Abstract
In this study, the axial stiffness of existing piles (Kve) of vertical extension remodeled building was quantified through theoretical and experimental approaches. Theoretically induced upper and lower boundary of the pile axial stiffness was estimated by using the formula proposed by Randolph and Wroth (1978), which can estimate the axial stiffness of rigid and flexible pile subjected under soil confinement. In addition, 38 cases of field measurement data on deteriorated piles with various diameters constructed in the period between 1995 - 1997 were taken in to account by overlapping the field data with the theoretical boundary of the axial stiffness. Through this the maximum axial stiffness of existing pile due to deterioration and long service time was presented for various slenderness ratio (L/D), which can be used in estimating the necessary axial stiffness of reinforcing piles(Kvr) for the vertical extension remodeling. The lower 95% value of the estimated axial stiffness of existing pile will be induced through statistical processing.
본 연구에서는 수직증축 구조물의 기존말뚝의 축강성(Kve)을 이론적인 접근과 현장 계측 결과를 바탕으로 추정하였다. 이론적인 접근에는 Randolph와 Wroth(1978)가 제안한 축강성 공식을 적용하여, 지중에 설치된 강성 및 연성말뚝의 세장비(L/D)에 따른 축강성의 범위를 도출하였다. 여기에, 1995 - 1997년 사이에 설치된 38본 말뚝의 계측된 시공 당시 축강성을 이론적으로 도출한 축강성 범위에 중첩해서 고려하였다. 이를 통하여, 노후화와 열화에 의하여 감소한 기존말뚝의 축강성의 최대값을 세장비에 따라 제안하였고, 도출된 값을 통계적인 기법을 통하여 상위 95% 값을 제안하여 신설 보강말뚝 설계 시 필요한 최소 축강성(Kvr)을 산정하는 데에 활용할 수 있도록 하였다.