Abstract
Apartment buildings are becoming taller and more densely populated with the advancements in science and the development of cities, Consequently, various amenities and safety facilities are being developed to improve the quality of life for residents. However, according to statistics, the number of casualties in apartments accounts for a high proportion of accidents, and the leading cause of the casualties is smoke emitted from fires while sleeping at night. Although it is best to install separate indoor facilities in apartments to minimize smoke damages to occupants, it is useful to minimize the smoke damages by utilizing the installed facilities while reducing the financial burden of occupants. Based on the review, the heat exchanger ventilation system and the kitchen collective exhaust system were selected, and the feasibility of these systems was verified through fire simulation. From the verification results, the available safe egress time improved by 27, 30, and 35 s on the 25th, 35th, 50th floors, respectively.
공동주택은 과학의 발전과 도시의 랜드마크적 상징성으로 점점 고층화 고밀화되어 가고, 입주민의 삶의 질 향상을 위해 각종 편의시설과 안전시설도 함께 발전되어 가고 있다. 그러나 통계자료에 의하면 공동주택은 사고 발생 대비 사상자가 높은 비중을 차지하고 있으며, 사상자의 주요 피해 원인은 심야 시간에 수면 상태에서 화재를 늦게 인지하여 연기에 의하여 많은 인명피해가 발생하고 있다. 공동주택에서 재실자의 연기피해를 최소화하기 위하여 실내에 별도의 배연 시설을 설치하는 것이 가장 최선의 방법이지만, 입주자의 경제적 부담을 줄이면서 현재 설치된 시설물을 활용하여 연기피해를 최소화하는 것이 공학적 입장에서 유용한 조치라고 판단된다. 검토 결과 전열교환환기방식과 주방공용배기방식을 선정하여 화재 시뮬레이션을 통하여 실증 여부를 검증하였다. 검증결과 피난허용시간(ASET)이 25층은 27 s, 35층은 30 s, 50층은 35 s가 향상되었다.