed Revision of each Facility according to the Establishment of Seismic Design Standards for Power Equipment, Ministry of Trade, Industry and Energy, Korea.
  19. Richards, J., Hamel, J., Kassawara, R. (2012) Seismic Evaluation Guidance, Screening, Prioritization and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic, EPRI, USA.
  20. Seo, C.G., Kim, J.M. (2012) KIESSI Program for 3-D Soil-Structure Interaction Analysis, J. Comput. Struct. Eng. Inst. Korea, 25(3), pp.77~83.
  21. Tsuneo, O., Kenichi, Y. (2000) Simplified Analysis Based on Non-Linear Seismic Coefficient Method for Sewage Facilities, Nippon Koei Technical Forum, 9, Japan.