DOI QR코드

DOI QR Code

Parametric analyses for the design of a closed-loop passive containment cooling system

  • Bang, Jungjin (Central Research Institute, Korea Hydro and Nuclear Power, Ltd.) ;
  • Hwang, Ji-Hwan (School of Energy Systems Engineering, Chung-Ang University) ;
  • Kim, Han Gon (Central Research Institute, Korea Hydro and Nuclear Power, Ltd.) ;
  • Jerng, Dong-Wook (School of Energy Systems Engineering, Chung-Ang University)
  • Received : 2020.05.11
  • Accepted : 2020.09.12
  • Published : 2021.04.25

Abstract

A design parameter study is presented for the closed-loop type passive containment cooling system (PCCS) which is equipped with two heat exchangers: one installed at the inside of the containment and the other submerged in the water pool at the outside of the containment. A GOTHIC code model for PCCS performance analyses was set up and the design parameters such as the heat exchanger sizes, locations, and water pool tank volumes were analyzed to investigate the feasibility of installing this type of PCCS in PWRs like OPR-1000 being operated in Korea. We identified the size of the circulation loop and heat exchangers as major design parameters affecting the performance of PCCS. The analyses showed that the heat exchangers in the inside of the containment would be more influential on the heat removal capability of PCCS than that installed in the water pool at the outside of the containment. Hence, it was recommended to down-size the heat exchangers in the water pool to optimize PCCS without compromising its performance. Based on the parametric study, it was demonstrated that a closed-loop type PCCS could be designed sufficiently compact for installation in the available space within the containment of PWRs like OPR-1000.

Keywords

Acknowledgement

This research was partly supported by the Chung-Ang University Graduate Research Scholarship in 2017 and by a National Research Foundation of Korea (NRF) grant funded by the Korean government (MSIP: Ministry of Science, ICT and Future Planning) (No. NRF-2017M2B2B1072552).

References

  1. N. Aksan, H. Choi J, J. Chung Y, J. Cleveland, F.S. D'Auria, N. Fil, O. Gimenez M, M. Ishii, H. Khartabil, K. Korotaev, Passive Safety Systems and Natural Circulation in Water Cooled Nuclear Power Plants, 2009. IAEA-TECDOC-1624.
  2. J. Reyes, Natural Circulation in Water Cooled Nuclear Power Plants Phenomena, Models, and Methodology for System Reliability Assessments, Dr. Jose Reyes (US), 2005.
  3. A. Ahmad, I. Catton, M. Cuesta-Gonzalez, F. Gazzillo, W. Kastenberg, R. Wong, PWR Severe Accident Delineation and Assessment, NUREG/CR-2666, 1983. UCLA-ENG-8284.
  4. F. De Cachard, S. Lomperski, G.-R. Monauni, Thermal-HydraulicModeling of finned tube containment condensers, in: Proceedings of the 6th International Conference on Nuclear Engineering, ICONE 6, 1998, pp. 1-14. Paper 6099.
  5. M. Leiendecker, N. Todreas, M. Driscoll, A. Hurtado, Design and numerical simulation of a two-phase thermosyphon loop as a passive containment cooling system for PWRs, Cambridge, MIT Cent. Adv. Nucl. Energy Syst. 1 (1997). I and II, MIT-ANP-TR-053, Rev.
  6. V. Cavicchia, E. Fiorino, P. Vannini, Innovative containment cooling for a double concrete containment, in: Proceedings of the International Topical Meeting on Advanced Reactors Safety vol. 2, 1997.
  7. C. Byun, D. Jerng, N. Todreas, M. Driscoll, Conceptual design and analysis of a semi-passive containment cooling system for a large concrete containment, Nucl. Eng. Des. 199 (3) (2000) 227-242. https://doi.org/10.1016/S0029-5493(00)00228-4
  8. Z. Huang, W. Ma, Performance evaluation of passive containment cooling system of an advanced PWR using coupled RELAP5/Gothic simulation, Nucl. Eng. Des. 310 (2016) 83-92. https://doi.org/10.1016/j.nucengdes.2016.10.004
  9. S.W. Lee, S. Heo, H.U. Ha, H.G. Kim, The concept of the innovative power reactor, Nucl. Eng. Technol. 49 (7) (2017) 1431-1441. https://doi.org/10.1016/j.net.2017.06.015
  10. H. Ha, S. Lee, H. Kim, Optimal design of passive containment cooling system for innovative PWR, Nucl. Eng. Technol. 49 (5) (2017) 941-952. https://doi.org/10.1016/j.net.2017.03.005
  11. L. Changdong, J. Wenying, Y. Jiang, C. Wei, W. Ting, C. Cheng, X. Hong, Experimental and computational analysis of a passive containment cooling system with closed-loop heat pipe technology, Prog. Nucl. Energy 113 (2019) 206-214. https://doi.org/10.1016/j.pnucene.2019.01.004
  12. M. Gavrilas, P. Hejzlar, N.E. Todreas, M.J. Driscoll, Gothic code evaluation of alternative passive containment cooling features, Nucl. Eng. Des. 166 (3) (1996) 427-442. https://doi.org/10.1016/S0029-5493(96)01259-9
  13. Z.-Y. Hung, Y.-M. Ferng, W.-S. Hsu, B.-S. Pei, Y.-S. Chen, Analysis of AP1000 containment passive cooling system during a loss-of-coolant accident, Ann. Nucl. Energy 85 (2015) 717-724. https://doi.org/10.1016/j.anucene.2015.06.027
  14. S. Estevez-Albuja, G. Jimenez, K. Fernandez-Cosials, C. Queral, Analysis of the AP1000® equipment and instrumentation qualification criteria for a DEGB LOCA with a 3D containment Gothic model, 27 th International Conferece Nuclear Energy of New Europe (NENE) (2018) 10-13. September.
  15. T.L. Schulz, Westinghouse AP1000 advanced passive plant, Nucl. Eng. Des. 236 (14-16) (2006) 1547-1557. https://doi.org/10.1016/j.nucengdes.2006.03.049
  16. C. Zhao, J. Chen, Dynamic characteristics of AP1000 shield building for various water levels and air intakes considering fluid-structure interaction, Prog. Nucl. Energy 70 (2014) 176-187. https://doi.org/10.1016/j.pnucene.2013.08.002
  17. IAEA Advanced Reactors Information System (ARSI), Status Report 100- Economic Simplified Boiling Water Reactor, ESBWR), 2011.
  18. IAEA Advanced Reactors Information System (ARSI), Status Report 108- VVER1200 (V-491), 2011. VVER-1200 (V-491).
  19. J. Xing, D. Song, Y. Wu, HPR1000: advanced pressurized water reactor with active and passive safety, Engineering 2 (1) (2016) 79-87. https://doi.org/10.1016/j.eng.2016.01.017
  20. KHNP, Hanuel 3,4 Final Safety Analysis Report, 1998.
  21. E.P.M.F. Rahnm, Gothic THERMAL HYDRAULICS ANALYSIS PACKAGE USER MANUAL Version 8.0(QA). NAI 8907e8909, Rev. 12, Numerical Applications Inc., 2012.
  22. B.-U. Bae, B.-J. Yun, S. Kim, K.H. Kang, Design of condensation heat exchanger for the PAFS (passive auxiliary feedwater system) of APR+ (advanced power reactor plus), Ann. Nucl. Energy 46 (2012) 134-143. https://doi.org/10.1016/j.anucene.2012.03.029
  23. S.-S. Jeon, Y.-J. Chooa, S.-J. Hong, Gothic multi-dimensional analysis for containment implemented with passive containment cooling system (PCCS), in: Transactions of the Korean Nuclear Society Spring Meeting, 2017.
  24. E.P.M.F. Rahnm, Gothic THERMAL HYDRAULIC ANALYSIS PACKAGE TECHNICAL MANUAL Version 8.0(QA). NAI 8907e06, Rev. 19, Numerical Applications Inc., 2012.
  25. H. Liu, N. Todreas, M. Driscoll, An experimental investigation of a passive cooling unit for nuclear plant containment, Nucl. Eng. Des. 199 (3) (2000) 243-255. https://doi.org/10.1016/S0029-5493(00)00229-6
  26. L.E. Herranz, J.L. Munoz-Cobo, M.a.J. Palomo, Modeling condensation heat transfer on a horizontal finned tube in the presence of noncondensable gases, Nucl. Eng. Des. 201 (2-3) (2000) 273-288. https://doi.org/10.1016/S0029-5493(00)00278-8

Cited by

  1. Dynamic thermal performance analysis for fin-concrete ceiling in main control rooms of passive nuclear power plants vol.28, 2021, https://doi.org/10.1016/j.csite.2021.101402