Abstract
Purpose: The risk assessment for earthquakes was conducted in accordance with the current design standard (KBC2016) for the Coalescer facility, which is a major facility of energy storage facilities. Method: The risk assessment for earthquakes was conducted in accordance with the current design standard (KBC2016) for the Coalescer facility, which is a major facility of energy storage facilities. Result: In this study, by statically loading earthquake loads and evaluating the level of collapse prevention of special-class structures, facility managers can easily recognize and evaluate the risk level, and this analysis result can be applied to future facility risk management. Earthquake analysis was performed so that. Conclusion: As a result of analyzing the Coalescer facility according to the current design standard KBC2016, the stress ratio of the main supporting members was found to be up to 4.7%. Therefore, the members supporting Coalescer were interpreted as being safe against earthquakes with a reproducibility period of 2400 years that may occur in Korea.
연구목적: 에너지저장시설의 주요 시설물인 Coalescer 시설물을 대상으로 현행 설계기준(KBC2016)에 따라 지진에 대한 위험성평가를 수행하였다. 연구방법: 구조해석은 상용프로그램인 MIDAS-IT의 MIDAS GENw를 사용하였고, 구조물의 해석을 위해 기존 설계 도서를 준용하였으며, 해석에 사용한 하중은 국토교통부의 「건축구조기준 KBC2016」와 미국 연방기준인 「Provisions of the Uniform Building Code」를 따랐다. 연구결과: 본 연구에서는 지진하중을 정적으로 재하하고 특급 구조물의 붕괴방지수준에 대하여 평가함으로써 시설물의 관리자가 간편하게 위험도를 인지하고 평가할 수 있도록 고려하였으며, 본 해석결과를 활용하여 향후 시설물의 위험관리에 적용할 수 있도록 지진해석을 수행하였다. 결론: 현재 설계기준인 KBC2016에 의해 Coalescer 시설을 해석한 결과, 주요 지지부재의 stress ratio는 최대 4.7% 정도로 나타났다. 따라서 Coalescer를 지지하는 부재는 국내에 발생할 수 있는 재현주기 2400년 수준의 지진에 대하여 안전한 것으로 해석되었다.