DOI QR코드

DOI QR Code

Two Low-Loss Large Current Rectifiers Based on Low KVA Rating Wye-Connected Autotransformers

  • Meng, Fangang (School of Electrical Engineering, Harbin Institute of Technology) ;
  • Man, Zhongcheng (School of Electrical Engineering, Harbin Institute of Technology) ;
  • Li, Quanhui (School of Electrical Engineering, Harbin Institute of Technology) ;
  • Gao, Lei (School of Electrical Engineering, Harbin Institute of Technology)
  • 투고 : 2018.04.12
  • 심사 : 2018.09.14
  • 발행 : 2018.11.20

초록

In this paper, two large current rectifiers are proposed based on two wye-connected autotransformers. The requirements of the ideal large current rectifier are analyzed, and it is concluded that the large current rectifier has a higher power density and a higher energy conversion efficiency when it is made up of two three-phase half-wave rectifiers and a wye-connected autotransformer. According to theoretical analysis results, the two novel wye-connected autotransformers are designed to feed two three-phase half-wave rectifiers. The two autotransformers can generate two groups of three-phase voltages with a 60o phase shifting, and their kVA ratings account for 95% and 80% of the load power, respectively. These values are less than those of a double star rectifier at 30% and 46%. From the input mains and output side, the power quality of the proposed rectifiers is the same as that of the double star rectifier. Some experiments validate the correctness of the theoretical analysis.

키워드

참고문헌

  1. J. R. Rodriguez, J. Pontt, C. Silva, E. P. Wiechmann, P. W. Hammond, F. W. Santucci, R. Alvarez, S. Kouro, and P. Lezana, “Large current rectifiers: State of the art and future trends,” IEEE Trans. Ind. Electron., Vol. 52, No. 3, pp. 738-746, Jun. 2005. https://doi.org/10.1109/TIE.2005.843949
  2. F. Carastro, A. Castellazzi, J. Clare, and P. Wheeler, "High-efficiency high-reliability pulsed power converters for industrial processes," IEEE Trans. Power Electron., Vol.27, No.1, pp.37-45, Jan. 2012 https://doi.org/10.1109/TPEL.2011.2155086
  3. W. Yang, S. Yang, and H. Liu, "Micro-arc oxidation flyback switching current pulse unit and combination of multi-units," 2012 IEEE 7th International Power Electronics and Motion Control Conference - ECCE Asia, 2012, pp. 2952-2956.
  4. J. Solanki, N. Frohleke, J. Bocker, and A. Averberg, "High-current variable-voltage rectifiers: State of the art topologies," IET Power Electronics, Vol. 8, No. 6, pp. 1068-1080, 2015. https://doi.org/10.1049/iet-pel.2014.0533
  5. B. Singh, S. Gairola, B. N. Singh, A. Chandra, and K. Alhadded, “Multi-pulse AC-DC converters for improving power quality: a review,” IEEE Trans. Power Electron., Vol. 23, No. 1, pp. 260-281, Jan. 2008. https://doi.org/10.1109/TPEL.2007.911880
  6. P. Aqueveque, E. P. Wiechmann, and R. P. Burgos, "On the efficiency and reliability of high-current rectifiers," IEEE Power Electronics Specialists Conference, pp. 4509-4516, 2008.
  7. R. C. Fernandes, P. S. Oliveira, and F. J. M. Seixas, “A family of autoconnected transformers for 12- and 18-pulse converters-generalization for delta and wye topologies,” IEEE Trans. Power Electron., Vol. 26, No. 7, pp. 2065-2078, Apr. 2011. https://doi.org/10.1109/TPEL.2010.2102773
  8. C. Young, M. Chen, C. Lai, and D. Shih, “A novel active interphase transformer scheme to achieve three-phase line current balance for 24-pulse converter,” IEEE Trans. Power Electron., Vol. 27, No. 4, pp. 1719-1731, Apr. 2012. https://doi.org/10.1109/TPEL.2011.2169684
  9. F. Meng, W. Yang, and S. Yang, “Effect of voltage transformation ratio on the kilovoltampere rating of delta-connected autotransformer for 12-pulse rectifier system,” IEEE Trans. Ind. Electron., Vol. 60, No. 9, pp. 3579-3588, Sep. 2013. https://doi.org/10.1109/TIE.2012.2205351
  10. R. Kalpana, G. Bhuvaneswari, and B. Singh, "Autoconnected transformer based 20-pulse AC-DC converter for telecommunication power supply," IEEE Trans. Ind. Electron., Vol. 60, No. 10, pp. 4178-4190, Oct. 2013. https://doi.org/10.1109/TIE.2012.2210373
  11. F. Meng, L. Gao, S. Yang, and W. Yang, "Effect of single-phasing on multipulse rectifier with active interphase reactor," IEEE Trans. Power Electron., Vol. 30, No. 5, pp.2549-2555, Jan. 2015. https://doi.org/10.1109/TPEL.2014.2345584
  12. A. Gerlando, G. M. Foglia, M. F. Iacchetti, and M. Ubaldini, “Optimized coil arrangement in wound interphase reactors for high-power rectifier systems,” IEEE Trans. Energy Convers., Vol. 29, No. 3, pp. 652-662, Sep. 2014. https://doi.org/10.1109/TEC.2014.2323475
  13. J. Sandoval, H. Krishnamoorthy, P. Enjeti, “Reduced active switch front end multi-pulse rectifier with medium frequency transformer isolation,” IEEE Trans. Power Electron., Vol. 32, No. 10, pp. 7458-7468, Oct. 2017. https://doi.org/10.1109/TPEL.2016.2632717
  14. J. Solanki, N. Frohleke, and J. Bocker, "Implementation of hybrid filter for 12-pulse thyristor rectifier supplying high-current variable-voltage dc load," IEEE Trans. Ind. Electron., Vol. 62, No. 8, pp. 4691-4701, Aug. 2015. https://doi.org/10.1109/TIE.2015.2393833
  15. D. A. Paice, Power Electronic Converter Harmonic Multipulse Methods for Clean Power, New York: IEEE Press, 1996.
  16. J. Wang, S. Yang, and W. Yang, "A low harmonic double wye rectifier with current injection at DC side," International Electronics and Application Conference and Exposition, pp. 909-913, 2014.
  17. J. A. Garcia and G. Moon, "A high-efficiency three-phase zvs pwm converter utilizing a positive double-wye active rectifier stage for server power supply," IEEE Trans. Ind. Electron., Vol.58, No.8, pp. 3317-3329, Aug. 2011. https://doi.org/10.1109/TIE.2010.2090833
  18. J. Ferens, H. D. Hajdinjak, and S. Rhodes, "18-pulse rectification system using a wye-connected autotransformer," U.S. Patent 6650557 B2, Nov. 18, 2003.
  19. B. Singh and S. Gairola, "A fork connected autotransformer based 24-pulse AC-DC converter," India International Conference on Power Electronics 2006, pp. 1391-1396, 2006.
  20. R. Abdollahi and A. Jalilian, "Fork-connected autotransformer based 30-pulse ac-dc converter for power quality improvement," Int. J. Electr. Eng. Informat., Vol. 4, No. 2, 2012.
  21. R. Abdollahi, "Delta/fork-connected transformer-based 36-pulse ac-dc converter for power quality improvement," J. Electr. Contr. Eng., Vol. 2, No. 2, 2012.
  22. B. Liu, S. Duan, and C. Qiu, "Research on 18-pulse rectifier based on a Boost star-fork connected autotransformer," 2011 International Conference on Electrical Machine and Systems, pp. 1-4, 2011.
  23. F. Meng, X. Xu, L. Gao, and C. Cai, “Active harmonic reduction using DC-side current injection applied in a novel large current rectifier based on fork-connected autotransformer,” IEEE Trans. Ind. Electron., Vol. 64, No. 7, pp. 5250-5264, Jul. 2017. https://doi.org/10.1109/TIE.2017.2677302
  24. F. Meng, P. Liu, and L. Gao, “Optimal design of starconnected autotransformer applied to large current rectifier,” IET Electric Power Appl., Vol. 11, No. 1, pp. 80-89, Jan. 2017. https://doi.org/10.1049/iet-epa.2016.0122