DOI QR코드

DOI QR Code

Detection Algorithm and Characteristics on DC Residual Current based on Analysis of IEC60479 Impedance Model for Human Body

IEC60479 인체 임피던스 모델에 근거한 직류누설전류의 특성 및 검출 알고리즘

  • Kim, Yong-Jung (Dept. of Electrical, Electronic and Control Eng., Kongju National University) ;
  • Lee, Jinsung (Dept. of Electrical, Electronic and Control Eng., Intech-FA) ;
  • Kim, Hyosung (Div. of Electrical, Electronic and Control Eng., Kongju National University)
  • Received : 2018.06.06
  • Accepted : 2018.06.28
  • Published : 2018.10.20

Abstract

DC distribution systems has recently taken the spotlight. Concerns over human safety and stability facility are raised in DC distribution systems. Std. IEC 60479 provides basic guidance on "the effects of shock current on human beings and livestock" for use in the establishment of electrical safety requirements and suggests an electrical impedance of the human body. This study analyzes impedance spectrums based on the electrical equivalent impedance circuit for the human body; human body impedances measured by experiments are analyzed below the fundamental frequency (60 Hz). The analysis shows that the equivalent impedance circuit for the human body should be modified at least in low-frequency range below the fundamental frequency (60 Hz). The DC residual current detection method that can classify electric shock accidents of humans and electric leakages of facilities is proposed by applying the analysis result. The detection method is verified by experiments on livestock.

Keywords

References

  1. IEC TR 60755, "General requirements for residual current operated protective devices," 2008.
  2. International Electrotechnical Commission, "Low-voltage electrical installations, Part 1: Fundamental principles, assessment of general characteristics, definitions," 603634-1, IEC, 2005.
  3. D. Salomonsson, L. Sogder, and A. Sannino, “Protection of low-voltage DC microgrids,” IEEE Transactions on Power Delivery, Vol. 24, No. 3, pp. 1045-1053, 2009. https://doi.org/10.1109/TPWRD.2009.2016622
  4. M. Noritake, T. Iino, A. Fukui, K. Hirose, and M. Yamasaki, "A study of the safety of the DC 400 V distribution system," IEEE INTELEC 31st International, pp. 1-6, Oct. 2009.
  5. W. K. Lee, B. H. Han, H. M. Jung, and H. S. Kim, "Development of residual current detector for DC distribution system," in Korean Power Electronics Annual Conference, pp. 53-54, Jul. 2013.
  6. D. W. Kim, Y. B. Lim, S. I. Lee, J. H. Kim, and D. C. Kang, "Prevention techniques of electrical fire and electrical shock caused by leakage current," Journal of the Korean Institute of Illuminating and Electrical installation Engineers, Vol. 27, pp. 82-87, Jun. 2013.
  7. H. J. Kim, J. B. Baek, G. S. Seo, K. S. Choi, H. S. Bae, and B. H. Cho, "Research on earth leakage circuit breaker for DC-based green home," in Korean Power Electronics Annual Conference, pp. 76-77, Nov. 2010.
  8. W. K. Lee, and H. S. Kim, "Development of residual current detector for protecting human and equipment of TN grounding systems in DC power distribution systems," in Korean Power Electronics Annual Conference, pp. 64-65, Nov. 2014.
  9. S. M. M. Alavi, A. Mahdi, S. J. Payne, and D. A. Howey, “Identifiability of generalized randles circuit models,” IEEE Transactions on Control Systems Technology, Vol. 25, No. 6, pp. 2112-2120, Nov. 2017. https://doi.org/10.1109/TCST.2016.2635582
  10. International Electrotechnical Commission, "Effects of current on human beings and livestock, Part 1: General Aspects," 60479-1, IEC, 2005.
  11. IEC 60479, "Residual current protective device dependent or independent of line voltage," 2008.