Emergency Brushless Synchronous Generator Having Rotating Exciter Status Monitoring and Protection Functions

  • Received : 2020.11.19
  • Accepted : 2020.12.28
  • Published : 2020.12.31

Abstract

This paper presents an emergency brushless synchronous generator having rotating exciter status monitoring and protection functions. For monitoring the rotating exciter status, a wireless rotor status detector and a digital AVR(Automatic Voltage Regulator), which has a wireless communication capability, are proposed. The proposed rotor status detector detects temperatures of exciter armature and main field windings and input voltage and current of the main field. Therefore, it is possible to protect the generator from the over-temperature of windings and detect the exciter bridge diode fault. Furthermore, the proposed digital AVR has rotor status monitoring and protection function, and remote generator tuning, wireless group parallel operation function. So the operator can efficiently operate the generator using a smartphone from a remote area.

Keywords

References

  1. K. M. Cho, "Digital AVR for Synchronous Generator," in Final Report of Business Development Technology Project, Small and Medium Business Administration, 2013.
  2. J. K. Noland, F. Everstedt, J. J. Perez-Loya, J. Abrahamsson, U. Lundin, "Design and Characterization of a Rotating Brushless Outer Pole PM Exciter for a Synchronous Generator," IEEE Trans. on Industry Applications, Vol. 53, No. 3, pp. 2016-2027, May-Jun. 2017. https://doi.org/10.1109/TIA.2017.2669890
  3. K. H. Yoo, B. S. Na, K. M. Cho, J. H. Shin, Y. S. Kim, "Emergency generator with rotor protection function," in Proc. of the Summer Conference of the Korean Institute of Electrical Engineers, Busan, 2010, pp. 896-897.
  4. K. M. Cho, "Development of synchronous generator rotor condition monitoring device," in Final Report of Business Development Technology Project, Small and Medium Business Administration, 2012.
  5. S. H. Yang, K. M. Cho, "An Automatic Voltage Regulator Having Remote Management Functions for the Diesel Generator," in Proc. of the Autumn Conference of the Korean Institute of Electrical Engineers, Daejun, 2016, pp. 229-231.
  6. J. Sottile, F. C. Trutt, A.W. Leedy, "Condition Monitoring of Brushless Three-Phase Synchronous Generators with Stator Winding or Rotor Circuit Deterioration," IEEE Trans. on Industry Applications, Vol. 42, No. 5, pp. 1209-1215, 2006. https://doi.org/10.1109/TIA.2006.880831
  7. P. J. Tavner, "Review of Condition Monitoring of Rotating Electrical Machines," IET Electrical Power Applications, Vol. 2, No. 4, pp. 215-247, 2008. https://doi.org/10.1049/iet-epa:20070280
  8. J. Y. Han, S. H. Lee, "Implementation of Aerogenerator Remote Individual Monitoring and Braking System," Journal of KIIT, Vol. 11, No. 4, pp. 27-33, April 2013.
  9. S. B. Brahim, R. Bouallegue, J. David, T. H. Vuong, "Wireless Communication to Monitor the Rotating Electrical Machines," IEEE 3rd International Conference on Software, Telecommunications and Computer Networks (SoftCOM), Sep., 2015, Split, Croatia, pp. 1-4.
  10. P. S. Kumar, L. Xie, B. H. Soong, "Feasibility of Wireless RF Communication inside Rotating Electrical Machines for Condition Monitoring Applications," IEEE 19th International Conference on Electrical Machines and Systems (ICEMS), Nov., 2016, Chiba, Japan, pp. 1-6.
  11. V. Sarkimaki, R. Tiainen, T. Lindh, J. Ahola, "Applicability of ZigBee Technology to Electric Motor Rotor Measurements," IEEE International Symposium on Power Electronics, Electrical Drives, Automation and Motion-SPEEDAM 2006, May, 2006, Taormina, Italy, pp. S36-1-5.
  12. Y. Wu, B. Cai, Q. Ma, "An Online Diagnostic Method for Rotary Diode Open-Circuit Faults in Brushless Exciters," IEEE Trans. on Energy Conversion, Vol. 33, No. 4, pp. 1677-1685, Dec. 2018. https://doi.org/10.1109/TEC.2018.2831241
  13. M. Rahnama, A. Vahedi, A. M. Alikhani, N. Takorabet, "Diode Open-Circuit Fault Detection in Rectifier Bridge of the Brushless Synchronous Generator," in Proc. Of the International Conference on Electrical Machines (ICEM), Alexandroupoli, 2018, pp. 1821-1826.
  14. T. L. Borim, J. Casey, T. Begalke, C. Ogawa, "Benefits of Monitoring the Rotor Electrical Quantities and Transmitting by Wireless Communication," IEEE Petroleum and Chemical Industry Committee Conference (PCIC), Oct. 2015, Houston, TX, USA, pp. 1-10.
  15. P. S. Kumar, L. Xie, K. Thiha, B. H. Soong, V. Vaiyapuri, S. Nadarajan, "Rotor Mounted Wireless Sensors for Condition Monitoring of Brushless Synchronous Generator," in Proc. of IECON 2017 - 43rd Annual Conference of the IEEE Industrial Electronics Society, Oct.-Nov., Beijing, China, 2017, pp. 3221-3226.
  16. H. W. Je, O. Yang, "Remote Monitoring System of Photovoltaic Inverter using Zigbee Communication," Journal of KIIT, Vol. 10, No. 2, pp. 93-100, Feb. 2012.