BEMS 데이터를 활용한 도서관 건물의 운전현황 분석 -준공 초기단계의 건물 에너지 성능 평가

An Operation Status Analysis of Library Building using BEMS Data; Energy Performance Evaluation on Initial Stage of Completion

  • 박성철 (경상대학교 건축공학과 대학원) ;
  • 하주완 (경상대학교 건축공학과 대학원) ;
  • 김환용 (경상대학교 건축공학과) ;
  • 송영학 (경상대학교 건축공학과)
  • Park, Seong-cheol (Department of Architectural Engineering, Gyeongsang National University) ;
  • Ha, Ju-wan (Department of Architectural Engineering, Gyeongsang National University) ;
  • Kim, Hwan-yong (Department of Architectural Engineering, ERI, Gyeongsang National University) ;
  • Song, Young-hak (Department of Architectural Engineering, ERI, Gyeongsang National University)
  • 투고 : 2018.12.14
  • 심사 : 2018.12.24
  • 발행 : 2018.12.31

초록

Energy consumption savings in buildings should be reviewed in diverse areas such as air conditioning system and lighting responsible for cooling and heating, and energy management systems such as BAS (Building Automation System) and BEMS (Building Energy Management System) are introduced to improve energy consumption efficiency and to promote economic control of related facilities by integrated management of energy generated and consumption in buildings. The measured building of this study uses regenerative geothermal system. Measured values of heat pump and system COP were 4.7 and 4.2 respectively, and they were found to be higher 11.9% and 23.5% than rated values. As a result of analyzing the air conditioning and lighting energy from the first floor to the fourth floor performing the air conditioning, the second and third floors, which have a high frequency of use, are compared with the first and fourth floors 50% higher energy consumption ratio. On the other hand, the general heat storage system uses the nighttime power of the previous day to store heat and use it the next day. The total number of days of abnormal operation during the summer season is 61 days. The electricity cost corresponding to the abnormal operation is 1,840,641 KRW, and the normal operation using the nighttime power is 1,363,561 KRW, which is difference of 477,080 KRW, 35% increase in cost. We will utilize it as the main data of BEMS through analysis of winter operation characteristics as well as summer operation characteristics.

키워드

과제정보

연구 과제 주관 기관 : 국토교통부

참고문헌

  1. 박성철, 이태원, 김환용, 송영학. (2017). 건물 HVAC의 에너지사용량 변동과 실온변화를 통한 고장발견진단 알고리즘 개발 연구. 한국건축친환경설비학회 논문집, 11(6), 499-516.
  2. 안병천. (2008). 건물에너지절약을 위한 유지관리 및 제어. 대한설비공학회 설비저널, 37(11), 1.
  3. 이경호, 최병윤, 주용진, 이상렬, 한승호. (2000). 예측 냉방부하를 이용한 빙축열시스템의 최적 운전계획. 공기조화냉동공학회, 12(11), 982-993.
  4. 이대영, 김사량, 김현정, 김동선, 박준석, 임병찬. (2017). 설비공학 분야의 최근 연구 동향 : 2016년 학회지 논문에 대한 종합적 고찰. 대한설비공학회 설비공학논문집, 29(6), 327-340.
  5. 신주봉. (2018). 아산중앙도서관-패시브 건축으로 맛을 내다. 한국건축친환경설비학회 2018 추계학술발표대회 특별강연.
  6. 이상준. (2014). 건물 냉난방 시스템의 지속적인 커미셔닝을 위한 주요 성능 인자들의 실시간 고장진단방법론에 관한 연구. 석사학위논문. 전주대학교. 대한민국.
  7. 에너지경제연구원. (2014). 2014년도 에너지 총 조사 보고서. 산업통상자원부.
  8. Ha, J.-W., Park, K.-S., Kim, H.-Y., Song, Y.-H. (2018). A Study on Zero Energy Building Verification with Measuring and Model-based Simulation in Exhibition Building. Architectural Research, 20(3), 93-102. https://doi.org/10.5659/AIKAR.2018.20.3.93