DOI QR코드

DOI QR Code

Performance Evaluation of the Cast-in-place Anchor Bolt in Non-cracked Concrete used in Power Plant Facilities

비균열 콘크리트에 매립된 발전설비 정착부 선 설치 앵커의 구조성능 평가

  • Kim, Dong-Ik (Department of Civil Engineering, Gangneung-Wonju Nation University) ;
  • Jong, Woo-Young (Department of Civil Engineering, Gangneung-Wonju Nation University)
  • 김동익 (강릉원주대학교 토목공학과) ;
  • 정우영 (강릉원주대학교 토목공학과)
  • Received : 2019.09.25
  • Accepted : 2019.11.01
  • Published : 2019.11.30

Abstract

The seismic performance and stability of operating facilities installed in domestic power plants need to be verified because of the increased incidence of earthquakes resulting in power plant damage due to the overturning failure of electric operating facilities. In this study, a structural performance evaluation of the anchor bolts constructed to setup the operating facilities on concrete slabs was carried out through an on-site inspection of power plants, called Daechung-Dam. M10 J hook and M12 J hook anchor bolts were installed in the field unit. According to the ASTM E 488-96 specifications, anchor bolt pullout and shear tests were carried out and compared with the anchor-bolt design standards. The results from the tension and shear pullout tests showed that the M10 and M12 J hook anchor bolts had higher performance than the required design load. Thus, they were found to be safe enough. Nevertheless, more research in the field of analytical study will be needed in the near future.

과거 지진 발생으로 인하여 발전소 내 전력 운용설비의 전도로 인한 피해가 크게 발생하여 이에 대한 국내 발전소 운용설비 정착부에 대한 내진 안정성 평가는 매우 중요하다. 본 연구에서는 현재 국내 발전소 내 설치된 발전설비 현장조사를 통하여 콘크리트 슬래브에 설치된 발전설비 정착부 앵커볼트의 구조성능을 평가하였다. 대상구조물인 대청댐의 경우, 고정부 설치용으로 선 설치 앵커볼트가 사용되었으며 규격은 M10 J형 선설치 앵커볼트와 M12 J형 선설치 앵커볼트로 시공되었다. ASTM E 488-96 기준을 고려하여 앵커볼트 인발 및 전단 성능평가를 수행하였으며 평가된 앵커볼트의 성능을 국내외 설계기준(KCI 2012, ACI 318, EOTA TR45)과 비교, 분석하였다. 그 결과 M10, M12 J형 선설치 앵커볼트들은 모두 설계하중 값보다 높게 저항하는 것으로 나타나 현재 시공 상태가 설계기준은 충분히 만족하다는 결과를 얻었다. 하지만 이는 실험적 평가를 통한 결과일 뿐이므로 향후 수치해석 평가를 통하여 보다 폭넓게 분석될 필요가 있을 것으로 판단된다.

Keywords

References

  1. Jeon, M. H., "Evaluation of the Concrete Breakout Capacity of the CIP Anchor Bolts under Tension and Shear Loading," Department of Civil Engineering Graduate School of Pusan National University, Pusan, Korea. (in Korean), 2012.
  2. Park, Y. M., Ju, H. J., Kim, D. H., Kang, M. K., and Lee, J. H., Static Shear Resistance of Cast-In Place Anchors in Cracked Concrete, Journal of Korean Society of Steel Construction, Vol. 27 No. 1, February, 2015, pp. 87-97, 2015. DOI http://dx.doi.org/10.7781/kjoss.2015.27.1.087
  3. Choi, D. U., Chun, S. C., "Anchoring to Concrete," Magazine of the Korea Concrete Institue 19(4), pp. 41 - 44 (in Korean), 2007.
  4. KCI ISO 19338:2014,, "Korea Structural Concrete Design Code, Korea Concrete Institute, Seoul, Korea. (in Korean), 2012.
  5. KCI M 10-005, "Anchor Design Methods and Examples for Concrete." Korea Concrete Institute, Seoul, Korea. (in Korean), 2010.
  6. ACI Committee 318, Building Conde Requirements for Structural Concrete(ACI 318-11) and Commentary, Appendix D "Anchoring to Concrete", American Concrete Institute, USA, 2011.
  7. ASTM E 488 - 96, "Standard Test Methods for Strength of Anchors in Concrete and Masonry Elements," American Society for Testing and Materials (ASTM), USA. 2003.
  8. EOTA TR 45 Technical Report, "Design of Metal Anchors For Use In Concrete Under Seismic Actions," European Organisation for technical approvals, EU, 2013.