DOI QR코드

DOI QR Code

Examination on Fire Extinguishing Performance of Full Cone and Hollow Cone Twin-fluid Atomizers: Effects of Supply Gas and Water Mist

중실원추형 및 중공원추형 2유체 미립화기의 화재 소화 성능 검토: 공급 기체와 미분무 영향

  • Kim, Dong Hwan (Dept. of Fire Protection Engineering, Pukyong Nat'l Univ.) ;
  • Lee, Chi Young (Dept. of Fire Protection Engineering, Pukyong Nat'l Univ.)
  • 김동환 (부경대학교 소방공학과 대학원) ;
  • 이치영 (부경대학교 소방공학과)
  • Received : 2019.09.17
  • Accepted : 2019.10.14
  • Published : 2019.10.31

Abstract

In the present study, the effects of supply gas and water mist on the heptane pool fire extinguishing performance were investigated using the full cone and hollow cone twin-fluid atomizers. Air or nitrogen of 30 lpm (Liter per minute; L/min) was used as the supply gas, and the experiments were conducted under the water flow rate conditions of 0 lpm (i.e., discharge of air or nitrogen only) and 0.085 lpm (i.e., discharge of water mist with supply gas). Experimental results confirmed that the use of water mist discharge with the supply gas and full cone spray pattern reduced the fire extinguishing time as compared to that of only supply gas discharge and hollow cone spray pattern. In addition, for the discharge of water mist using the full cone twin-fluid atomizer, water mist significantly affected fire extinguishing performance, whereas the effect of the supply gas was less pronounced. On the other hand, for the discharge of water mist using the hollow cone twin-fluid atomizer, the fire extinguishing time was remarkably reduced by the supply of nitrogen, as compared with that of air, indicating that the supply gas as well as water mist can significantly affect fire extinguishing performance.

본 연구에서는 분사 형태(Spray pattern)가 중실원추형(Full cone) 및 중공원추형(Hollow cone)인 2유체 미립화기를 이용하여 공급 기체 및 미분무가 헵탄 풀화재(Heptane pool fire) 소화 성능에 미치는 영향을 검토하였다. 2유체 미립화기의 공급 기체로 30 lpm (Liter per minute; L/min)의 공기 또는 질소를 이용하였으며, 물을 공급하지 않은 경우(즉, 공기 또는 질소만 분사한 경우)와 물 0.085 lpm을 공급한 경우(즉, 미분무와 공급 기체를 함께 분사한 경우)에 대해 실험을 수행하였다. 실험 결과, 공급 기체만 분사한 경우보다 미분무와 공급 기체를 함께 분사한 경우에, 그리고 중공원추형인 경우보다 중실원추형인 경우에 빠르게 화재 소화 가능함을 확인하였다. 또한, 중실원추형의 경우, 미분무와 공급 기체 함께 분사 시 화재 소화 성능에 미분무의 영향은 지배적이었으나 공급 기체의 영향은 미비한 것으로 관찰되었다. 반면, 중공원추형의 경우, 중실원추형과 달리 미분무와 공급 기체 함께 분사 시 공급 기체로 질소를 공급한 경우가 공기를 공급한 경우에 비해 평균 화재 소화 시간이 확연하게 짧아지는 것으로 측정되었고, 이를 통해 미분무 뿐 아니라 공급 기체도 화재 소화 성능에 지대한 영향을 미칠 수 있음을 확인하였다.

Keywords

References

  1. Z. Liu and A. K. Kim, "A Review of Water Mist Fire Suppression Systems-Fundamental Studies", Journal of Fire Protection Engineering, Vol. 10, No. 3, pp. 32-50 (1999). https://doi.org/10.1177/104239159901000303
  2. NFPA 750 "Standard on Water Mist Fire Protection Systems", 2000 Edition, National Fire Protection Association, Quincy, USA (2000).
  3. NFSC (National Fire Safety Code) 104A, § 3(2) (2019).
  4. J. R. Mawhinney, B. Z. Dlugogorski and A. K. Kim, "A Closer Look at the Fire Extinguishing Properties of Water Mist", Fire Safety Science, Vol. 4, pp. 47-60 (1994). https://doi.org/10.3801/IAFSS.FSS.4-47
  5. A. H. Lefebvre and V. G. McDonell, "Atomization and Sprays", 2nd Edition, CRC Press, Boca Raton, USA (2017).
  6. L. Yinshui, J. Zhuo, W. Dan and L. Xiaohui, "Experimental Research on the Water Mist Fire Suppression Performance in an Enclosed Space by Changing the Characteristics of Nozzles", Experimental Thermal and Fluid Science, Vol. 52, pp. 174-181 (2014). https://doi.org/10.1016/j.expthermflusci.2013.09.008
  7. A. Jenft, A. Collin, P. Boulet, G. Pianet, A. Breton and A. Muller, "Experimental and Numerical Study of Pool Fire Suppression Using Water Mist", Fire Safety Journal, Vol. 67, pp. 1-12 (2014). https://doi.org/10.1016/j.firesaf.2014.05.003
  8. Y. Ferng and C. Liu, "Numerically Investigating Fire Suppression Mechanisms for the Water Mist with Various Droplet Sizes through FDS Code", Nuclear Engineering and Design, Vol. 241, No. 8, pp. 3142-3148 (2011). https://doi.org/10.1016/j.nucengdes.2011.06.002
  9. M. Gupta, A. Pasi, A. Ray and S. R. Kale, "An Experimental Study of the Effects of Water Mist Characteristics on Pool Fire Suppression", Experimental Thermal and Fluid Science, Vol. 44, pp. 768-778 (2013). https://doi.org/10.1016/j.expthermflusci.2012.09.020
  10. S. Lal, M. Gupta, A. Kushari, J. C. Kapoor and S. Maji, "Suppression of Pool Fire in a Large Enclosure with Water Mist", International Journal of Spray and Combustion Dynamics, Vol. 5, No. 3, pp. 181-200 (2013). https://doi.org/10.1260/1756-8277.5.3.181
  11. M. Gupta, R. Rajora, S. Sahai, R. Shankar, A. Ray and S. R. Kale, "Experimental Evaluation of Fire Suppression Characteristics of Twin Fluid Water Mist System", Fire Safety Journal, Vol. 54, pp. 130-142 (2012). https://doi.org/10.1016/j.firesaf.2012.08.007
  12. Z. Liu, A. K. Kim and J. Z. Su, "Examination of the Extinguishment Performance of a Water Mist System Using Continuous and Cycling Discharges", Fire Technology, Vol. 35, No. 4, pp. 336-361 (1999). https://doi.org/10.1023/A:1015453014065
  13. C. Shin, G. Jeon and K. Kim, "Extinguishing of Oil Fire by Water Mist Suppression System Using Compressed Inert Gas", Journal of the Korean Society of Safety, Vol. 25, No. 6, pp. 109-114 (2010).
  14. C. S. Jeong and C. Y. Lee, "Experimental Study on the Extinguishing Characteristics of Twin-fluid Nozzle using a Small-scale Hexane Pool Fire", Fire Science and Engineering, Vol. 32, No. 3, pp. 35-41 (2018). https://doi.org/10.7731/KIFSE.2018.32.3.035
  15. Y. A. Cengel and A. J. Ghajar, "Heat and Mass Transfer: Fundamentals and Applications", 5th Edition, McGraw-Hill Education, New York, USA (2015).
  16. N. Ashgriz (Editor), "Handbook of Atomization and Sprays: Theory and Applications", Springer Science & Business Media, New York, USA (2011).
  17. B. Karlsson and J. G. Quintiere, "Enclosure Fire Dynamics", CRC Press, Washington, USA (2000).
  18. M. Yuan, B. Chen, C. Li, J. Zhang and S. Lu, "Analysis of the Combustion Efficiencies and Heat Release Rates of Pool Fires in Ceiling Vented Compartments", Procedia Engineering, Vol. 62, pp. 275-282 (2013). https://doi.org/10.1016/j.proeng.2013.08.065
  19. Society of Fire Protection Engineers, "SFPE Handbook of Fire Protection Engineering", 3rd Edition, NFPA, Quincy, USA (2002).