Abstract
Zinc coatings are widely used because of their environmental friendliness and high performance. In general, the coating temperature is a major factor in determining the coating layer thickness and coating quality. In the case of a zinc coating, a uniform and appropriate coating temperature is required. In this study, a thermal flow simulation of the air flow was performed to analyze the temperature distribution of a zinc spray coating room in a natural convection state. Using SolidWorks, modeling was performed for two spray coating rooms, a preheating room, and a drying room, and a thermal flow coupled analysis was performed using ANSYS-FLUENT. As a result of the analysis, the temperature distribution characteristics in the spray coating rooms were determined. It was found that the present temperature was below the target temperature of $25^{\circ}C$. Simulations were conducted for two different boundary conditions (one with a heater added and another with the open part closed). The simulation results show that the method of closing the open part is better than adding the heater.
아연말 코팅은 친환경성 및 고성능으로 인하여 널리 사용되고 있다. 일반적으로 코팅온도가 코팅층 두께 및 코팅 품질을 결정하는 주요한 요소이며 아연말 코팅의 경우에도 코팅 룸 내 균일하며 적절한 코팅온도가 요구된다. 본 연구에서는 일반적으로 사용하는 자연대류 상태에서의 아연말 스프레이 코팅 룸의 온도 분포를 해석하기 위해 룸 내부의 공기 유동을 포함하는 열 유동 전산 시뮬레이션을 수행하였다. 3차원 CAD 프로그램인 SolidWorks를 이용하여 스프레이 코팅 룸 전체와 예열실과 건조실을 모두 고려한 모델링을 수행하였으며 ANSYS의 FLUENT 프로그램을 이용하여 열 유동연성 해석을 수행하였다. 해석 결과 스프레이 코팅 룸에서의 온도 분포 특성을 파악할 수 있었으며, 현재의 상태로는 목표 온도 값인 $25^{\circ}C$에 미달하고 있었음을 알 수 있었다. 이에 두 가지 다른 경계조건 (히터를 추가하는 방법과 현재 상태에서 Open 부분을 닫는 방법) 에 대해 열 유동 시뮬레이션을 수행하였으며, 시뮬레이션 결과 히터를 추가하기보다는 Open된 부분을 닫는 방법이 더 좋은 결과를 나타내었다.