사고사례 정밀분석을 통한 상압저장탱크의 안전에 관한 연구

A Study on Safety of Atmospheric Storage Tank through Detailed Analysis of Accident Case

  • 임지표 (한국산업안전보건공단 화학사고예방센터) ;
  • 박수율 (한국산업안전보건공단 화학사고예방센터)
  • 투고 : 2019.03.25
  • 심사 : 2019.07.12
  • 발행 : 2019.08.31

초록

In October 2018, a large fire occurred after an explosion in an internal floating roof tank (IFRT) that stores gasoline by wind lantern in Goyang city, Gyeonggi-do. Although there was no casualty damage, the fire inside the tank lasted for 17 hours, and caused a great wave socially, and it was a chance to review the safety of the atmospheric storage tank. In this study, the necessity of installing a flame arrester at peripheral vents was examined through the calculation of the size of ventilation pipe and ventilation rate of internal floating roof tanks in terms of the function of the peripheral vent. Next, the necessity of the emergency shut-off valve linked with the high-level alarm to prevent the overflow of the atmospheric storage tank was confirmed by LOPA. Finally, safety measures to prevent overpressure, flame propagation and overflow which cause major accidents in atmospheric storage tank are suggested.

키워드

참고문헌

  1. National Fire Protection Association(NFPA), NFPA 30, "Flammable and Combustible Liquids Code", p. 13, 2003.
  2. Korea Occupational Safety and Health Agency, KOSHA Guide(D-14-2012), "Technical Guideline for Installation of Vent Facility", pp. 1-7, 2012.
  3. https://ko.wikipedia.org/wiki/Explosion accident at an oil reservoir in Go-Yang
  4. Health & Safety Executive, "The Buncefield Investigation (Liquid flow and vapor production)", pp. 1-42, 2007.
  5. Korea Petrochemical Industry Association, "Material Safety Data Sheet(Toluene)", pp. 1-8, 2016.
  6. American Petroleum Institute, API Std 2000, "Venting Atmospheric and Low-pressure Storage Tanks", pp. 1-72, 2014.
  7. J. P. Yim, D. Y. Jin, B. C. Ma, S. J. Kang and C. B. Chung, "Review of Safety for Pressure-Relieving Systems of Small to Middle Scale Chemicals Plants", Vol. 30, No. 6, pp. 48-55, 2015. https://doi.org/10.14346/JKOSOS.2015.30.6.48
  8. J. P. Yim and C. B. Chung, "A Study on Classification of Explosion Hazardous Area for Facilities using Lighter-than-Air Gases", J. Korea Soc. Saf., Vol. 29, No. 2, pp. 24-30, 2014. https://doi.org/10.14346/JKOSOS.2014.29.2.024
  9. American Petroleum Institute, API Std 650, "Welded Tanks for Oil Storage", pp. 86-94, 2014.
  10. Korea Maritime Safety Tribunal, "Crude Oil Wuyishan Wharf Facility Contact Accident Investigation Report", pp. 1-30, 2015.
  11. Korea Occupational Safety and Health Agency, KOSHA Guide(D-11-2012), "Technical Guideline for Installation of Emergency Shutoff Valve", pp. 1-9, 2012.
  12. Center for Chemical Process Safety, "Layer of Protection Analysis(Simplified Process Risk Assessment)", pp. 31-149, 2001.
  13. Korea Occupational Safety and Health Agency, KOSHA Guide(P-102-2012), "Technical Guideline for Accident Damage Prediction Technique", pp. 12-13, 2012.
  14. Korea Occupational Safety and Health Agency, KOSHA Guide(P-82-2012), "Technical Guideline for HAZOP Technique for Continuous Process", pp. 1-14, 2012.
  15. K. Park, "Simplified Risk Assessment on Fire Hazard of LPG Filling Station", Korean J. Chem. Eng., Vol. 34, Issue 3, pp. 642-650, 2017. https://doi.org/10.1007/s11814-016-0325-x
  16. Korea Occupational Safety and Health Agency, KOSHA Guide(P-70-2016), "Technical Guideline for Installation of Flame Arrestor", pp. 1-18, 2016.
  17. Korea Occupational Safety and Health Agency, KOSHA Guide(D-8-2017), "Technical Guideline for Installation of Flame Arrestor", pp. 1-5, 2017.