DOI QR코드

DOI QR Code

Experimental Study on the Effect of a Metal Storage Cask and Openings on Flame Temperature in a Compartment Fire

  • Received : 2020.07.27
  • Accepted : 2020.09.14
  • Published : 2020.09.30

Abstract

Compartment fire tests were performed using kerosene and Jet A-1 as fire sources to evaluate the relationship between flame temperature and opening size. The tests were performed for a fire caused by the release of kerosene owing to vehicle impact, and for a fire caused by the release of Jet-A-1 owing to airplane collision. The compartment fire tests were performed using a 1/3-scale model of a metal storage cask when the flame temperature was deemed to be the highest. We found the combustion time of Jet-A-1 to be shorter than that of kerosene, and consequently, the flame temperature of Jet-A-1 was measured to be higher than that of kerosene. When the opening was installed on the compartment roof, even though the area of the opening was small, the ventilation factor was large, resulting in a high flame temperature and long combustion. Therefore, the position of the opening is a crucial factor that affects the flame temperature. When the metal storage cask was stored in the compartment, the flame temperature decreased proportionally with the energy that the metal storage cask received from the flame.

Keywords

References

  1. Nuclear Safety and Security Commission, Regulations for the Safe Transport of Radioactive Material, NSSC Notice No. 2019-7 (2019).
  2. International Atomic Energy Agency, Regulations for Packaging and Transportation of Radioactive Material, IAEA Safety standard Series No. SSR-6 (2018).
  3. United States Nuclear Regulatory Commission, Packaging & Transportation of Radioactive Material, U.S. Code of Federal Regulations, Title 10, Part 71 (2005).
  4. M. Greiner, M. del Valle, C. Lopez, V. Figueroa, and E. Abu-Irshaid, "Thermal Measurements of a Rail-Cask- Size Pipe-Calorimeter in Jet Fuel Fires", Proc. of ASME 2009 Heat Transfer Summer Conference, HT2009-88520, 173-181, July 19-23, 2009, San Francisco.
  5. V.G. Figueroa, C. Lopez, and V.F. Nicolette, "Regulatory Fire Test Requirements for Plutonium Air Transport Packages: JP-4 or JP-5 vs. JP-8 Aviation Fuel", Proc. of the PATRAM 2010 Conference, October 3-8, 2010, London.
  6. W. Brucher, M. Rowekamp, and V. Kunze, "FDS3 Simulations of Indoor Hydrocarbon Fires Engulfing Radioactive Waste Packages", Proc. of the PATRAM 2004 Conference, September 20-24, 2004, Berlin.
  7. B. Thomauske, "Realization of the German concept for interim storage of spent nuclear fuel-current situation and prospects", Proc. of the Waste Management '03 Conference, February 23-27, 2003, Tucson, AZ.
  8. J.G. Quintiere, Principles of fire behavior, 2nd ed., 267-269, CRC Press, New York (2017).
  9. United States Nuclear Regulatory Commission, Quantitative Fire Hazard Analysis Methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program, U.S. NRC Report, NUREG-1805 (2004).
  10. J.G. Quintiere, Fundamentals of Fire Phenomena, 339-355, Wiley, England (2006).
  11. J.S. Han, S.J. Kim, and Y. Kim, "Effect of droplet length on a burning constant rate of suspended droplet", J. of the Korean Society of Propulsion Engineers, 6(1), 47-54 (2002).
  12. S.E. Magnuson and S. Thelandersson, Temperature-Time curves of Complete Process of Fire Development-Theoretical Study of Wood Fuels in Enclosed Spaces, Acta Politechnica Scandinavica, Ci 65, 34-38, Royal Swedish Academy of Engineering Sciences, Stockholm (1970).
  13. International Atomic Energy Agency, Advisory Material for the IAEA Regulations for the Safe Transport of Radioactive Material, IAEA Safety Standards No. SSG-26 (2012).
  14. United States Nuclear Regulatory Commission, Standard Review Plan for Spent Fuel Dry Cask Storage Systems, U.S. NRC Report, NUREG-1536 (2010).
  15. American Society of Mechanical Engineers Boiler and Pressure Vessel Code, Class 1 Components in Elevated Temperature Service, 1995 Code Case, Nuclear Components, ASME Code Case N-47-33 (1995).
  16. Parker Seal Company, Parker O-Ring Handbook, Catalog ORD 5700/US, 18 (2007).